Case study on the effectiveness of condition monitoring techniques for fault diagnosis of pumps in thermal power plant

Caneon Kurien, A. Srivastava
{"title":"Case study on the effectiveness of condition monitoring techniques for fault diagnosis of pumps in thermal power plant","authors":"Caneon Kurien, A. Srivastava","doi":"10.2478/mme-2019-0010","DOIUrl":null,"url":null,"abstract":"Abstract A case study was carried out to investigate the effectiveness of condition monitoring techniques in the early failure detection of pumps in a thermal power plant. Various condition monitoring techniques used in this case study involved vibration analysis, motor current signature analysis, noise monitoring and wear debris analysis. These techniques were applied on the three pumps, namely boiler feed water pump, auxiliary cooling water pump and condensate extraction pump, which have to work continuously for the operation of the thermal power plant. Vibration analysis of the auxiliary cooling water pump showed that there is a rising trend in the acceleration values at its driving and non-driving end indicating the deterioration of bearings. Motor current index range of all the pumps was found to be within acceptable limits. Wear debris analysis of lubricant in the hydraulic coupling of boiler feed water pump indicated the presence of sand, dirt and low alloy steel sliding wear particles in it. Condition monitoring techniques have been proved to be an effective technique in early failure detection of pumps.","PeriodicalId":53557,"journal":{"name":"Mechanics and Mechanical Engineering","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"2019-06-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Mechanics and Mechanical Engineering","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.2478/mme-2019-0010","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"Engineering","Score":null,"Total":0}
引用次数: 2

Abstract

Abstract A case study was carried out to investigate the effectiveness of condition monitoring techniques in the early failure detection of pumps in a thermal power plant. Various condition monitoring techniques used in this case study involved vibration analysis, motor current signature analysis, noise monitoring and wear debris analysis. These techniques were applied on the three pumps, namely boiler feed water pump, auxiliary cooling water pump and condensate extraction pump, which have to work continuously for the operation of the thermal power plant. Vibration analysis of the auxiliary cooling water pump showed that there is a rising trend in the acceleration values at its driving and non-driving end indicating the deterioration of bearings. Motor current index range of all the pumps was found to be within acceptable limits. Wear debris analysis of lubricant in the hydraulic coupling of boiler feed water pump indicated the presence of sand, dirt and low alloy steel sliding wear particles in it. Condition monitoring techniques have been proved to be an effective technique in early failure detection of pumps.
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
状态监测技术在火电厂水泵故障诊断中的有效性案例研究
摘要通过一个案例研究,探讨了状态监测技术在火电厂水泵早期故障检测中的有效性。本案例研究中使用的各种状态监测技术包括振动分析、电机电流特征分析、噪声监测和磨损碎片分析。这些技术被应用于三台泵上,即锅炉给水泵、辅助冷却水泵和冷凝水抽取泵,它们必须连续工作才能满足火力发电厂的运行。对辅助冷却水泵的振动分析表明,其驱动端和非驱动端的加速度值有上升趋势,表明轴承的老化。发现所有泵的电机电流指数范围都在可接受的范围内。通过对锅炉给水泵液力耦合器润滑油磨损碎屑的分析,发现其内部存在砂、污垢和低合金钢滑动磨损颗粒,状态监测技术已被证明是早期检测水泵故障的有效技术。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 去求助
来源期刊
Mechanics and Mechanical Engineering
Mechanics and Mechanical Engineering Engineering-Automotive Engineering
自引率
0.00%
发文量
0
期刊最新文献
The use of FEM to evaluate the influence of logarithmic correction parameters of roller generators on the axle box bearing life Experimental and finite element analysis of slope stability treated by lime milk (case of El Amir Abdelkader embankment) Numerical study of coupled oscillator system using the classical Euler-Lagrange equations Experimental investigation of air pressure drops on different mesh layers using air filter performance test rig Effect of passive coupling on seismic interaction optimization of adjacent structures
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1