{"title":"水轮发电机直流斜坡、极化和去极化试验比较","authors":"C. Hudon, N. Amyot, S. Bernier, É. David, M. Essalihi","doi":"10.1109/EIC.2018.8481087","DOIUrl":null,"url":null,"abstract":"Hydro-Quebec has started carrying out Polarization and Depolarization Current measurements (PDC) more than 20 years ago. A Direct Current Ramp Test (DCRT) apparatus has also been built in house in the early 2000's and since 2012 systematic measurements with both tests are prescribed to be done every 6 years on every one of our 350 generators. An extensive comparison of both types of electric tests has been done to determine the influence of factors such as temperature and humidity, type of ground wall insulation and the nature of the stress grading coating on the measured current. The DCRT and PDC test procedures are such that they are not always giving the same diagnosis and sometimes this can easily be explained, but in some case more in depth analysis is required. A comparison of the results of both types of tests was done and the main features and limits are presented herein.","PeriodicalId":184139,"journal":{"name":"2018 IEEE Electrical Insulation Conference (EIC)","volume":"21 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2018-06-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"3","resultStr":"{\"title\":\"Comparison of DC Ramp and Polarization and Depolarisation Tests on Hydrogenerators\",\"authors\":\"C. Hudon, N. Amyot, S. Bernier, É. David, M. Essalihi\",\"doi\":\"10.1109/EIC.2018.8481087\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Hydro-Quebec has started carrying out Polarization and Depolarization Current measurements (PDC) more than 20 years ago. A Direct Current Ramp Test (DCRT) apparatus has also been built in house in the early 2000's and since 2012 systematic measurements with both tests are prescribed to be done every 6 years on every one of our 350 generators. An extensive comparison of both types of electric tests has been done to determine the influence of factors such as temperature and humidity, type of ground wall insulation and the nature of the stress grading coating on the measured current. The DCRT and PDC test procedures are such that they are not always giving the same diagnosis and sometimes this can easily be explained, but in some case more in depth analysis is required. A comparison of the results of both types of tests was done and the main features and limits are presented herein.\",\"PeriodicalId\":184139,\"journal\":{\"name\":\"2018 IEEE Electrical Insulation Conference (EIC)\",\"volume\":\"21 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2018-06-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"3\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2018 IEEE Electrical Insulation Conference (EIC)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/EIC.2018.8481087\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2018 IEEE Electrical Insulation Conference (EIC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/EIC.2018.8481087","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3

摘要

Hydro-Quebec早在20多年前就开始进行极化和去极化电流测量(PDC)。直流斜坡测试(DCRT)设备也在2000年初在内部建造,自2012年以来,我们的350台发电机每6年对这两项测试进行系统测量。对两种类型的电气测试进行了广泛的比较,以确定温度和湿度、地墙绝缘类型和应力分级涂层的性质等因素对测量电流的影响。DCRT和PDC的测试程序并不总是给出相同的诊断,有时这很容易解释,但在某些情况下,需要更深入的分析。对两种试验的结果进行了比较,介绍了两种试验的主要特点和局限性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Comparison of DC Ramp and Polarization and Depolarisation Tests on Hydrogenerators
Hydro-Quebec has started carrying out Polarization and Depolarization Current measurements (PDC) more than 20 years ago. A Direct Current Ramp Test (DCRT) apparatus has also been built in house in the early 2000's and since 2012 systematic measurements with both tests are prescribed to be done every 6 years on every one of our 350 generators. An extensive comparison of both types of electric tests has been done to determine the influence of factors such as temperature and humidity, type of ground wall insulation and the nature of the stress grading coating on the measured current. The DCRT and PDC test procedures are such that they are not always giving the same diagnosis and sometimes this can easily be explained, but in some case more in depth analysis is required. A comparison of the results of both types of tests was done and the main features and limits are presented herein.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Experimental Research on Flashover Characteristics of Insulator with N2 Dissolved Gas Analysis (DGA) of Arc Discharge Fault in Transformer Insulation Oils (Ester and Mineral Oils) Nonparametric Kernel Density Estimation Model of Transformer Health Based on Dissolved Gases in Oil Experimental validation of a moisture sensor for cellulosic insulation of power transformers Development Process of Vibration Sparking Erosion on Stator Bars
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1