{"title":"博物馆室内湿度对空气和装饰表面微生物污染状况的影响:以Wilanow国王约翰三世宫殿博物馆17世纪纪念碑为例(波兰华沙)","authors":"B. Andres, I. Betlej, Wojciech Bagiński","doi":"10.3390/air1020009","DOIUrl":null,"url":null,"abstract":"This article is a case study of museum premises at the Museum of King John III’s Palace at Wilanow (Warsaw, Poland), wetted as a result of a failure of the water supply system to the air conditioning unit located in the attic of the building. As a result of flooding, discoloration and cracks appeared on the plaster and stucco decoration of the ceiling, located mainly in the central part of the ceiling of the King’s Library. The paintings (plafonds) mounted on the ceiling of this room also became damp. The article analyzes the microbiological contamination of air and damp paintings in the context of promptly proceeding with the drying of damp building partitions. The obtained results of microbiological air pollution in the flooded rooms were significantly lower than the permissible values recommended by Interdepartmental Commission for Maximum Admissible Concentrations and Intensities for Agents Harmful to Health in the Working Environment. In the King’s Library, i.e., the room with the dampest plaster and stucco as a result of the accident, the concentration of mold spores in the air was only 15 cfu/m3. This means that the immediate commencement of intensive drying of the building partitions (walls, ceilings with wooden floors) brought very good results. The rapid reduction in the moisture of the building partitions contributed to the worsening conditions for the development of microorganisms, which can have an adverse effect on wooden building partitions, plaster, stucco, etc.","PeriodicalId":13529,"journal":{"name":"Indoor air","volume":null,"pages":null},"PeriodicalIF":4.3000,"publicationDate":"2023-04-24","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Influence of Moisture in Museum Rooms on the State of Microbial Contamination of the Air and Decoration Surfaces: The Example of a 17th Century Monument in the Museum of King John III’s Palace at Wilanow (Warsaw, Poland)\",\"authors\":\"B. Andres, I. Betlej, Wojciech Bagiński\",\"doi\":\"10.3390/air1020009\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"This article is a case study of museum premises at the Museum of King John III’s Palace at Wilanow (Warsaw, Poland), wetted as a result of a failure of the water supply system to the air conditioning unit located in the attic of the building. As a result of flooding, discoloration and cracks appeared on the plaster and stucco decoration of the ceiling, located mainly in the central part of the ceiling of the King’s Library. The paintings (plafonds) mounted on the ceiling of this room also became damp. The article analyzes the microbiological contamination of air and damp paintings in the context of promptly proceeding with the drying of damp building partitions. The obtained results of microbiological air pollution in the flooded rooms were significantly lower than the permissible values recommended by Interdepartmental Commission for Maximum Admissible Concentrations and Intensities for Agents Harmful to Health in the Working Environment. In the King’s Library, i.e., the room with the dampest plaster and stucco as a result of the accident, the concentration of mold spores in the air was only 15 cfu/m3. This means that the immediate commencement of intensive drying of the building partitions (walls, ceilings with wooden floors) brought very good results. The rapid reduction in the moisture of the building partitions contributed to the worsening conditions for the development of microorganisms, which can have an adverse effect on wooden building partitions, plaster, stucco, etc.\",\"PeriodicalId\":13529,\"journal\":{\"name\":\"Indoor air\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":4.3000,\"publicationDate\":\"2023-04-24\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Indoor air\",\"FirstCategoryId\":\"93\",\"ListUrlMain\":\"https://doi.org/10.3390/air1020009\",\"RegionNum\":2,\"RegionCategory\":\"环境科学与生态学\",\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q1\",\"JCRName\":\"CONSTRUCTION & BUILDING TECHNOLOGY\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Indoor air","FirstCategoryId":"93","ListUrlMain":"https://doi.org/10.3390/air1020009","RegionNum":2,"RegionCategory":"环境科学与生态学","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"CONSTRUCTION & BUILDING TECHNOLOGY","Score":null,"Total":0}
引用次数: 0

摘要

本文是对位于波兰华沙Wilanow的国王约翰三世宫殿博物馆馆舍的案例研究,该博物馆由于位于建筑物阁楼的空调机组供水系统故障而潮湿。由于淹水,天花板的灰泥装饰出现了变色和裂缝,主要位于国王图书馆天花板的中央部分。挂在这个房间天花板上的画(画板)也受潮了。文章分析了在及时进行潮湿建筑隔墙干燥的情况下,空气和潮湿墙面的微生物污染。在被淹的房间中获得的微生物空气污染结果明显低于工作环境中有害物质最大允许浓度和强度部门间委员会建议的允许值。在国王图书馆,也就是由于事故造成的最潮湿的灰泥和灰泥的房间,空气中霉菌孢子的浓度仅为15 cfu/m3。这意味着立即开始对建筑分区(墙壁,带有木地板的天花板)进行密集干燥带来了非常好的效果。建筑隔断水分的迅速减少导致微生物生长条件的恶化,这可能对木质建筑隔断、灰泥、灰泥等产生不利影响。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Influence of Moisture in Museum Rooms on the State of Microbial Contamination of the Air and Decoration Surfaces: The Example of a 17th Century Monument in the Museum of King John III’s Palace at Wilanow (Warsaw, Poland)
This article is a case study of museum premises at the Museum of King John III’s Palace at Wilanow (Warsaw, Poland), wetted as a result of a failure of the water supply system to the air conditioning unit located in the attic of the building. As a result of flooding, discoloration and cracks appeared on the plaster and stucco decoration of the ceiling, located mainly in the central part of the ceiling of the King’s Library. The paintings (plafonds) mounted on the ceiling of this room also became damp. The article analyzes the microbiological contamination of air and damp paintings in the context of promptly proceeding with the drying of damp building partitions. The obtained results of microbiological air pollution in the flooded rooms were significantly lower than the permissible values recommended by Interdepartmental Commission for Maximum Admissible Concentrations and Intensities for Agents Harmful to Health in the Working Environment. In the King’s Library, i.e., the room with the dampest plaster and stucco as a result of the accident, the concentration of mold spores in the air was only 15 cfu/m3. This means that the immediate commencement of intensive drying of the building partitions (walls, ceilings with wooden floors) brought very good results. The rapid reduction in the moisture of the building partitions contributed to the worsening conditions for the development of microorganisms, which can have an adverse effect on wooden building partitions, plaster, stucco, etc.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
Indoor air
Indoor air 环境科学-工程:环境
CiteScore
10.80
自引率
10.30%
发文量
175
审稿时长
3 months
期刊介绍: The quality of the environment within buildings is a topic of major importance for public health. Indoor Air provides a location for reporting original research results in the broad area defined by the indoor environment of non-industrial buildings. An international journal with multidisciplinary content, Indoor Air publishes papers reflecting the broad categories of interest in this field: health effects; thermal comfort; monitoring and modelling; source characterization; ventilation and other environmental control techniques. The research results present the basic information to allow designers, building owners, and operators to provide a healthy and comfortable environment for building occupants, as well as giving medical practitioners information on how to deal with illnesses related to the indoor environment.
期刊最新文献
Assessment on the Personal Exposure Risk Associated With Real-Time Indoor PM2.5 in Different Microenvironments Shared Risk Volatile Organic Compounds Among Chronic Respiratory Diseases: Mediation Effects of System Inflammation Comparison of Real-Time PM2.5 Between Rural and Urban Homes in Southwest China Based on Field Measurement: Insight Into the Cooking Activity Contribution Investigation of Indoor Airborne Bacteria in the Severe Cold Region in China: Genera, Levels, and the Influencing Factors of Concentration Patterns of Resident Activity and Their Impact on Environmental Parameters in Residential Apartments: Case Study and Implications for Design and Management
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1