用多棒和木炭作土壤处理提高配电变电所接地电阻

N. M. Karmiathi, Putu Martin Puja Yoga
{"title":"用多棒和木炭作土壤处理提高配电变电所接地电阻","authors":"N. M. Karmiathi, Putu Martin Puja Yoga","doi":"10.31940/matrix.v13i1.33-41","DOIUrl":null,"url":null,"abstract":"The grounding system plays the important role in securing the electric power system. Low grounding resistance ensures the proper operation of the grounding system. The lower the grounding resistance value, the easier current flow through the earth without any obstacles then prevents equipment from being damaged or causing the injury of personnel. According to the PUIL 2000 standard, grounding resistance should be less than 5Ω. Methods that can be performed to reduce grounding resistance are increasing the length and diameter of the grounding rod, using multiple rods, and treating the soil to reduce its resistivity. In this study, we would like to improve the grounding system of the KA2317 distribution substation located at Mertasari, Jimbaran in South Kuta, Bali which has a grounding resistance of 8.1Ω (more than 5Ω). The method that was applied in this study was grounding improvement by adding an electrode rod and adding wood charcoal to reduce soil resistivity. At the end of the study, grounding resistance can be reduced from 8.1Ω to 1.9 Ω or improved by 76.6%.","PeriodicalId":31964,"journal":{"name":"Matrix Jurnal Manajemen Teknologi dan Informatika","volume":"44 1","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2023-03-30","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment\",\"authors\":\"N. M. Karmiathi, Putu Martin Puja Yoga\",\"doi\":\"10.31940/matrix.v13i1.33-41\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The grounding system plays the important role in securing the electric power system. Low grounding resistance ensures the proper operation of the grounding system. The lower the grounding resistance value, the easier current flow through the earth without any obstacles then prevents equipment from being damaged or causing the injury of personnel. According to the PUIL 2000 standard, grounding resistance should be less than 5Ω. Methods that can be performed to reduce grounding resistance are increasing the length and diameter of the grounding rod, using multiple rods, and treating the soil to reduce its resistivity. In this study, we would like to improve the grounding system of the KA2317 distribution substation located at Mertasari, Jimbaran in South Kuta, Bali which has a grounding resistance of 8.1Ω (more than 5Ω). The method that was applied in this study was grounding improvement by adding an electrode rod and adding wood charcoal to reduce soil resistivity. At the end of the study, grounding resistance can be reduced from 8.1Ω to 1.9 Ω or improved by 76.6%.\",\"PeriodicalId\":31964,\"journal\":{\"name\":\"Matrix Jurnal Manajemen Teknologi dan Informatika\",\"volume\":\"44 1\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2023-03-30\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Matrix Jurnal Manajemen Teknologi dan Informatika\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.31940/matrix.v13i1.33-41\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Matrix Jurnal Manajemen Teknologi dan Informatika","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.31940/matrix.v13i1.33-41","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

接地系统在保证电力系统安全运行中起着重要的作用。低接地电阻是接地系统正常运行的重要保证。接地电阻值越小,电流越容易畅通无阻地通过大地,从而避免损坏设备或造成人员伤害。根据PUIL 2000标准,接地电阻应小于5Ω。减少接地电阻的方法包括增加接地棒的长度和直径、使用多根接地棒、对土壤进行处理以降低其电阻率。本研究拟对位于巴厘岛南库塔金巴兰Mertasari的KA2317配电变电站的接地系统进行改进,该变电站的接地电阻为8.1Ω(大于5Ω)。本研究采用的方法是通过添加电极棒和添加木炭来降低土壤电阻率来改善接地。研究结束时,接地电阻可从8.1Ω降低到1.9 Ω或提高76.6%。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
The grounding resistance improvement of distribution substation using multiple rods and wood charcoal as soil treatment
The grounding system plays the important role in securing the electric power system. Low grounding resistance ensures the proper operation of the grounding system. The lower the grounding resistance value, the easier current flow through the earth without any obstacles then prevents equipment from being damaged or causing the injury of personnel. According to the PUIL 2000 standard, grounding resistance should be less than 5Ω. Methods that can be performed to reduce grounding resistance are increasing the length and diameter of the grounding rod, using multiple rods, and treating the soil to reduce its resistivity. In this study, we would like to improve the grounding system of the KA2317 distribution substation located at Mertasari, Jimbaran in South Kuta, Bali which has a grounding resistance of 8.1Ω (more than 5Ω). The method that was applied in this study was grounding improvement by adding an electrode rod and adding wood charcoal to reduce soil resistivity. At the end of the study, grounding resistance can be reduced from 8.1Ω to 1.9 Ω or improved by 76.6%.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
13
审稿时长
24 weeks
期刊最新文献
Optimizing transaction data performance in database management systems Library apps to improve the digitization of Sekolah Penggerak Program Literature review: visible light communication system business model scheme for telecommunication business in Indonesia Determination of the best rule-based analysis results from the comparison of the Fp-Growth, Apriori, and TPQ-Apriori Algorithms for recommendation systems The empirical study of Joomla CMS map extension and location performance
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1