{"title":"太平洋Intertie高压直流换流站绝缘子涂层的长期评价","authors":"B. Almgren, B. Jacobson, Dong Wu","doi":"10.1109/ELINSL.2002.995932","DOIUrl":null,"url":null,"abstract":"Since the Pacific HVDC Intertie was commissioned in 1970, measures have been taken to prevent pollution flashovers of the outdoor insulators at the Sylmar West Converter Station. In April 1991, a research program was started with a view to finding the optimum type and layer thickness for different insulator coatings available at the time. Various types and thicknesses of insulator coatings and one type of massive silicone rubber plate were installed, together with bare porcelain plates as references, on test racks at the station. Annual inspections were performed the first three years and the last one after 10 years of exposure. The following conclusions may be drawn from the research program. Most plates coated with silicone grease of three different types and in three different layer thicknesses were still water repellent after 10 years of exposure. The massive silicone rubber plate and one out of three RTV coatings also showed good performance, while the other two types of silicone rubber coating had become wetter. Silicone greases performed better than other coatings in this test. A thin layer of coating, e.g. 0.5-1 mm, is sufficient for good long-term performance.","PeriodicalId":10532,"journal":{"name":"Conference Record of the the 2002 IEEE International Symposium on Electrical Insulation (Cat. No.02CH37316)","volume":"9 1","pages":"285-289"},"PeriodicalIF":0.0000,"publicationDate":"2002-04-07","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Long term evaluation of insulator coatings at one of the Pacific Intertie HVDC converter stations\",\"authors\":\"B. Almgren, B. Jacobson, Dong Wu\",\"doi\":\"10.1109/ELINSL.2002.995932\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Since the Pacific HVDC Intertie was commissioned in 1970, measures have been taken to prevent pollution flashovers of the outdoor insulators at the Sylmar West Converter Station. In April 1991, a research program was started with a view to finding the optimum type and layer thickness for different insulator coatings available at the time. Various types and thicknesses of insulator coatings and one type of massive silicone rubber plate were installed, together with bare porcelain plates as references, on test racks at the station. Annual inspections were performed the first three years and the last one after 10 years of exposure. The following conclusions may be drawn from the research program. Most plates coated with silicone grease of three different types and in three different layer thicknesses were still water repellent after 10 years of exposure. The massive silicone rubber plate and one out of three RTV coatings also showed good performance, while the other two types of silicone rubber coating had become wetter. Silicone greases performed better than other coatings in this test. A thin layer of coating, e.g. 0.5-1 mm, is sufficient for good long-term performance.\",\"PeriodicalId\":10532,\"journal\":{\"name\":\"Conference Record of the the 2002 IEEE International Symposium on Electrical Insulation (Cat. No.02CH37316)\",\"volume\":\"9 1\",\"pages\":\"285-289\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2002-04-07\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Conference Record of the the 2002 IEEE International Symposium on Electrical Insulation (Cat. No.02CH37316)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ELINSL.2002.995932\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Conference Record of the the 2002 IEEE International Symposium on Electrical Insulation (Cat. No.02CH37316)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ELINSL.2002.995932","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

自1970年太平洋高压直流电网投入使用以来,已采取措施防止Sylmar West换流站室外绝缘子的污染闪络。1991年4月,一项研究计划启动,目的是为当时可用的不同绝缘体涂层寻找最佳类型和层厚度。在该站的测试架上安装了各种类型和厚度的绝缘子涂层和一种大型硅橡胶板,并以裸瓷板为参考。前三年进行年度检查,10年后进行最后一次检查。从研究计划中可以得出以下结论。大多数涂有三种不同类型和三种不同层厚度的硅脂的板在暴露10年后仍然具有拒水性。块状硅橡胶板和三分之一的RTV涂层也表现出良好的性能,而其他两种硅橡胶涂层则变得更湿。硅脂在该测试中表现优于其他涂层。一层薄的涂层,例如0.5-1毫米,足以保持良好的长期性能。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Long term evaluation of insulator coatings at one of the Pacific Intertie HVDC converter stations
Since the Pacific HVDC Intertie was commissioned in 1970, measures have been taken to prevent pollution flashovers of the outdoor insulators at the Sylmar West Converter Station. In April 1991, a research program was started with a view to finding the optimum type and layer thickness for different insulator coatings available at the time. Various types and thicknesses of insulator coatings and one type of massive silicone rubber plate were installed, together with bare porcelain plates as references, on test racks at the station. Annual inspections were performed the first three years and the last one after 10 years of exposure. The following conclusions may be drawn from the research program. Most plates coated with silicone grease of three different types and in three different layer thicknesses were still water repellent after 10 years of exposure. The massive silicone rubber plate and one out of three RTV coatings also showed good performance, while the other two types of silicone rubber coating had become wetter. Silicone greases performed better than other coatings in this test. A thin layer of coating, e.g. 0.5-1 mm, is sufficient for good long-term performance.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
After-installation test of HV extruded cable insulation Experimental investigation into the thermal-ageing of Kraft paper and mineral insulating oil Enhanced online PD evaluation on power transformers using wavelet techniques and frequency rejection filter for noise suppression On-line PD detection, requirements for practical use PD site location in distribution power cables
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1