{"title":"电力变压器中PD的超高频检测:干扰的影响","authors":"A. Cavallini, C. G. A. Ramos, G. Montanari, H. Saad, M. Tozzi","doi":"10.1109/CEIDP.2011.6232688","DOIUrl":null,"url":null,"abstract":"Ultra-high frequency partial discharge sensors are often deemed to be immune to disturbance, i.e., signals generated by partial discharge sources outside the transformer itself. In this paper, the above claim is investigated resorting to both computer simulations and experimental tests. The results indicate that corona from power lines in proximity of a transformer, or surface discharges on the surface of bushings can provide signals that are comparable with those generated by PD sources. These findings suggest that care must be taken when evaluating data coming from this type of sensors, as false alarms can be obtained.","PeriodicalId":6317,"journal":{"name":"2011 Annual Report Conference on Electrical Insulation and Dielectric Phenomena","volume":"35 1","pages":"436-439"},"PeriodicalIF":0.0000,"publicationDate":"2011-10-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"5","resultStr":"{\"title\":\"UHF detection of PD in power transformers: The influence of disturbances\",\"authors\":\"A. Cavallini, C. G. A. Ramos, G. Montanari, H. Saad, M. Tozzi\",\"doi\":\"10.1109/CEIDP.2011.6232688\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Ultra-high frequency partial discharge sensors are often deemed to be immune to disturbance, i.e., signals generated by partial discharge sources outside the transformer itself. In this paper, the above claim is investigated resorting to both computer simulations and experimental tests. The results indicate that corona from power lines in proximity of a transformer, or surface discharges on the surface of bushings can provide signals that are comparable with those generated by PD sources. These findings suggest that care must be taken when evaluating data coming from this type of sensors, as false alarms can be obtained.\",\"PeriodicalId\":6317,\"journal\":{\"name\":\"2011 Annual Report Conference on Electrical Insulation and Dielectric Phenomena\",\"volume\":\"35 1\",\"pages\":\"436-439\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2011-10-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"5\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2011 Annual Report Conference on Electrical Insulation and Dielectric Phenomena\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/CEIDP.2011.6232688\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2011 Annual Report Conference on Electrical Insulation and Dielectric Phenomena","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CEIDP.2011.6232688","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
UHF detection of PD in power transformers: The influence of disturbances
Ultra-high frequency partial discharge sensors are often deemed to be immune to disturbance, i.e., signals generated by partial discharge sources outside the transformer itself. In this paper, the above claim is investigated resorting to both computer simulations and experimental tests. The results indicate that corona from power lines in proximity of a transformer, or surface discharges on the surface of bushings can provide signals that are comparable with those generated by PD sources. These findings suggest that care must be taken when evaluating data coming from this type of sensors, as false alarms can be obtained.