{"title":"由于CT/VT模块故障导致T60继电器差动保护功能误操作","authors":"O. B. Elkhidir, I. El-Amin","doi":"10.1109/ICCCEEE.2018.8515870","DOIUrl":null,"url":null,"abstract":"T60 relay is one of the new digital relays has been designed to meet the requirements of high sensitivity, reliability and high speed. This development led to notable simplification in transformer differential protection 87T function by reducing cost, cabling and auxiliary equipment. However, still miss-operation cases in transformer differential protection can occur from time to time. This paper reports on two unwanted-operation cases of transformer differential protection happened in Garie power plant in Sudan. In the both cases, failures in the CT/VT module of T60 relays cause unwanted operation of the protection system. These failures could be a result of aging, problems in DC power supply or from the design of these modules. More investigations are needed to find the roots of these failures. In the both cases, the failures are hidden type in which the relay will not operate unless unusual event has happened. The failures could have been detected and removed, if the preventive maintenance was effective. In order to insure reliability and sensitivity of the relays, preventive maintenance should take place from time to time.","PeriodicalId":6567,"journal":{"name":"2018 International Conference on Computer, Control, Electrical, and Electronics Engineering (ICCCEEE)","volume":"12 1","pages":"1-6"},"PeriodicalIF":0.0000,"publicationDate":"2018-08-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Unwanted operation of differential protection function in T60 relays due to failures in CT/VT modules\",\"authors\":\"O. B. Elkhidir, I. El-Amin\",\"doi\":\"10.1109/ICCCEEE.2018.8515870\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"T60 relay is one of the new digital relays has been designed to meet the requirements of high sensitivity, reliability and high speed. This development led to notable simplification in transformer differential protection 87T function by reducing cost, cabling and auxiliary equipment. However, still miss-operation cases in transformer differential protection can occur from time to time. This paper reports on two unwanted-operation cases of transformer differential protection happened in Garie power plant in Sudan. In the both cases, failures in the CT/VT module of T60 relays cause unwanted operation of the protection system. These failures could be a result of aging, problems in DC power supply or from the design of these modules. More investigations are needed to find the roots of these failures. In the both cases, the failures are hidden type in which the relay will not operate unless unusual event has happened. The failures could have been detected and removed, if the preventive maintenance was effective. In order to insure reliability and sensitivity of the relays, preventive maintenance should take place from time to time.\",\"PeriodicalId\":6567,\"journal\":{\"name\":\"2018 International Conference on Computer, Control, Electrical, and Electronics Engineering (ICCCEEE)\",\"volume\":\"12 1\",\"pages\":\"1-6\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2018-08-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2018 International Conference on Computer, Control, Electrical, and Electronics Engineering (ICCCEEE)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICCCEEE.2018.8515870\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2018 International Conference on Computer, Control, Electrical, and Electronics Engineering (ICCCEEE)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICCCEEE.2018.8515870","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

T60继电器是为满足高灵敏度、高可靠性和高速度的要求而设计的一种新型数字继电器。这一发展通过降低成本、电缆和辅助设备,使变压器差动保护87T功能显著简化。但是,在变压器差动保护中仍时有发生误动的情况。本文报道了苏丹加里电厂发生的两起变压器差动保护非正常运行案例。在这两种情况下,T60继电器的CT/VT模块故障导致保护系统不必要的操作。这些故障可能是由于老化,直流电源问题或这些模块的设计。需要更多的调查来找到这些失败的根源。在这两种情况下,故障都是隐性故障,除非发生异常事件,否则继电器不会运行。如果预防性维护是有效的,故障是可以被检测和消除的。为了保证继电器的可靠性和灵敏度,应不时地进行预防性维护。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Unwanted operation of differential protection function in T60 relays due to failures in CT/VT modules
T60 relay is one of the new digital relays has been designed to meet the requirements of high sensitivity, reliability and high speed. This development led to notable simplification in transformer differential protection 87T function by reducing cost, cabling and auxiliary equipment. However, still miss-operation cases in transformer differential protection can occur from time to time. This paper reports on two unwanted-operation cases of transformer differential protection happened in Garie power plant in Sudan. In the both cases, failures in the CT/VT module of T60 relays cause unwanted operation of the protection system. These failures could be a result of aging, problems in DC power supply or from the design of these modules. More investigations are needed to find the roots of these failures. In the both cases, the failures are hidden type in which the relay will not operate unless unusual event has happened. The failures could have been detected and removed, if the preventive maintenance was effective. In order to insure reliability and sensitivity of the relays, preventive maintenance should take place from time to time.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
相关文献
二甲双胍通过HDAC6和FoxO3a转录调控肌肉生长抑制素诱导肌肉萎缩
IF 8.9 1区 医学Journal of Cachexia, Sarcopenia and MusclePub Date : 2021-11-02 DOI: 10.1002/jcsm.12833
Min Ju Kang, Ji Wook Moon, Jung Ok Lee, Ji Hae Kim, Eun Jeong Jung, Su Jin Kim, Joo Yeon Oh, Sang Woo Wu, Pu Reum Lee, Sun Hwa Park, Hyeon Soo Kim
具有疾病敏感单倍型的非亲属供体脐带血移植后的1型糖尿病
IF 3.2 3区 医学Journal of Diabetes InvestigationPub Date : 2022-11-02 DOI: 10.1111/jdi.13939
Kensuke Matsumoto, Taisuke Matsuyama, Ritsu Sumiyoshi, Matsuo Takuji, Tadashi Yamamoto, Ryosuke Shirasaki, Haruko Tashiro
封面:蛋白质组学分析确定IRSp53和fastin是PRV输出和直接细胞-细胞传播的关键
IF 3.4 4区 生物学ProteomicsPub Date : 2019-12-02 DOI: 10.1002/pmic.201970201
Fei-Long Yu, Huan Miao, Jinjin Xia, Fan Jia, Huadong Wang, Fuqiang Xu, Lin Guo
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Performance Evaluation of AODV, OLSR and GRP Routing Protocols in Vehicular Highway Environment Performance Evaluation and Failure Analysis of Modular Power Amplifier with Gysel and Branch Coupler Network Efftciency Analysis ofLighting Bulbs Using Fuzzy Data Envelopment Analysis Vehicles Distribution and Lines Planning in Public Transportation A case Study: Wad Medani, Gezira State, Sudan Mobile based Tele-medicine Diabetic Retinopathy Screening
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1