某多层建筑抗震性能评价及钢筋混凝土柱的加固

A. Hasan, M. G. Kibria, F. M. Hasan
{"title":"某多层建筑抗震性能评价及钢筋混凝土柱的加固","authors":"A. Hasan, M. G. Kibria, F. M. Hasan","doi":"10.9790/1684-1403027986","DOIUrl":null,"url":null,"abstract":"Earthquake is a major concerned natural disaster that causes great damage to the structure. Many multistoried commercial, factory and also residential building in Bangladesh are not designed properly considering seismic loads and also seismic zone effects, thereby large storey displacement and cracks have been observed in the structures. In the present study, a G+10 storied factory building is considered and finite element analysis software ETABS 2015 is used to determine the seismic demand and capacity of each structural element considering seismic zone 1 and zone 3. The building is preliminary designed and analyzed for zone 1 and found safe against seismic loads but vulnerable at zone 3. In the developing countries like Bangladesh, RC jacketing method is popular due to its cost effectiveness comparing with other strengthening methods. Therefore, in this study, a guideline for strengthening of columns only by RC jacketing method is discussed and analyzed. The columns having Demand Capacity Ratio (DCR) ratio more than 1.0 found from analysis are considered to strengthen. Pushover analysis is done to determine the performance of the structure before and after retrofitting and it is found that structure after retrofit have more base shear and displacement capacity, and less storey drift compared to unretrofitted structure.","PeriodicalId":14565,"journal":{"name":"IOSR Journal of Mechanical and Civil Engineering","volume":"122 1","pages":"79-86"},"PeriodicalIF":0.0000,"publicationDate":"2017-05-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Seismic Performance Assessment of a Multistoried Building and Retrofitting of RC Columns\",\"authors\":\"A. Hasan, M. G. Kibria, F. M. Hasan\",\"doi\":\"10.9790/1684-1403027986\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Earthquake is a major concerned natural disaster that causes great damage to the structure. Many multistoried commercial, factory and also residential building in Bangladesh are not designed properly considering seismic loads and also seismic zone effects, thereby large storey displacement and cracks have been observed in the structures. In the present study, a G+10 storied factory building is considered and finite element analysis software ETABS 2015 is used to determine the seismic demand and capacity of each structural element considering seismic zone 1 and zone 3. The building is preliminary designed and analyzed for zone 1 and found safe against seismic loads but vulnerable at zone 3. In the developing countries like Bangladesh, RC jacketing method is popular due to its cost effectiveness comparing with other strengthening methods. Therefore, in this study, a guideline for strengthening of columns only by RC jacketing method is discussed and analyzed. The columns having Demand Capacity Ratio (DCR) ratio more than 1.0 found from analysis are considered to strengthen. Pushover analysis is done to determine the performance of the structure before and after retrofitting and it is found that structure after retrofit have more base shear and displacement capacity, and less storey drift compared to unretrofitted structure.\",\"PeriodicalId\":14565,\"journal\":{\"name\":\"IOSR Journal of Mechanical and Civil Engineering\",\"volume\":\"122 1\",\"pages\":\"79-86\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2017-05-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"IOSR Journal of Mechanical and Civil Engineering\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.9790/1684-1403027986\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"IOSR Journal of Mechanical and Civil Engineering","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.9790/1684-1403027986","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

地震是对建筑物造成巨大破坏的重大自然灾害。孟加拉国的许多多层商业、工厂和住宅建筑在设计时没有考虑到地震荷载和地震带效应,因此在结构中观察到较大的层位移和裂缝。本研究以某G+10层厂房为例,采用有限元分析软件ETABS 2015,考虑1区和3区地震带,确定各结构单元的抗震需求和承载力。该建筑对1区进行了初步设计和分析,发现对地震荷载是安全的,但在3区是脆弱的。在孟加拉国等发展中国家,RC护套法由于其与其他加固方法相比具有成本效益而受到欢迎。因此,本文对钢筋混凝土护套加固柱的指导原则进行了探讨和分析。通过分析发现,需求容量比(DCR)大于1.0的柱子被认为是加强的。对改造前后的结构进行了推覆分析,发现改造后的结构比未改造的结构具有更大的基底抗剪和位移能力,层间位移更小。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Seismic Performance Assessment of a Multistoried Building and Retrofitting of RC Columns
Earthquake is a major concerned natural disaster that causes great damage to the structure. Many multistoried commercial, factory and also residential building in Bangladesh are not designed properly considering seismic loads and also seismic zone effects, thereby large storey displacement and cracks have been observed in the structures. In the present study, a G+10 storied factory building is considered and finite element analysis software ETABS 2015 is used to determine the seismic demand and capacity of each structural element considering seismic zone 1 and zone 3. The building is preliminary designed and analyzed for zone 1 and found safe against seismic loads but vulnerable at zone 3. In the developing countries like Bangladesh, RC jacketing method is popular due to its cost effectiveness comparing with other strengthening methods. Therefore, in this study, a guideline for strengthening of columns only by RC jacketing method is discussed and analyzed. The columns having Demand Capacity Ratio (DCR) ratio more than 1.0 found from analysis are considered to strengthen. Pushover analysis is done to determine the performance of the structure before and after retrofitting and it is found that structure after retrofit have more base shear and displacement capacity, and less storey drift compared to unretrofitted structure.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
An Evaluation OfSoil Condition And Flood Risk For Road Network Of Bangladesh—Compiled From Engineering Soil Maps And Digital Elevation Model Improved Limiting Criteria for Deflection in Multi-Story Buildings Subjected to Aerodynamic Load Study on Eco-Friendly Concrete Blocks without Cement and Curing Evaluation of High Performance Concrete by Partial Replacement of Cement with Silica Fume Natural Sand and Manufactured Sand Multi Response Optimization TIG welding parameters for dissimilar weld of MONEL 400 and AISI 304 using RSM
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1