Influences of power frequency magnetic fields when a 110kV high voltage substation and a cloud data center exist in the same building

L. Jike, Z. Xinghai, He Jinliang, Qi Zheng, Shi Dan, W. Zhigang
{"title":"Influences of power frequency magnetic fields when a 110kV high voltage substation and a cloud data center exist in the same building","authors":"L. Jike, Z. Xinghai, He Jinliang, Qi Zheng, Shi Dan, W. Zhigang","doi":"10.1109/CEEM.2015.7368620","DOIUrl":null,"url":null,"abstract":"Since 1960s, no solutions have been found both home and abroad to the theory and protective technology related to hazard influences of a high voltage transmission system on a communication system. Previously, the major technical measure against comprehensive hazards of the strong current is to make them separated. However, in city planning, it is inevitable to arrange them closely or construct them on the same site. Whether a communication system mainly having the weak current and a high voltage system in hundreds of kilovolts can co-exist and how to make them co-exist have become a worldwide puzzle which influences the development of communications. When the cloud data center of a communication system is constructed with a high voltage substation together, three critical technical problems should be solved: influences of hazards caused by the rise of the earth potential in thousands of kilovolts on the communication system due to the power- frequency short-circuit accident of the strong current system; influences of the electromagnetic field in the high-voltage power distribution room on the communication system; and influences of the on-off of high-voltage strong-current grounding and information grounding on communication equipment. When the high voltage substation works normally, the power frequency magnetic field may cause hazards to the information storage equipment of the cloud data center constructed on the same site. By measurements and analyses, this article systematically summarizes characteristics of the power frequency magnetic field generated by the substation.","PeriodicalId":442379,"journal":{"name":"2015 7th Asia-Pacific Conference on Environmental Electromagnetics (CEEM)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2015-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2015 7th Asia-Pacific Conference on Environmental Electromagnetics (CEEM)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CEEM.2015.7368620","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

Abstract

Since 1960s, no solutions have been found both home and abroad to the theory and protective technology related to hazard influences of a high voltage transmission system on a communication system. Previously, the major technical measure against comprehensive hazards of the strong current is to make them separated. However, in city planning, it is inevitable to arrange them closely or construct them on the same site. Whether a communication system mainly having the weak current and a high voltage system in hundreds of kilovolts can co-exist and how to make them co-exist have become a worldwide puzzle which influences the development of communications. When the cloud data center of a communication system is constructed with a high voltage substation together, three critical technical problems should be solved: influences of hazards caused by the rise of the earth potential in thousands of kilovolts on the communication system due to the power- frequency short-circuit accident of the strong current system; influences of the electromagnetic field in the high-voltage power distribution room on the communication system; and influences of the on-off of high-voltage strong-current grounding and information grounding on communication equipment. When the high voltage substation works normally, the power frequency magnetic field may cause hazards to the information storage equipment of the cloud data center constructed on the same site. By measurements and analyses, this article systematically summarizes characteristics of the power frequency magnetic field generated by the substation.
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
110kV高压变电站与云数据中心位于同一建筑物时工频磁场的影响
自20世纪60年代以来,国内外对高压输电系统对通信系统危害影响的相关理论和防护技术尚无定论。以往针对强电综合危害的主要技术措施是将强电分离。然而,在城市规划中,不可避免地要将它们紧密排列或建设在同一地点。以弱电为主的通信系统能否与数百千伏的高压系统共存,以及如何使两者共存,已成为影响通信发展的世界性难题。当通信系统的云数据中心与高压变电站一起建设时,需要解决三个关键的技术问题:强电系统工频短路事故引起的千千伏地电位上升对通信系统的危害影响;高压配电室电磁场对通信系统的影响以及高压强流接地和信息接地的通断对通信设备的影响。高压变电所正常工作时,工频磁场可能对同一站点的云数据中心信息存储设备造成危害。通过测量和分析,系统地总结了变电站工频磁场的特点。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Shielding effectiveness of infinite metal plate with finite thickness at oblique incident and arbitrary polarizations Measurement uncertainty analysis of the electro-optical E-field measurement system EMP effects statistical analysis based on incident waveform characteristics Method of pulse function fitting based on the corona current measurement data A hybrid implicit-explicit FDTD method with an intermediate field
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1