{"title":"Thermal runaway and induced electrical failure of epoxy resin in high-frequency transformers: Insulation design reference","authors":"Xingyu Shang, Lei Pang, Qinhao Bu, Qiaogen Zhang","doi":"10.1049/hve2.12424","DOIUrl":null,"url":null,"abstract":"<p>Solid-state transformers (SSTs) have applications in medium-voltage direct current (MVDC) grids and compact power systems. High-frequency transformer (HFT) is the core component of SSTs. High levels of high frequency high d<i>v</i>/d<i>t</i> voltage stresses challenged the integrity of the galvanic insulation of HFTs. However, dielectric thermal runaway and resultant electrical failure mechanisms in epoxy resin (EP) cast insulation remain unclear. Dielectric heating of EP across varying voltages, frequencies, rising edges, duty cycles and DC biases were measured and corroborated by simulation. The thermal runaway threshold mainly depends on the tangency point of the loss generation and heat dissipation curves below the glass transition temperature. Observations reveal that thermal runaway does not directly cause breakdown; instead, thermal decomposition above 200°C triggers discharge and eventual failure. Simulations demonstrate that temperature rise mainly depends on the average field within the electrode region and inter-segment and inter-layer distances within the HFT winding definitively impact insulation thermal runaway. By applying different criteria for MV and high-voltage (HV) transformers, the reference electric fields for insulation design with unfilled and filled EP were obtained. For instance, limiting dielectric heating below 5 K at 50 kHz necessitates an RMS average field less than 0.44 V/mm, which is much lower than dry-type transformer conventions. The authors prove the necessity of re-evaluating the permissible field strength in HFT insulation design.</p>","PeriodicalId":48649,"journal":{"name":"High Voltage","volume":"9 5","pages":"989-1000"},"PeriodicalIF":4.4000,"publicationDate":"2024-03-11","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://onlinelibrary.wiley.com/doi/epdf/10.1049/hve2.12424","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"High Voltage","FirstCategoryId":"5","ListUrlMain":"https://onlinelibrary.wiley.com/doi/10.1049/hve2.12424","RegionNum":2,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0
Abstract
Solid-state transformers (SSTs) have applications in medium-voltage direct current (MVDC) grids and compact power systems. High-frequency transformer (HFT) is the core component of SSTs. High levels of high frequency high dv/dt voltage stresses challenged the integrity of the galvanic insulation of HFTs. However, dielectric thermal runaway and resultant electrical failure mechanisms in epoxy resin (EP) cast insulation remain unclear. Dielectric heating of EP across varying voltages, frequencies, rising edges, duty cycles and DC biases were measured and corroborated by simulation. The thermal runaway threshold mainly depends on the tangency point of the loss generation and heat dissipation curves below the glass transition temperature. Observations reveal that thermal runaway does not directly cause breakdown; instead, thermal decomposition above 200°C triggers discharge and eventual failure. Simulations demonstrate that temperature rise mainly depends on the average field within the electrode region and inter-segment and inter-layer distances within the HFT winding definitively impact insulation thermal runaway. By applying different criteria for MV and high-voltage (HV) transformers, the reference electric fields for insulation design with unfilled and filled EP were obtained. For instance, limiting dielectric heating below 5 K at 50 kHz necessitates an RMS average field less than 0.44 V/mm, which is much lower than dry-type transformer conventions. The authors prove the necessity of re-evaluating the permissible field strength in HFT insulation design.
High VoltageEnergy-Energy Engineering and Power Technology
CiteScore
9.60
自引率
27.30%
发文量
97
审稿时长
21 weeks
期刊介绍:
High Voltage aims to attract original research papers and review articles. The scope covers high-voltage power engineering and high voltage applications, including experimental, computational (including simulation and modelling) and theoretical studies, which include:
Electrical Insulation
● Outdoor, indoor, solid, liquid and gas insulation
● Transient voltages and overvoltage protection
● Nano-dielectrics and new insulation materials
● Condition monitoring and maintenance
Discharge and plasmas, pulsed power
● Electrical discharge, plasma generation and applications
● Interactions of plasma with surfaces
● Pulsed power science and technology
High-field effects
● Computation, measurements of Intensive Electromagnetic Field
● Electromagnetic compatibility
● Biomedical effects
● Environmental effects and protection
High Voltage Engineering
● Design problems, testing and measuring techniques
● Equipment development and asset management
● Smart Grid, live line working
● AC/DC power electronics
● UHV power transmission
Special Issues. Call for papers:
Interface Charging Phenomena for Dielectric Materials - https://digital-library.theiet.org/files/HVE_CFP_ICP.pdf
Emerging Materials For High Voltage Applications - https://digital-library.theiet.org/files/HVE_CFP_EMHVA.pdf