Elia Mateu-Barriendos, Onur Alican, Javier Renedo, Carlos Collados-Rodriguez, Macarena Martin, Edgar Nuño, Eduardo Prieto-Araujo, Oriol Gomis-Bellmunt
{"title":"Power Oscillation Damping Controllers for Grid-Forming Power Converters in Modern PowerSystems","authors":"Elia Mateu-Barriendos, Onur Alican, Javier Renedo, Carlos Collados-Rodriguez, Macarena Martin, Edgar Nuño, Eduardo Prieto-Araujo, Oriol Gomis-Bellmunt","doi":"arxiv-2409.10726","DOIUrl":null,"url":null,"abstract":"Inter-area oscillations have been extensively studied in conventional power\nsystems dominated by synchronous machines, as well as methods to mitigate them.\nSeveral publications have addressed Power Oscillation Damping (POD) controllers\nin grid-following voltage source converters (GFOL). However, the performance of\nPOD controllers for Grid-Forming voltage source converters (GFOR) in modern\npower systems with increased penetration of power electronics requires further\ninvestigation. This paper investigates the performance of GFORs and\nsupplementary POD controllers in the damping of electromechanical oscillations\nin modern power systems. This paper proposes POD controllers in GFORs by\nsupplementary modulation of active- and reactive-power injections of the\nconverter and both simultaneously (POD- P, POD-Q and POD-PQ, respectively). The\nproposed POD controllers use the frequency imposed by the GFOR as the input\nsignal, which has a simple implementation and it eliminates the need for\nadditional measurements. Eigenvalue-sensitivity methods using a synthetic test\nsystem are applied to the design of POD controllers in GFORs, which is useful\nwhen limited information of the power system is available. This paper\ndemonstrates the effectiveness of POD controllers in GFOR converters to damp\nelectromechanical oscillations, by small-signal stability analysis and\nnon-linear time-domain simulations in a small test system and in a large-scale\npower system.","PeriodicalId":501175,"journal":{"name":"arXiv - EE - Systems and Control","volume":"7 1","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2024-09-16","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"arXiv - EE - Systems and Control","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/arxiv-2409.10726","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
Inter-area oscillations have been extensively studied in conventional power
systems dominated by synchronous machines, as well as methods to mitigate them.
Several publications have addressed Power Oscillation Damping (POD) controllers
in grid-following voltage source converters (GFOL). However, the performance of
POD controllers for Grid-Forming voltage source converters (GFOR) in modern
power systems with increased penetration of power electronics requires further
investigation. This paper investigates the performance of GFORs and
supplementary POD controllers in the damping of electromechanical oscillations
in modern power systems. This paper proposes POD controllers in GFORs by
supplementary modulation of active- and reactive-power injections of the
converter and both simultaneously (POD- P, POD-Q and POD-PQ, respectively). The
proposed POD controllers use the frequency imposed by the GFOR as the input
signal, which has a simple implementation and it eliminates the need for
additional measurements. Eigenvalue-sensitivity methods using a synthetic test
system are applied to the design of POD controllers in GFORs, which is useful
when limited information of the power system is available. This paper
demonstrates the effectiveness of POD controllers in GFOR converters to damp
electromechanical oscillations, by small-signal stability analysis and
non-linear time-domain simulations in a small test system and in a large-scale
power system.
在以同步电机为主导的传统电力系统中,人们已经广泛研究了区域间振荡以及缓解振荡的方法。然而,在电力电子技术渗透率不断提高的现代电力系统中,电网电压源变换器(GFOR)的功率振荡抑制(POD)控制器的性能还需要进一步研究。本文研究了现代电力系统中 GFOR 和辅助 POD 控制器在抑制机电振荡方面的性能。本文提出了 GFOR 中的 POD 控制器,即同时对变流器的有功功率注入和无功功率注入进行补充调制(分别为 POD-P、POD-Q 和 POD-PQ)。拟议的 POD 控制器使用 GFOR 施加的频率作为输入信号,实现简单,无需额外测量。使用合成测试系统的特征值灵敏度方法被应用于 GFOR 中 POD 控制器的设计,这在电力系统信息有限的情况下非常有用。本文通过在小型测试系统和大型电力系统中进行小信号稳定性分析和非线性时域仿真,证明了 POD 控制器在 GFOR 变流器中抑制机电振荡的有效性。