Analysis of Fire Intensity According to the Zones Classification in Traditional Market Stores

Tae Kwon Kim
{"title":"Analysis of Fire Intensity According to the Zones Classification in Traditional Market Stores","authors":"Tae Kwon Kim","doi":"10.5762/KAIS.2020.21.6.154","DOIUrl":null,"url":null,"abstract":"This study analyzed the fire intensity according to the zones classification between traditional market stores using FDS software. Modeling was conducted for the Seomoon traditional market district 4 at Daegu, which places combustibles, such as textiles and clothing near the passageway. The first ignition point assumed a short circuit fire situation at the fourth store combustible. The analysis was conducted under similar conditions as the fire situation in 2016. When there was no section wall, the fire spread rapidly through radiation in all directions from the fire-origin point. After 600 seconds, the mall was burnt to the ground. When section walls were present, however, the fire could be restricted inside the compartment. The first intensity of the two analysis conditions was predicted from the total heat energy from 200 seconds (X1) to 600 seconds (X2), where the heat generation rate began to increase rapidly. As a result of installing section walls near the fire point, heat energy generation of approximately 11.12 MW (55.68 %) was delayed. Further analysis of smoke control, according to the section wall arrangement and re-installation facilities, will be needed to study the characteristics of fire in traditional markets comprehensively.","PeriodicalId":23087,"journal":{"name":"The Korea Academia-Industrial cooperation Society","volume":"5 3 1","pages":"154-160"},"PeriodicalIF":0.0000,"publicationDate":"2020-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"The Korea Academia-Industrial cooperation Society","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.5762/KAIS.2020.21.6.154","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

This study analyzed the fire intensity according to the zones classification between traditional market stores using FDS software. Modeling was conducted for the Seomoon traditional market district 4 at Daegu, which places combustibles, such as textiles and clothing near the passageway. The first ignition point assumed a short circuit fire situation at the fourth store combustible. The analysis was conducted under similar conditions as the fire situation in 2016. When there was no section wall, the fire spread rapidly through radiation in all directions from the fire-origin point. After 600 seconds, the mall was burnt to the ground. When section walls were present, however, the fire could be restricted inside the compartment. The first intensity of the two analysis conditions was predicted from the total heat energy from 200 seconds (X1) to 600 seconds (X2), where the heat generation rate began to increase rapidly. As a result of installing section walls near the fire point, heat energy generation of approximately 11.12 MW (55.68 %) was delayed. Further analysis of smoke control, according to the section wall arrangement and re-installation facilities, will be needed to study the characteristics of fire in traditional markets comprehensively.
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
基于区域划分的传统市场店铺火灾强度分析
本研究利用FDS软件对传统市场店铺之间的分区进行火灾强度分析。大邱西门传统市场第4区在通道附近放置了纺织品和衣服等易燃物品,并进行了模拟。第一个着火点假定在第四个可燃物库发生短路着火情况。该分析是在与2016年火灾情况相似的条件下进行的。在没有截面墙的情况下,火势从火源向四面辐射,蔓延迅速。600秒后,商场被夷为平地。然而,当有截面墙存在时,火焰可以限制在隔间内。从200秒(X1)到600秒(X2)的总热能预测两种分析条件的第一强度,此时生热率开始迅速增加。由于在火点附近安装了分段墙,导致约11.12 MW(55.68%)的热能发电延迟。进一步的烟雾控制分析,根据截面墙布置和重新安装设施,将需要全面研究传统市场的火灾特征。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Self-Awareness and Coping Behavior of Smartphone Dependence among Undergraduate Students The Verification Method for Missing Software Standardization in Weapon System - Focused on Firmware A Study on Modeling of Leakage Current in ESS Using PSCAD/EMTDC Development of Chicken Carcass Segmentation Algorithm using Image Processing System Effect of Different Cooling System on Performance and Hair Cortisol on Sows under Heat Stress
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1