Investigation on variable flow control in existing water-cooled chiller plant of high-rise commercial building in subtropical climate

K. F. Fong, C. K. Lee, T. Chow
{"title":"Investigation on variable flow control in existing water-cooled chiller plant of high-rise commercial building in subtropical climate","authors":"K. F. Fong, C. K. Lee, T. Chow","doi":"10.1080/10789669.2013.822253","DOIUrl":null,"url":null,"abstract":"An all-variable-speed chiller plant has been advocated so that the chillers and their associated pumps can work at reduced speed during part-load conditions for energy saving purposes. In this new building project, the savings merit is certainly attractive. However, an existing chiller plant or retrofit project, which is constrained by the performance of installed equipment and the configuration of a hydronic circuit, may not benefit from the an ideal extent of savings. As such, an existing chiller plant serving a typical commercial building was used to evaluate this. Through year-round dynamic simulation, it is found that there were about 5%, 6%, and 8% energy savings of the whole chiller plant when applying variable flow control on secondary chilled water pumps only, both primary and secondary chilled water pumps, and all chilled and condenser water pumps, respectively. If constant-speed centrifugal chillers were substituted by the variable-speed ones, an additional 4% savings could be achieved, which was, however, less than that incurred from the associated pumps. The payback periods of different variable flow control strategies were well below 1 year, indicating the techno-economical feasibility for wider application in existing chiller plants in subtropical climates.","PeriodicalId":13238,"journal":{"name":"HVAC&R Research","volume":"44 1","pages":"51 - 60"},"PeriodicalIF":0.0000,"publicationDate":"2014-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"5","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"HVAC&R Research","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1080/10789669.2013.822253","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 5

Abstract

An all-variable-speed chiller plant has been advocated so that the chillers and their associated pumps can work at reduced speed during part-load conditions for energy saving purposes. In this new building project, the savings merit is certainly attractive. However, an existing chiller plant or retrofit project, which is constrained by the performance of installed equipment and the configuration of a hydronic circuit, may not benefit from the an ideal extent of savings. As such, an existing chiller plant serving a typical commercial building was used to evaluate this. Through year-round dynamic simulation, it is found that there were about 5%, 6%, and 8% energy savings of the whole chiller plant when applying variable flow control on secondary chilled water pumps only, both primary and secondary chilled water pumps, and all chilled and condenser water pumps, respectively. If constant-speed centrifugal chillers were substituted by the variable-speed ones, an additional 4% savings could be achieved, which was, however, less than that incurred from the associated pumps. The payback periods of different variable flow control strategies were well below 1 year, indicating the techno-economical feasibility for wider application in existing chiller plants in subtropical climates.
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
亚热带气候下高层商业建筑既有水冷机组变流量控制研究
提倡采用全变速冷水机组,以便冷水机组及其配套泵在部分负荷条件下以减速工作,以达到节能目的。在这个新建筑项目中,节约的优点当然很有吸引力。然而,现有的冷水机组或改造项目,由于受到已安装设备性能和水力回路配置的限制,可能无法从理想的节约程度中受益。因此,一个现有的冷水机组服务于一个典型的商业建筑被用来评估这一点。通过全年动态仿真,发现仅对二次冷冻水泵、一次和二次冷冻水泵均采用变流量控制、所有冷冻水泵和凝汽器水泵均采用变流量控制时,整个冷水机组分别节能5%、6%和8%左右。如果等速离心冷却器被变速冷却器所取代,可以额外节省4%,然而,这比相关泵所产生的要少。不同变流量控制策略的投资回收期均在1年以下,表明在现有的亚热带气候条件下的冷水机组中广泛应用的技术经济可行性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 去求助
来源期刊
HVAC&R Research
HVAC&R Research 工程技术-工程:机械
自引率
0.00%
发文量
0
审稿时长
3 months
期刊最新文献
EOV Editorial Board The never-ending search Accelerating fast fluid dynamics with a coarse-grid projection scheme Numerical modeling of volatile organic compound emissions from ozone reactions with human-worn clothing in an aircraft cabin Dynamic simulation and analysis of ancillary service demand response strategies for variable air volume HVAC systems
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1