Assessing the “sufficient ventilation” requirement for Austrian buildings: development of a Monte Carlo based spreadsheet calculation to estimate airing intervals and mould risk in window ventilated buildings

IF 1.1 4区 工程技术 Q3 CONSTRUCTION & BUILDING TECHNOLOGY International Journal of Ventilation Pub Date : 2023-04-18 DOI:10.1080/14733315.2023.2198788
G. Rojas, Andreas Greml, Rainer Pfluger, P. Tappler
{"title":"Assessing the “sufficient ventilation” requirement for Austrian buildings: development of a Monte Carlo based spreadsheet calculation to estimate airing intervals and mould risk in window ventilated buildings","authors":"G. Rojas, Andreas Greml, Rainer Pfluger, P. Tappler","doi":"10.1080/14733315.2023.2198788","DOIUrl":null,"url":null,"abstract":"Abstract In Austria the lack of guidelines or standards has caused many discussions and disputes on the question if “sufficient ventilation” can be ensured with window airing only, in particular in newly constructed, airtight residential buildings. This work presents the development of a calculation method aiming to provide a simple-to-use tool to estimate the risk of mould growth and the window airing interval required to ensure good indoor air quality assuming a range of different boundary conditions and occupant behaviours. The method implements a Monte Carlo approach calculating 1000 single zone mass balances for carbon dioxide (on a room level) and water vapor (on a housing level). Air infiltration through the building envelope is accounted using the so-called LBL-model. The time interval between window airing required to comply with CO2 limit value is estimated by calculating the time evolution of the CO2 concentration for 1000 different parameter combinations. The mould risk is estimated by a 1000-fold calculation of the daily averaged indoor air humidity and the resulting water activity on critical wall surfaces. The results are displayed as probability distributions providing information on the risk that the queried situation can or cannot ensure “sufficient ventilation”. Exemplary calculations for bedrooms of new multifamily buildings estimate that intervals between window airing events (to keep time-averaged CO2-concentration below 1000 ppm), will vary between 23 and 190 minutes (representing the 5th and the 95th percentile). This is clearly below an acceptable intervention interval for bedrooms. For living rooms, the assessment shows a strong sensitivity on the “accessible” air volume. The humidity assessment for this type of housing suggests that mould growth could occur in about 17% of the cases even though air exchange corresponding to two airing events per day were assumed. An additional outdoor air exchange of up to 40 m³/h would be required to reduce the mould risk fraction to <1%, suggesting the need for mechanical ventilation concepts in residential housing to enable healthy indoor environment independently of occupant behaviour.","PeriodicalId":55613,"journal":{"name":"International Journal of Ventilation","volume":null,"pages":null},"PeriodicalIF":1.1000,"publicationDate":"2023-04-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"International Journal of Ventilation","FirstCategoryId":"5","ListUrlMain":"https://doi.org/10.1080/14733315.2023.2198788","RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"CONSTRUCTION & BUILDING TECHNOLOGY","Score":null,"Total":0}
引用次数: 0

Abstract

Abstract In Austria the lack of guidelines or standards has caused many discussions and disputes on the question if “sufficient ventilation” can be ensured with window airing only, in particular in newly constructed, airtight residential buildings. This work presents the development of a calculation method aiming to provide a simple-to-use tool to estimate the risk of mould growth and the window airing interval required to ensure good indoor air quality assuming a range of different boundary conditions and occupant behaviours. The method implements a Monte Carlo approach calculating 1000 single zone mass balances for carbon dioxide (on a room level) and water vapor (on a housing level). Air infiltration through the building envelope is accounted using the so-called LBL-model. The time interval between window airing required to comply with CO2 limit value is estimated by calculating the time evolution of the CO2 concentration for 1000 different parameter combinations. The mould risk is estimated by a 1000-fold calculation of the daily averaged indoor air humidity and the resulting water activity on critical wall surfaces. The results are displayed as probability distributions providing information on the risk that the queried situation can or cannot ensure “sufficient ventilation”. Exemplary calculations for bedrooms of new multifamily buildings estimate that intervals between window airing events (to keep time-averaged CO2-concentration below 1000 ppm), will vary between 23 and 190 minutes (representing the 5th and the 95th percentile). This is clearly below an acceptable intervention interval for bedrooms. For living rooms, the assessment shows a strong sensitivity on the “accessible” air volume. The humidity assessment for this type of housing suggests that mould growth could occur in about 17% of the cases even though air exchange corresponding to two airing events per day were assumed. An additional outdoor air exchange of up to 40 m³/h would be required to reduce the mould risk fraction to <1%, suggesting the need for mechanical ventilation concepts in residential housing to enable healthy indoor environment independently of occupant behaviour.
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
评估奥地利建筑物的“充分通风”要求:开发基于蒙特卡罗的电子表格计算,以估计通风间隔和窗户通风建筑物的霉菌风险
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 去求助
来源期刊
International Journal of Ventilation
International Journal of Ventilation CONSTRUCTION & BUILDING TECHNOLOGY-ENERGY & FUELS
CiteScore
3.50
自引率
6.70%
发文量
7
审稿时长
>12 weeks
期刊介绍: This is a peer reviewed journal aimed at providing the latest information on research and application. Topics include: • New ideas concerned with the development or application of ventilation; • Validated case studies demonstrating the performance of ventilation strategies; • Information on needs and solutions for specific building types including: offices, dwellings, schools, hospitals, parking garages, urban buildings and recreational buildings etc; • Developments in numerical methods; • Measurement techniques; • Related issues in which the impact of ventilation plays an important role (e.g. the interaction of ventilation with air quality, health and comfort); • Energy issues related to ventilation (e.g. low energy systems, ventilation heating and cooling loss); • Driving forces (weather data, fan performance etc).
期刊最新文献
Assessing thermal resilience to overheating in a Belgian apartment: impact of building parameters Introducing an optimization approach for enthalpy exchangers for residential ventilation Passive ventilation for building not subjected to solar radiation Experimental study on the periodic pulsating ventilation by fluidic oscillator on pollutant dispersion and ventilation performance in enclosed environment Numerical study on aerodynamic pressure caused by high-speed train passing through the subway station
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1