Estimating LV secondary voltage drop using AMI data for improved distribution management

O. Leitermann, Vincent Martinelli, J. Simonelli
{"title":"Estimating LV secondary voltage drop using AMI data for improved distribution management","authors":"O. Leitermann, Vincent Martinelli, J. Simonelli","doi":"10.1109/TDC.2016.7519863","DOIUrl":null,"url":null,"abstract":"Low voltage (LV) wiring and distribution transformers are an important part of the system delivering electricity to the customer, but information about the performance, and even about the lengths and impedances, of service-level components has been limited in the past. Now that increased pressures are being put on the grid by distributed generation and new loads, and the system is being held to closer tolerances through programs like conservation voltage reduction (CVR), it is becoming more important to understand the voltage drops at the LV service level. However, these voltage drops are rarely measured and reported on in the literature, particularly for US systems. This paper discusses three methods for measuring for LV secondary drop, using newly available measurements of customer voltage by advanced metering infrastructure (AMI) alongside other data. Based on AMI measurments and other data from three US utilities, it was found that while most secondary drops are within the ranges typically cited by utilities, there are a few spots with larger voltage drops that could be a problem given future CVR programs or the installation of additional load or PV.","PeriodicalId":6497,"journal":{"name":"2016 IEEE/PES Transmission and Distribution Conference and Exposition (T&D)","volume":"184 1","pages":"1-5"},"PeriodicalIF":0.0000,"publicationDate":"2016-05-03","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"3","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2016 IEEE/PES Transmission and Distribution Conference and Exposition (T&D)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/TDC.2016.7519863","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3

Abstract

Low voltage (LV) wiring and distribution transformers are an important part of the system delivering electricity to the customer, but information about the performance, and even about the lengths and impedances, of service-level components has been limited in the past. Now that increased pressures are being put on the grid by distributed generation and new loads, and the system is being held to closer tolerances through programs like conservation voltage reduction (CVR), it is becoming more important to understand the voltage drops at the LV service level. However, these voltage drops are rarely measured and reported on in the literature, particularly for US systems. This paper discusses three methods for measuring for LV secondary drop, using newly available measurements of customer voltage by advanced metering infrastructure (AMI) alongside other data. Based on AMI measurments and other data from three US utilities, it was found that while most secondary drops are within the ranges typically cited by utilities, there are a few spots with larger voltage drops that could be a problem given future CVR programs or the installation of additional load or PV.
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
利用AMI数据估计低压二次电压降,改善配电管理
低压(LV)布线和配电变压器是向用户输送电力的系统的重要组成部分,但是关于服务级元件的性能,甚至长度和阻抗的信息在过去一直是有限的。现在,分布式发电和新负荷给电网带来了越来越大的压力,并且通过诸如保护电压降低(CVR)之类的计划,系统被保持在更接近的公差范围内,因此了解低压服务级别的电压降变得越来越重要。然而,这些电压降很少在文献中测量和报道,特别是对于美国系统。本文讨论了低压二次降的三种测量方法,利用先进的计量基础设施(AMI)和其他数据新获得的客户电压测量值。根据AMI测量和美国三家公用事业公司的其他数据,研究人员发现,虽然大多数二次电压降都在公用事业公司通常引用的范围内,但考虑到未来的CVR项目或安装额外负载或PV,有一些地方的电压降较大,可能会成为一个问题。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Fast evaluation of probabilistic total transfer capability considering multiple wind farms An automated model based fault locating method for distribution systems Fault location identification of a hybrid HVDC-VSC system containing cable and overhead line segments using transient data Conductor corrosion inspection of aluminum conductor steel reinforced transmission lines Microgrid load management and control strategies
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1