Some methods for harmonic emission determination in wind power plants

D. Schwanz, M. Bollen, A. Larsson
{"title":"Some methods for harmonic emission determination in wind power plants","authors":"D. Schwanz, M. Bollen, A. Larsson","doi":"10.1109/ICHQP.2018.8378934","DOIUrl":null,"url":null,"abstract":"The connection of new installations, as wind power plants, into the public grid requires that some conditions are fulfilled. Their aim is among others to ensure a proper power quality in the grid and to ensure a high probability of electromagnetic compatibility. The harmonic emission of individual sources is one of the power quality concerns, because they can damage and increase heating in devices. However, as there are other power electronics loads are connected, the correct assessment of the harmonic emission from one specific source is not straightforward. in this paper, a review of the most used methods for harmonic emission determination is presented and some considerations are discussed regarding their use in wind power plants harmonic contribution. Depending on the application, one method is more suitable than the other. However, assumptions are necessary with any method, especially for the harmonic impedances. For wind power plants not all the presented methods are suitable. Also, further investigations are needed to determine the harmonic impedance of the wind power plant and public grid, especially around resonant frequencies.","PeriodicalId":6506,"journal":{"name":"2018 18th International Conference on Harmonics and Quality of Power (ICHQP)","volume":"87 1","pages":"1-6"},"PeriodicalIF":0.0000,"publicationDate":"2018-05-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"11","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2018 18th International Conference on Harmonics and Quality of Power (ICHQP)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICHQP.2018.8378934","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 11

Abstract

The connection of new installations, as wind power plants, into the public grid requires that some conditions are fulfilled. Their aim is among others to ensure a proper power quality in the grid and to ensure a high probability of electromagnetic compatibility. The harmonic emission of individual sources is one of the power quality concerns, because they can damage and increase heating in devices. However, as there are other power electronics loads are connected, the correct assessment of the harmonic emission from one specific source is not straightforward. in this paper, a review of the most used methods for harmonic emission determination is presented and some considerations are discussed regarding their use in wind power plants harmonic contribution. Depending on the application, one method is more suitable than the other. However, assumptions are necessary with any method, especially for the harmonic impedances. For wind power plants not all the presented methods are suitable. Also, further investigations are needed to determine the harmonic impedance of the wind power plant and public grid, especially around resonant frequencies.
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
风力发电厂谐波排放的几种测定方法
新设备,如风力发电厂,接入公共电网需要满足一些条件。他们的目标是确保电网中适当的电能质量,并确保高概率的电磁兼容性。单个源的谐波发射是电能质量问题之一,因为它们会损坏设备并增加加热。然而,由于有其他电力电子负载连接,从一个特定的源谐波发射的正确评估是不直接的。本文综述了目前常用的谐波排放测定方法,并对其在风力发电厂谐波贡献测量中的应用进行了讨论。根据应用的不同,一种方法比另一种方法更合适。然而,任何方法都需要假设,特别是谐波阻抗。对于风力发电厂来说,并非所有的方法都适用。此外,还需要进一步研究确定风力发电厂和公共电网的谐波阻抗,特别是谐振频率附近的谐波阻抗。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Adaptive segmentation and machine learning based potential DR capacity analysis Harmonic resonance risk of massive ultra fast charging station grid integration A general process recommended by CIGRE WG C4.27 for benchmarking power quality performance in transmission systems On the limitations of harmonic modeling with measured inputs - a case study Analysis of replacement from disconnecting switch to circuit breaker for 500 kV line shunt reactor
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1