{"title":"Form 2S电表浮中性状态的检测","authors":"Ibon Vicente Figueirido, L. Piyasinghe, Lawrence R. Kremer","doi":"10.1109/GridEdge54130.2023.10102718","DOIUrl":null,"url":null,"abstract":"In North American, most residential electrical meters are of the form 2S type. While the neutral conductor from the split-phase transformer to the customer’s service panel is routed through the meter socket, the meter does not have a connection to the neutral conductor. Line 1 and line 2 voltage magnitudes are nominally equal when referenced to the neutral. Conditions arise that the neutral connection becomes compromised, in which case the line 1 and line 2 voltages become unbalance, creating potentially hazardous conditions. This paper describe an algorithm in a form 2S smart meter can use to detect a faulted neutral connection by observing changes in the currents seen by the meter even though it does not have a direct connection to the neutral reference point. Results of laboratory experiments show that it is possible to detect faulted neutral conditions in a typical household in less than a day.","PeriodicalId":377998,"journal":{"name":"2023 IEEE PES Grid Edge Technologies Conference & Exposition (Grid Edge)","volume":"35 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2023-04-10","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Detection of Floating Neutral Condition in a Form 2S Electric Meter\",\"authors\":\"Ibon Vicente Figueirido, L. Piyasinghe, Lawrence R. Kremer\",\"doi\":\"10.1109/GridEdge54130.2023.10102718\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"In North American, most residential electrical meters are of the form 2S type. While the neutral conductor from the split-phase transformer to the customer’s service panel is routed through the meter socket, the meter does not have a connection to the neutral conductor. Line 1 and line 2 voltage magnitudes are nominally equal when referenced to the neutral. Conditions arise that the neutral connection becomes compromised, in which case the line 1 and line 2 voltages become unbalance, creating potentially hazardous conditions. This paper describe an algorithm in a form 2S smart meter can use to detect a faulted neutral connection by observing changes in the currents seen by the meter even though it does not have a direct connection to the neutral reference point. Results of laboratory experiments show that it is possible to detect faulted neutral conditions in a typical household in less than a day.\",\"PeriodicalId\":377998,\"journal\":{\"name\":\"2023 IEEE PES Grid Edge Technologies Conference & Exposition (Grid Edge)\",\"volume\":\"35 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2023-04-10\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2023 IEEE PES Grid Edge Technologies Conference & Exposition (Grid Edge)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/GridEdge54130.2023.10102718\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2023 IEEE PES Grid Edge Technologies Conference & Exposition (Grid Edge)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/GridEdge54130.2023.10102718","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
Detection of Floating Neutral Condition in a Form 2S Electric Meter
In North American, most residential electrical meters are of the form 2S type. While the neutral conductor from the split-phase transformer to the customer’s service panel is routed through the meter socket, the meter does not have a connection to the neutral conductor. Line 1 and line 2 voltage magnitudes are nominally equal when referenced to the neutral. Conditions arise that the neutral connection becomes compromised, in which case the line 1 and line 2 voltages become unbalance, creating potentially hazardous conditions. This paper describe an algorithm in a form 2S smart meter can use to detect a faulted neutral connection by observing changes in the currents seen by the meter even though it does not have a direct connection to the neutral reference point. Results of laboratory experiments show that it is possible to detect faulted neutral conditions in a typical household in less than a day.