G. Stone, H. Sedding, C. Chan, C. Wendel
{"title":"旋转电机定子绕组低频与高频PD测量的比较","authors":"G. Stone, H. Sedding, C. Chan, C. Wendel","doi":"10.1109/EIC.2018.8481128","DOIUrl":null,"url":null,"abstract":"Partial discharge (PD) testing has been used for over 60 years primarily as a method to detect aging of the stator winding insulation in motors and generators rated 6 kV and above. More recently it has also been used by some machine manufacturers as a means of assuring the quality of the insulation. The PD measuring systems in use work either in the low frequency regime (less than about 1 MHz) or in the very high frequency (30–300 MHz) range. By reference to several international standards, published work as well as some experiments described here, the advantages and disadvantages of the two approaches are reviewed. In most circumstances it is now clear that off-line PD tests should be done in the low frequency range. For on-line tests, either frequency range can be used, but with different advantages.","PeriodicalId":184139,"journal":{"name":"2018 IEEE Electrical Insulation Conference (EIC)","volume":"15 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2018-06-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Comparison of Low Frequency and High Frequency PD Measurements on Rotating Machine Stator Windings\",\"authors\":\"G. Stone, H. Sedding, C. Chan, C. Wendel\",\"doi\":\"10.1109/EIC.2018.8481128\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Partial discharge (PD) testing has been used for over 60 years primarily as a method to detect aging of the stator winding insulation in motors and generators rated 6 kV and above. More recently it has also been used by some machine manufacturers as a means of assuring the quality of the insulation. The PD measuring systems in use work either in the low frequency regime (less than about 1 MHz) or in the very high frequency (30–300 MHz) range. By reference to several international standards, published work as well as some experiments described here, the advantages and disadvantages of the two approaches are reviewed. In most circumstances it is now clear that off-line PD tests should be done in the low frequency range. For on-line tests, either frequency range can be used, but with different advantages.\",\"PeriodicalId\":184139,\"journal\":{\"name\":\"2018 IEEE Electrical Insulation Conference (EIC)\",\"volume\":\"15 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2018-06-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2018 IEEE Electrical Insulation Conference (EIC)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/EIC.2018.8481128\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2018 IEEE Electrical Insulation Conference (EIC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/EIC.2018.8481128","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

摘要

局部放电(PD)测试已经使用了60多年,主要是作为检测额定6kv及以上的电机和发电机定子绕组绝缘老化的方法。最近,它也被一些机器制造商用作保证绝缘质量的一种手段。目前使用的PD测量系统工作在低频(小于1 MHz)或高频(30-300 MHz)范围内。通过参考一些国际标准、已发表的工作以及本文描述的一些实验,综述了这两种方法的优缺点。在大多数情况下,现在很清楚,离线PD测试应该在低频范围内进行。对于在线测试,任何一种频率范围都可以使用,但具有不同的优点。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Comparison of Low Frequency and High Frequency PD Measurements on Rotating Machine Stator Windings
Partial discharge (PD) testing has been used for over 60 years primarily as a method to detect aging of the stator winding insulation in motors and generators rated 6 kV and above. More recently it has also been used by some machine manufacturers as a means of assuring the quality of the insulation. The PD measuring systems in use work either in the low frequency regime (less than about 1 MHz) or in the very high frequency (30–300 MHz) range. By reference to several international standards, published work as well as some experiments described here, the advantages and disadvantages of the two approaches are reviewed. In most circumstances it is now clear that off-line PD tests should be done in the low frequency range. For on-line tests, either frequency range can be used, but with different advantages.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Experimental Research on Flashover Characteristics of Insulator with N2 Dissolved Gas Analysis (DGA) of Arc Discharge Fault in Transformer Insulation Oils (Ester and Mineral Oils) Nonparametric Kernel Density Estimation Model of Transformer Health Based on Dissolved Gases in Oil Experimental validation of a moisture sensor for cellulosic insulation of power transformers Development Process of Vibration Sparking Erosion on Stator Bars
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1