{"title":"传输电压下真空断路器开断速度的测定","authors":"X. Yao, Jianhua Wang, Yingsan Geng, Zhiyuan Liu, Xiaoshe Zhai","doi":"10.1109/DEIV.2016.7748703","DOIUrl":null,"url":null,"abstract":"The objective of this paper is to propose a quantitative method to determine opening velocities for VCBs at transmission voltage. A couple of 2/3 coil-type axial magnetic field (AMF) contacts, which are used in a 126 kV vacuum interrupter, are arranged in a demountable vacuum chamber. The movable contact is opening with three different kinds of opening travel-curves. Each curve is adjusted by two opening velocities, v1 and v2, respectively. The v1 is an average opening velocity within 1/3 full contact gap, which is with 1.8 m/s, 2.4 m/s and 2.7 m/s, respectively. The v2 is an average opening velocity within 2/3 full contact gap, which is with 2.4 m/s, 2.7 m/s, and 3.0 m/s, respectively. The test current ranges from 4 kA to 40 kA, stepped by 4 kA. When a VCB is used to interrupt a short-circuit current, the preferred opening velocity is determined by reducing the arcing interval tI for the intense arc mode and increasing the arcing interval tII until the formation of high-current anode mode (HAM). The preferred v1 is higher than a threshold value v1_th, at which there is a peak critical contact gap dI_peak, for the evolving from intense arc mode into diffuse arc mode. The preferred value v2 is lower than another threshold value v2_th, at which there also exists a peak critical contact gap dII_peak, for the evolving from diffuse arc mode into the footpoint mode and anode spot mode.","PeriodicalId":296641,"journal":{"name":"2016 27th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV)","volume":"23 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2016-09-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"4","resultStr":"{\"title\":\"Determination of opening velocities for vacuum circuit breakers at transmission voltage\",\"authors\":\"X. Yao, Jianhua Wang, Yingsan Geng, Zhiyuan Liu, Xiaoshe Zhai\",\"doi\":\"10.1109/DEIV.2016.7748703\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The objective of this paper is to propose a quantitative method to determine opening velocities for VCBs at transmission voltage. A couple of 2/3 coil-type axial magnetic field (AMF) contacts, which are used in a 126 kV vacuum interrupter, are arranged in a demountable vacuum chamber. The movable contact is opening with three different kinds of opening travel-curves. Each curve is adjusted by two opening velocities, v1 and v2, respectively. The v1 is an average opening velocity within 1/3 full contact gap, which is with 1.8 m/s, 2.4 m/s and 2.7 m/s, respectively. The v2 is an average opening velocity within 2/3 full contact gap, which is with 2.4 m/s, 2.7 m/s, and 3.0 m/s, respectively. The test current ranges from 4 kA to 40 kA, stepped by 4 kA. When a VCB is used to interrupt a short-circuit current, the preferred opening velocity is determined by reducing the arcing interval tI for the intense arc mode and increasing the arcing interval tII until the formation of high-current anode mode (HAM). The preferred v1 is higher than a threshold value v1_th, at which there is a peak critical contact gap dI_peak, for the evolving from intense arc mode into diffuse arc mode. The preferred value v2 is lower than another threshold value v2_th, at which there also exists a peak critical contact gap dII_peak, for the evolving from diffuse arc mode into the footpoint mode and anode spot mode.\",\"PeriodicalId\":296641,\"journal\":{\"name\":\"2016 27th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV)\",\"volume\":\"23 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2016-09-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"4\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2016 27th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/DEIV.2016.7748703\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2016 27th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/DEIV.2016.7748703","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 4

摘要

本文的目的是提出一种定量的方法来确定在传输电压下vcb的打开速度。一对2/3线圈型轴向磁场(AMF)触点,用于126 kV真空灭弧,被安排在一个可拆卸的真空室。活动触点的开启有三种不同的开启行程曲线。每条曲线分别由两个开启速度v1和v2来调节。v1为1/3全接触间隙内的平均开启速度,分别为1.8 m/s、2.4 m/s和2.7 m/s。其中v2为2/3全接触间隙内的平均开启速度,分别为2.4 m/s、2.7 m/s和3.0 m/s。测试电流范围为4ka ~ 40ka,步进4ka。当使用压断路器中断短路电流时,通过减小强电弧模式的电弧间隔tI和增大电弧间隔tII来确定优选的开断速度,直到形成大电流阳极模式(HAM)。优选v1大于阈值v1_th,在该阈值处存在一个峰值临界接触间隙dI_peak,表明从强弧模式向扩散弧模式演化。优选值v2低于另一个阈值v2_th,在该阈值处也存在一个峰值临界接触间隙dII_peak,从扩散电弧模式演变为脚点模式和阳极点模式。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Determination of opening velocities for vacuum circuit breakers at transmission voltage
The objective of this paper is to propose a quantitative method to determine opening velocities for VCBs at transmission voltage. A couple of 2/3 coil-type axial magnetic field (AMF) contacts, which are used in a 126 kV vacuum interrupter, are arranged in a demountable vacuum chamber. The movable contact is opening with three different kinds of opening travel-curves. Each curve is adjusted by two opening velocities, v1 and v2, respectively. The v1 is an average opening velocity within 1/3 full contact gap, which is with 1.8 m/s, 2.4 m/s and 2.7 m/s, respectively. The v2 is an average opening velocity within 2/3 full contact gap, which is with 2.4 m/s, 2.7 m/s, and 3.0 m/s, respectively. The test current ranges from 4 kA to 40 kA, stepped by 4 kA. When a VCB is used to interrupt a short-circuit current, the preferred opening velocity is determined by reducing the arcing interval tI for the intense arc mode and increasing the arcing interval tII until the formation of high-current anode mode (HAM). The preferred v1 is higher than a threshold value v1_th, at which there is a peak critical contact gap dI_peak, for the evolving from intense arc mode into diffuse arc mode. The preferred value v2 is lower than another threshold value v2_th, at which there also exists a peak critical contact gap dII_peak, for the evolving from diffuse arc mode into the footpoint mode and anode spot mode.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Improvement of the CERN SPS electrostatic septa ion traps Experimental investigation on the dynamic of cathode spot of vacuum arc in external transverse magnetic field Simulation of the hydrogen isotope desorption in the cathode spot of a vacuum arc with a ZrDx cathode Surface discharge detection of external insulation of outdoor vacuum circuit breaker based on ultraviolet imaging Model of the formation of an elementary crater on the cucr cathode of a vacuum interrupters
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1