{"title":"基于微处理器的变压器差动继电器的妨害跳闸研究","authors":"P. Sutherland","doi":"10.1109/ICPS.2010.5489877","DOIUrl":null,"url":null,"abstract":"A “nuisance trip” of a microprocessor based transformer differential relay was observed, with an unknown cause. The relay settings were modified with a higher pickup and an alarm at a more sensitive setting. The relay was then able to capture an event, which then did not cause tripping. The results were analyzed and found to be caused by energization of a downstream transformer. In addition, the CT ratio on the transformer primary was excessively high, which was corrected by auxiliary CTs. Based on these results, no further changes needed to be made to the relay settings.","PeriodicalId":346769,"journal":{"name":"2010 IEEE Industrial and Commercial Power Systems Technical Conference - Conference Record","volume":"8 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2010-05-09","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Investigation of nuisance trips in microprocessor based transformer differential relay\",\"authors\":\"P. Sutherland\",\"doi\":\"10.1109/ICPS.2010.5489877\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"A “nuisance trip” of a microprocessor based transformer differential relay was observed, with an unknown cause. The relay settings were modified with a higher pickup and an alarm at a more sensitive setting. The relay was then able to capture an event, which then did not cause tripping. The results were analyzed and found to be caused by energization of a downstream transformer. In addition, the CT ratio on the transformer primary was excessively high, which was corrected by auxiliary CTs. Based on these results, no further changes needed to be made to the relay settings.\",\"PeriodicalId\":346769,\"journal\":{\"name\":\"2010 IEEE Industrial and Commercial Power Systems Technical Conference - Conference Record\",\"volume\":\"8 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2010-05-09\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2010 IEEE Industrial and Commercial Power Systems Technical Conference - Conference Record\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICPS.2010.5489877\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2010 IEEE Industrial and Commercial Power Systems Technical Conference - Conference Record","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICPS.2010.5489877","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

观察到基于微处理器的变压器差动继电器的“令人讨厌的跳闸”,原因不明。继电器设置修改为更高的拾取和警报在更敏感的设置。然后,继电器能够捕捉到一个事件,而这个事件不会导致跳闸。分析结果表明,这是由下游变压器通电引起的。此外,变压器初级上的CT比过高,这是通过辅助CT纠正的。根据这些结果,不需要对继电器设置进行进一步更改。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Investigation of nuisance trips in microprocessor based transformer differential relay
A “nuisance trip” of a microprocessor based transformer differential relay was observed, with an unknown cause. The relay settings were modified with a higher pickup and an alarm at a more sensitive setting. The relay was then able to capture an event, which then did not cause tripping. The results were analyzed and found to be caused by energization of a downstream transformer. In addition, the CT ratio on the transformer primary was excessively high, which was corrected by auxiliary CTs. Based on these results, no further changes needed to be made to the relay settings.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Considerations in unit substation design to optimize reliability and electrical workplace safety Methods for limiting arc flash hazards while maintaining system selectivity A hybrid method for the dynamic parameter identification of generators via on-line measurements Wireless health monitoring system for vibration detection of induction motors Impact of placement of inductive fault current limiters on synchronized operations of generators
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1