多端子MVDC配电系统中电源变流器与接触器故障保护的协调

P. Cairoli, R. Dougal, K. Lentijo
{"title":"多端子MVDC配电系统中电源变流器与接触器故障保护的协调","authors":"P. Cairoli, R. Dougal, K. Lentijo","doi":"10.1109/ESTS.2013.6523782","DOIUrl":null,"url":null,"abstract":"We present a fast and effective method for detecting and isolating faults in multi-terminal medium voltage dc shipboard power distribution systems. This new detection method permits coordination between the power supply converters and a set of bus segmentizing contactors without requiring fast communication between the elements. The power converters go into current-limiting mode as soon they recognize a fault condition and the segmentizing contactors autonomously decide whether or not to open based on local interpretation of time-to-trip curves as functions of apparent circuit resistance. This method allows converters and contactors to use only local measurements when deciding whether or not to trip in order to isolate the faulted section (later fine tuning can rely on communications). Simulation and experimental results show that faults can be isolated within 10 to 20 ms and the system can be re-energized within 40 to 60 ms.","PeriodicalId":119318,"journal":{"name":"2013 IEEE Electric Ship Technologies Symposium (ESTS)","volume":"20 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2013-04-22","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"25","resultStr":"{\"title\":\"Coordination between supply power converters and contactors for fault protection in multi-terminal MVDC distribution systems\",\"authors\":\"P. Cairoli, R. Dougal, K. Lentijo\",\"doi\":\"10.1109/ESTS.2013.6523782\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"We present a fast and effective method for detecting and isolating faults in multi-terminal medium voltage dc shipboard power distribution systems. This new detection method permits coordination between the power supply converters and a set of bus segmentizing contactors without requiring fast communication between the elements. The power converters go into current-limiting mode as soon they recognize a fault condition and the segmentizing contactors autonomously decide whether or not to open based on local interpretation of time-to-trip curves as functions of apparent circuit resistance. This method allows converters and contactors to use only local measurements when deciding whether or not to trip in order to isolate the faulted section (later fine tuning can rely on communications). Simulation and experimental results show that faults can be isolated within 10 to 20 ms and the system can be re-energized within 40 to 60 ms.\",\"PeriodicalId\":119318,\"journal\":{\"name\":\"2013 IEEE Electric Ship Technologies Symposium (ESTS)\",\"volume\":\"20 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2013-04-22\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"25\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2013 IEEE Electric Ship Technologies Symposium (ESTS)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ESTS.2013.6523782\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2013 IEEE Electric Ship Technologies Symposium (ESTS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ESTS.2013.6523782","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 25

摘要

提出了一种快速有效的船舶多端中压直流配电系统故障检测与隔离方法。这种新的检测方法允许电源转换器和一组总线分割接触器之间的协调,而不需要元件之间的快速通信。电源变换器识别出故障后立即进入限流模式,分段接触器根据视电阻对脱扣时间曲线的局部解释自主决定是否断开。这种方法允许转换器和接触器在决定是否跳闸时仅使用本地测量,以便隔离故障部分(稍后的微调可以依赖于通信)。仿真和实验结果表明,该方法能在10 ~ 20 ms内隔离故障,在40 ~ 60 ms内重新通电。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Coordination between supply power converters and contactors for fault protection in multi-terminal MVDC distribution systems
We present a fast and effective method for detecting and isolating faults in multi-terminal medium voltage dc shipboard power distribution systems. This new detection method permits coordination between the power supply converters and a set of bus segmentizing contactors without requiring fast communication between the elements. The power converters go into current-limiting mode as soon they recognize a fault condition and the segmentizing contactors autonomously decide whether or not to open based on local interpretation of time-to-trip curves as functions of apparent circuit resistance. This method allows converters and contactors to use only local measurements when deciding whether or not to trip in order to isolate the faulted section (later fine tuning can rely on communications). Simulation and experimental results show that faults can be isolated within 10 to 20 ms and the system can be re-energized within 40 to 60 ms.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Pole-restraining control for Modular Multilevel Converters in electric-ship applications Generic modeling and analysis framework for shipboard system design Electric generation technologies for all-electric ships with Medium-Voltage DC power distribution systems Electrical machine iron loss predictions - A unique engineering approach utilizing transient finite element methods - Part 1: Theory and calculation method Modular Multilevel Converter for propulsion system of electric ships
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1