功率摇摆和失步工况下故障分析工具的评价

A. Esmaeilian, M. Kezunovic
{"title":"功率摇摆和失步工况下故障分析工具的评价","authors":"A. Esmaeilian, M. Kezunovic","doi":"10.1109/NAPS.2014.6965415","DOIUrl":null,"url":null,"abstract":"Several major blackouts were caused by distance relay mis-operation. Distance relay mis-operation may occur following a large disturbance in the system causing power swing and out-of-step conditions. If an on-line fault analysis tool is able to detect power swing or out-of-step conditions and indicate mis-operation of relays, the operator may be notified to switch back the healthy transmission lines tripped due to relay mis-operation. A new automated fault analysis tool comprising fault detection, classification and location has been developed and its performance under various power swing and out-of-step conditions is reported. The test results indicate that the fault analysis tool performs better than distance relay under power swing and out of-step conditions and can be used as a tool to verify distance relay operation in practical circumstances. The simulations have been performed using IEEE118 bus test system modeled in ATP software.","PeriodicalId":421766,"journal":{"name":"2014 North American Power Symposium (NAPS)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2014-11-24","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"5","resultStr":"{\"title\":\"Evaluation of fault analysis tool under power swing and out-of-step conditions\",\"authors\":\"A. Esmaeilian, M. Kezunovic\",\"doi\":\"10.1109/NAPS.2014.6965415\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Several major blackouts were caused by distance relay mis-operation. Distance relay mis-operation may occur following a large disturbance in the system causing power swing and out-of-step conditions. If an on-line fault analysis tool is able to detect power swing or out-of-step conditions and indicate mis-operation of relays, the operator may be notified to switch back the healthy transmission lines tripped due to relay mis-operation. A new automated fault analysis tool comprising fault detection, classification and location has been developed and its performance under various power swing and out-of-step conditions is reported. The test results indicate that the fault analysis tool performs better than distance relay under power swing and out of-step conditions and can be used as a tool to verify distance relay operation in practical circumstances. The simulations have been performed using IEEE118 bus test system modeled in ATP software.\",\"PeriodicalId\":421766,\"journal\":{\"name\":\"2014 North American Power Symposium (NAPS)\",\"volume\":\"1 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2014-11-24\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"5\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2014 North American Power Symposium (NAPS)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/NAPS.2014.6965415\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2014 North American Power Symposium (NAPS)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/NAPS.2014.6965415","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 5

摘要

几次大停电都是由距离继电器误操作造成的。当系统中出现较大的扰动导致功率摆动和失步时,可能会发生距离继电器误动作。如果在线故障分析工具能够检测到功率摆动或失步情况,并指示继电器误操作,则可以通知操作人员将由于继电器误操作而跳闸的健康输电线路切换回。本文介绍了一种新的故障自动分析工具,包括故障检测、分类和定位,并报道了该工具在各种功率摆动和失步工况下的性能。试验结果表明,该故障分析工具在功率摆幅和失步工况下的性能优于距离继电器,可作为验证距离继电器实际运行情况的工具。利用ATP软件建模的IEEE118总线测试系统进行了仿真。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Evaluation of fault analysis tool under power swing and out-of-step conditions
Several major blackouts were caused by distance relay mis-operation. Distance relay mis-operation may occur following a large disturbance in the system causing power swing and out-of-step conditions. If an on-line fault analysis tool is able to detect power swing or out-of-step conditions and indicate mis-operation of relays, the operator may be notified to switch back the healthy transmission lines tripped due to relay mis-operation. A new automated fault analysis tool comprising fault detection, classification and location has been developed and its performance under various power swing and out-of-step conditions is reported. The test results indicate that the fault analysis tool performs better than distance relay under power swing and out of-step conditions and can be used as a tool to verify distance relay operation in practical circumstances. The simulations have been performed using IEEE118 bus test system modeled in ATP software.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Addressing cyber security for the oil, gas and energy sector Investigation of voltage stability in three-phase unbalanced distribution systems with DG using modal analysis technique Dynamic Remedial Action Scheme using online transient stability analysis Implementing a real-time cyber-physical system test bed in RTDS and OPNET Size reduction of permanent magnet generators for wind turbines with higher energy density permanent magnets
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1