从各种化学和介电测量评价变压器油在工作负荷下的老化

J. Crine, M. Duval, C. Lamarre
{"title":"从各种化学和介电测量评价变压器油在工作负荷下的老化","authors":"J. Crine, M. Duval, C. Lamarre","doi":"10.1109/EIC.1982.7464430","DOIUrl":null,"url":null,"abstract":"Oil from transformers under normal service load was analyzed by several techniques in order to determine the degree of aging and the best aging evaluation method. The interfacial tension was found to vary with the antioxidant concentration but it is also affected by exposure to daylight, which implies that samples should be measured without too long a delay. Carbonyl and polar groups were determined by IR and HPLC, respectively. The dissolved capper content in the oil, which modifies the tan o values, was determined by neutron activation analysis. Tan δ and dielectric breakdown are not really conclusive tests because of their sensitivity to contamination. The best techniques to evaluate the aging of transformer oil, and to predict its lifetime, are interfacial tension and antioxidant concentration (above 100–150 ppm) measurements and HPLC analysis for lower concentrations.","PeriodicalId":422317,"journal":{"name":"1982 IEEE International Conference on Electrical Insulation","volume":"23 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1982-06-07","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"3","resultStr":"{\"title\":\"Evaluation of transformer oil aging under service load from various chemical and dielectric measurements\",\"authors\":\"J. Crine, M. Duval, C. Lamarre\",\"doi\":\"10.1109/EIC.1982.7464430\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Oil from transformers under normal service load was analyzed by several techniques in order to determine the degree of aging and the best aging evaluation method. The interfacial tension was found to vary with the antioxidant concentration but it is also affected by exposure to daylight, which implies that samples should be measured without too long a delay. Carbonyl and polar groups were determined by IR and HPLC, respectively. The dissolved capper content in the oil, which modifies the tan o values, was determined by neutron activation analysis. Tan δ and dielectric breakdown are not really conclusive tests because of their sensitivity to contamination. The best techniques to evaluate the aging of transformer oil, and to predict its lifetime, are interfacial tension and antioxidant concentration (above 100–150 ppm) measurements and HPLC analysis for lower concentrations.\",\"PeriodicalId\":422317,\"journal\":{\"name\":\"1982 IEEE International Conference on Electrical Insulation\",\"volume\":\"23 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"1982-06-07\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"3\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"1982 IEEE International Conference on Electrical Insulation\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/EIC.1982.7464430\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"1982 IEEE International Conference on Electrical Insulation","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/EIC.1982.7464430","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3

摘要

为了确定变压器在正常工作负荷下的老化程度和最佳的老化评定方法,采用多种技术对变压器油进行了分析。发现界面张力随抗氧化剂浓度而变化,但它也受到日光照射的影响,这意味着样品的测量不应延迟太长时间。红外光谱法和高效液相色谱法分别测定了羰基和极性基团。用中子活化法测定了油品中溶解盖普的含量,它改变了tan - o值。由于Tan δ和介电击穿对污染的敏感性,它们不是真正的结论性试验。评估变压器油老化和预测其寿命的最佳技术是界面张力和抗氧化剂浓度(高于100-150 ppm)的测量和低浓度的HPLC分析。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Evaluation of transformer oil aging under service load from various chemical and dielectric measurements
Oil from transformers under normal service load was analyzed by several techniques in order to determine the degree of aging and the best aging evaluation method. The interfacial tension was found to vary with the antioxidant concentration but it is also affected by exposure to daylight, which implies that samples should be measured without too long a delay. Carbonyl and polar groups were determined by IR and HPLC, respectively. The dissolved capper content in the oil, which modifies the tan o values, was determined by neutron activation analysis. Tan δ and dielectric breakdown are not really conclusive tests because of their sensitivity to contamination. The best techniques to evaluate the aging of transformer oil, and to predict its lifetime, are interfacial tension and antioxidant concentration (above 100–150 ppm) measurements and HPLC analysis for lower concentrations.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Impulse corona in positive rod-plane gaps filled with SF6 gas mixtures Polymer concrete as a dielectric material a critical assessment of the state-of-the-art Estimation of cable life and service reliability A prediction of deposition of contaminants on insulator surface with and without grading rings Influence of electrode surface roughness on the impulse breakdown probabilities of SF6
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1