利用 CFD 仿真研究中庭侧墙喷淋器的启动问题

Q2 Mathematics CFD Letters Pub Date : 2024-07-05 DOI:10.37934/cfdl.16.11.92110
Jaime III Reyes, Jaime Honra
{"title":"利用 CFD 仿真研究中庭侧墙喷淋器的启动问题","authors":"Jaime III Reyes, Jaime Honra","doi":"10.37934/cfdl.16.11.92110","DOIUrl":null,"url":null,"abstract":"This study investigates the actuation of sidewall sprinklers in large-scale buildings with high-ceilinged atriums, addressing the challenges of unique architectural configurations. Compliance with NFPA 101 requires automatic sprinkler systems, including atrium areas, in these buildings. To maintain aesthetic considerations, design engineers, particularly in the middle east, often propose sidewall sprinklers as an alternative to traditional ceiling sprinklers. This research assesses whether the sidewall sprinklers would actuate during a fire using Fire Dynamic Simulator (FDS). The findings indicate that sidewall sprinklers will fail to actuate if the fire is located at the centre of the atrium, even if the edge of the fire area is below the sprinklers. Furthermore, the study emphasizes the importance of using an FDS mesh resolution (D*/dx) of 6 or finer resolution when measuring temperatures near the flame or fire plume to ensure accurate evaluations of sprinkler activation. These findings provide valuable insights for design engineers and authorities, assisting in decision-making processes related to fire safety measures, system designs, and regulatory compliance.","PeriodicalId":9736,"journal":{"name":"CFD Letters","volume":" 9","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2024-07-05","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Investigating the Actuation of Sidewall Sprinkler in an Atrium Using CFD Simulation\",\"authors\":\"Jaime III Reyes, Jaime Honra\",\"doi\":\"10.37934/cfdl.16.11.92110\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"This study investigates the actuation of sidewall sprinklers in large-scale buildings with high-ceilinged atriums, addressing the challenges of unique architectural configurations. Compliance with NFPA 101 requires automatic sprinkler systems, including atrium areas, in these buildings. To maintain aesthetic considerations, design engineers, particularly in the middle east, often propose sidewall sprinklers as an alternative to traditional ceiling sprinklers. This research assesses whether the sidewall sprinklers would actuate during a fire using Fire Dynamic Simulator (FDS). The findings indicate that sidewall sprinklers will fail to actuate if the fire is located at the centre of the atrium, even if the edge of the fire area is below the sprinklers. Furthermore, the study emphasizes the importance of using an FDS mesh resolution (D*/dx) of 6 or finer resolution when measuring temperatures near the flame or fire plume to ensure accurate evaluations of sprinkler activation. These findings provide valuable insights for design engineers and authorities, assisting in decision-making processes related to fire safety measures, system designs, and regulatory compliance.\",\"PeriodicalId\":9736,\"journal\":{\"name\":\"CFD Letters\",\"volume\":\" 9\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2024-07-05\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"CFD Letters\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.37934/cfdl.16.11.92110\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q2\",\"JCRName\":\"Mathematics\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"CFD Letters","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.37934/cfdl.16.11.92110","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q2","JCRName":"Mathematics","Score":null,"Total":0}
引用次数: 0

摘要

本研究调查了带有高天花板中庭的大型建筑中侧壁自动喷水灭火系统的启动情况,以应对独特建筑结构所带来的挑战。NFPA 101 标准要求在这些建筑中安装自动喷水灭火系统,包括中庭区域。为了保持美观,设计工程师(尤其是中东地区的设计工程师)通常会建议采用侧墙自动喷水灭火系统来替代传统的天花板自动喷水灭火系统。本研究使用火灾动态模拟器(FDS)评估了侧壁水喷淋设施在火灾中是否会启动。研究结果表明,如果火势位于中庭中心,即使着火区域的边缘低于水喷淋设施,侧墙水喷淋设施也无法启动。此外,研究还强调,在测量火焰或火羽附近的温度时,必须使用 6 分辨率或更精细分辨率的 FDS 网格(D*/dx),以确保准确评估水喷淋设施的启动情况。这些发现为设计工程师和管理机构提供了宝贵的见解,有助于与消防安全措施、系统设计和法规遵从相关的决策过程。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Investigating the Actuation of Sidewall Sprinkler in an Atrium Using CFD Simulation
This study investigates the actuation of sidewall sprinklers in large-scale buildings with high-ceilinged atriums, addressing the challenges of unique architectural configurations. Compliance with NFPA 101 requires automatic sprinkler systems, including atrium areas, in these buildings. To maintain aesthetic considerations, design engineers, particularly in the middle east, often propose sidewall sprinklers as an alternative to traditional ceiling sprinklers. This research assesses whether the sidewall sprinklers would actuate during a fire using Fire Dynamic Simulator (FDS). The findings indicate that sidewall sprinklers will fail to actuate if the fire is located at the centre of the atrium, even if the edge of the fire area is below the sprinklers. Furthermore, the study emphasizes the importance of using an FDS mesh resolution (D*/dx) of 6 or finer resolution when measuring temperatures near the flame or fire plume to ensure accurate evaluations of sprinkler activation. These findings provide valuable insights for design engineers and authorities, assisting in decision-making processes related to fire safety measures, system designs, and regulatory compliance.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
CFD Letters
CFD Letters Chemical Engineering-Fluid Flow and Transfer Processes
CiteScore
3.40
自引率
0.00%
发文量
76
期刊最新文献
Numerical Investigation of Thermal Performance for Turbulent Water Flow through Dimpled Pipe MHD Stagnation Point Flow of Micropolar Fluid over a Stretching/ Shrinking Sheet Unsteady MHD Walter’s-B Viscoelastic Flow Past a Vertical Porous Plate Effects of Activation Energy and Diffusion Thermo an Unsteady MHD Maxwell Fluid Flow over a Porous Vertical Stretched Sheet in the Presence of Thermophoresis and Brownian Motion Effect of Inlet Pressure on the Polyurethane Spray Nozzle for Soil Cracking Improvement: Simulations using CFD Method
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1