基于特高压换流站的交流滤波器跳闸事故分析

Ye Ai, Ruixuan Bi, Mengchao Ma, Pei Li, Lina Chen, Haifeng Li
{"title":"基于特高压换流站的交流滤波器跳闸事故分析","authors":"Ye Ai, Ruixuan Bi, Mengchao Ma, Pei Li, Lina Chen, Haifeng Li","doi":"10.1088/1742-6596/2774/1/012058","DOIUrl":null,"url":null,"abstract":"\n An AC filter tripping accident occurred in a converter station of the North China Power Grid in 2019, which seriously affected the safe and stable operation of the power grid. In this paper, combined with the configuration of the AC filter in the converter station and the principle of capacitor unbalance protection, the tripping mechanism of the AC filter is explained. It is considered that the direct cause of the tripping of the AC filter is the short-circuit discharge phenomenon between the layers caused by the dead trees (grass) branches on the capacitor tower, which causes the instantaneous fault between the layers of the low-voltage capacitor, and finally leads to the action of the capacitor unbalance protection. From the perspective of operation and maintenance, some practical preventive measures are put forward, which will help to improve the safety of AC filter operation in the future, and then improve the reliability of DC transmission system, especially during the peak summer, peak winter and special power protection period, to ensure that there will be no fluctuation in DC load transmission and protect the safe and stable operation of power grid.","PeriodicalId":506941,"journal":{"name":"Journal of Physics: Conference Series","volume":"83 6","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2024-07-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Analysis of AC Filter Tripping Accident based on UHV Converter Station\",\"authors\":\"Ye Ai, Ruixuan Bi, Mengchao Ma, Pei Li, Lina Chen, Haifeng Li\",\"doi\":\"10.1088/1742-6596/2774/1/012058\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"\\n An AC filter tripping accident occurred in a converter station of the North China Power Grid in 2019, which seriously affected the safe and stable operation of the power grid. In this paper, combined with the configuration of the AC filter in the converter station and the principle of capacitor unbalance protection, the tripping mechanism of the AC filter is explained. It is considered that the direct cause of the tripping of the AC filter is the short-circuit discharge phenomenon between the layers caused by the dead trees (grass) branches on the capacitor tower, which causes the instantaneous fault between the layers of the low-voltage capacitor, and finally leads to the action of the capacitor unbalance protection. From the perspective of operation and maintenance, some practical preventive measures are put forward, which will help to improve the safety of AC filter operation in the future, and then improve the reliability of DC transmission system, especially during the peak summer, peak winter and special power protection period, to ensure that there will be no fluctuation in DC load transmission and protect the safe and stable operation of power grid.\",\"PeriodicalId\":506941,\"journal\":{\"name\":\"Journal of Physics: Conference Series\",\"volume\":\"83 6\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2024-07-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Journal of Physics: Conference Series\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1088/1742-6596/2774/1/012058\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of Physics: Conference Series","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1088/1742-6596/2774/1/012058","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

2019年华北电网某换流站发生交流滤波器跳闸事故,严重影响了电网的安全稳定运行。本文结合换流站交流滤波器的配置和电容器不平衡保护原理,阐述了交流滤波器的跳闸机理。认为交流滤波器跳闸的直接原因是电容器塔上枯树(草)枝引起的层间短路放电现象,造成低压电容器层间瞬时故障,最终导致电容器不平衡保护动作。从运行维护的角度出发,提出了一些切实可行的预防措施,有助于提高今后交流滤波器运行的安全性,进而提高直流输电系统的可靠性,特别是在迎峰度夏、迎峰度冬和特殊保电期间,确保直流负荷输送不出现波动,保障电网安全稳定运行。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Analysis of AC Filter Tripping Accident based on UHV Converter Station
An AC filter tripping accident occurred in a converter station of the North China Power Grid in 2019, which seriously affected the safe and stable operation of the power grid. In this paper, combined with the configuration of the AC filter in the converter station and the principle of capacitor unbalance protection, the tripping mechanism of the AC filter is explained. It is considered that the direct cause of the tripping of the AC filter is the short-circuit discharge phenomenon between the layers caused by the dead trees (grass) branches on the capacitor tower, which causes the instantaneous fault between the layers of the low-voltage capacitor, and finally leads to the action of the capacitor unbalance protection. From the perspective of operation and maintenance, some practical preventive measures are put forward, which will help to improve the safety of AC filter operation in the future, and then improve the reliability of DC transmission system, especially during the peak summer, peak winter and special power protection period, to ensure that there will be no fluctuation in DC load transmission and protect the safe and stable operation of power grid.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
LPI radar waveform recognition model based on multiple feature image and quasi-residual attention module About the 3D virtualization of the Millikan oil drop experiment Study on the characteristics of the bypass flow field of the net structure under different Reynolds number conditions Exploring the Universe through Gamma-Ray Astronomy: Characterization and Performance of the LST-1 Telescope Analysis of structural dynamic response of vertical sound barriers under natural wind and vehicle induced pulsating wind effects
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1