基于磁化浪涌电流波形预测的变流器变压器饱和保护防止误动作方案

IF 1.6 4区 工程技术 Q3 ENGINEERING, ELECTRICAL & ELECTRONIC Electrical Engineering Pub Date : 2024-08-29 DOI:10.1007/s00202-024-02668-2
Yaming Ge, Junchao Zheng, Xuchao Ren, Shi Chen, Xiangping Kong, Chenqing Wang
{"title":"基于磁化浪涌电流波形预测的变流器变压器饱和保护防止误动作方案","authors":"Yaming Ge, Junchao Zheng, Xuchao Ren, Shi Chen, Xiangping Kong, Chenqing Wang","doi":"10.1007/s00202-024-02668-2","DOIUrl":null,"url":null,"abstract":"<p>In high-voltage direct current transmission systems, the unloaded energizations of converter transformers may cause magnetizing inrush currents with high amplitude and slow decaying, as well as the zero-sequence inrush current in the neutral line. This may cause the maloperation of saturation protection based on the amplitude of the neutral line current. Aiming at this problem, a scheme for preventing the maloperation of converter transformer saturation protection based on the waveform prediction of magnetizing inrush current is proposed. The proposed scheme utilizes the differences between the mathematical models of pure magnetizing inrush and magnetizing inrush superimposed with DC bias. Based on the mathematical analytical expression of magnetizing inrush current during the transformer unloaded energization, the complete waveform of the second cycle of phase current is predicted by using the actual measured values of the phase current within 1¼ cycles. The deviation between the predicted and measured peak values of the phase current of the second cycle is calculated. On this base, a modification coefficient is constructed to modify the measured current in the neutral line, which eliminates the influence of magnetizing inrush and prevents the maloperation of saturation protection. Simulation results indicate that the proposed scheme can separate the influences of magnetizing inrush and DC bias on the saturation protection, effectively preventing the maloperation of saturation protection caused by magnetizing inrush.</p>","PeriodicalId":50546,"journal":{"name":"Electrical Engineering","volume":null,"pages":null},"PeriodicalIF":1.6000,"publicationDate":"2024-08-29","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Preventing maloperation scheme for saturation protection of converter transformers based on waveform prediction of magnetizing inrush current\",\"authors\":\"Yaming Ge, Junchao Zheng, Xuchao Ren, Shi Chen, Xiangping Kong, Chenqing Wang\",\"doi\":\"10.1007/s00202-024-02668-2\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"<p>In high-voltage direct current transmission systems, the unloaded energizations of converter transformers may cause magnetizing inrush currents with high amplitude and slow decaying, as well as the zero-sequence inrush current in the neutral line. This may cause the maloperation of saturation protection based on the amplitude of the neutral line current. Aiming at this problem, a scheme for preventing the maloperation of converter transformer saturation protection based on the waveform prediction of magnetizing inrush current is proposed. The proposed scheme utilizes the differences between the mathematical models of pure magnetizing inrush and magnetizing inrush superimposed with DC bias. Based on the mathematical analytical expression of magnetizing inrush current during the transformer unloaded energization, the complete waveform of the second cycle of phase current is predicted by using the actual measured values of the phase current within 1¼ cycles. The deviation between the predicted and measured peak values of the phase current of the second cycle is calculated. On this base, a modification coefficient is constructed to modify the measured current in the neutral line, which eliminates the influence of magnetizing inrush and prevents the maloperation of saturation protection. Simulation results indicate that the proposed scheme can separate the influences of magnetizing inrush and DC bias on the saturation protection, effectively preventing the maloperation of saturation protection caused by magnetizing inrush.</p>\",\"PeriodicalId\":50546,\"journal\":{\"name\":\"Electrical Engineering\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":1.6000,\"publicationDate\":\"2024-08-29\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Electrical Engineering\",\"FirstCategoryId\":\"5\",\"ListUrlMain\":\"https://doi.org/10.1007/s00202-024-02668-2\",\"RegionNum\":4,\"RegionCategory\":\"工程技术\",\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q3\",\"JCRName\":\"ENGINEERING, ELECTRICAL & ELECTRONIC\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Electrical Engineering","FirstCategoryId":"5","ListUrlMain":"https://doi.org/10.1007/s00202-024-02668-2","RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0

摘要

在高压直流输电系统中,变流器变压器的空载通电可能会导致幅值大、衰减慢的磁化浪涌电流,以及中性线上的零序浪涌电流。这可能会导致基于中性线电流幅值的饱和保护误动作。针对这一问题,提出了一种基于磁化浪涌电流波形预测的防止变流器变压器饱和保护误动作的方案。所提方案利用了纯磁化浪涌和叠加直流偏置的磁化浪涌数学模型之间的差异。根据变压器空载通电时磁化浪涌电流的数学分析表达式,利用 1¼ 个周期内相电流的实际测量值来预测相电流第二个周期的完整波形。计算第二个周期相电流预测值和测量值峰值之间的偏差。在此基础上,构建一个修正系数来修正中性线上的测量电流,从而消除磁化浪涌的影响,防止饱和保护误动作。仿真结果表明,所提出的方案可以分离磁浪涌和直流偏置对饱和保护的影响,有效防止磁浪涌引起的饱和保护误动作。
本文章由计算机程序翻译,如有差异,请以英文原文为准。

摘要图片

查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Preventing maloperation scheme for saturation protection of converter transformers based on waveform prediction of magnetizing inrush current

In high-voltage direct current transmission systems, the unloaded energizations of converter transformers may cause magnetizing inrush currents with high amplitude and slow decaying, as well as the zero-sequence inrush current in the neutral line. This may cause the maloperation of saturation protection based on the amplitude of the neutral line current. Aiming at this problem, a scheme for preventing the maloperation of converter transformer saturation protection based on the waveform prediction of magnetizing inrush current is proposed. The proposed scheme utilizes the differences between the mathematical models of pure magnetizing inrush and magnetizing inrush superimposed with DC bias. Based on the mathematical analytical expression of magnetizing inrush current during the transformer unloaded energization, the complete waveform of the second cycle of phase current is predicted by using the actual measured values of the phase current within 1¼ cycles. The deviation between the predicted and measured peak values of the phase current of the second cycle is calculated. On this base, a modification coefficient is constructed to modify the measured current in the neutral line, which eliminates the influence of magnetizing inrush and prevents the maloperation of saturation protection. Simulation results indicate that the proposed scheme can separate the influences of magnetizing inrush and DC bias on the saturation protection, effectively preventing the maloperation of saturation protection caused by magnetizing inrush.

求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
Electrical Engineering
Electrical Engineering 工程技术-工程:电子与电气
CiteScore
3.60
自引率
16.70%
发文量
0
审稿时长
>12 weeks
期刊介绍: The journal “Electrical Engineering” following the long tradition of Archiv für Elektrotechnik publishes original papers of archival value in electrical engineering with a strong focus on electric power systems, smart grid approaches to power transmission and distribution, power system planning, operation and control, electricity markets, renewable power generation, microgrids, power electronics, electrical machines and drives, electric vehicles, railway electrification systems and electric transportation infrastructures, energy storage in electric power systems and vehicles, high voltage engineering, electromagnetic transients in power networks, lightning protection, electrical safety, electrical insulation systems, apparatus, devices, and components. Manuscripts describing theoretical, computer application and experimental research results are welcomed. Electrical Engineering - Archiv für Elektrotechnik is published in agreement with Verband der Elektrotechnik Elektronik Informationstechnik eV (VDE).
期刊最新文献
A method for assessing and locating protection measurement loop errors based on an improved similarity algorithm Microgrid energy management with renewable energy using gravitational search algorithm Generation expansion planning incorporating the recuperation of older power plants for economic advantage Robot dynamics-based cable fault diagnosis using stacked transformer encoder layers Rule based coordinated source and demand side energy management of a remote area power supply system
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1