一种基于运行试验的电力变压器内部故障和涌流鉴别方法

B. Fani, M. Golshan, H. Abyaneh, M. Saghaian-nejad
{"title":"一种基于运行试验的电力变压器内部故障和涌流鉴别方法","authors":"B. Fani, M. Golshan, H. Abyaneh, M. Saghaian-nejad","doi":"10.1002/ETEP.506","DOIUrl":null,"url":null,"abstract":"A new method based on runs test is proposed to distinguish the inrush currents from the internal faults in power transformers, which is derived from the inherent differences between these waveforms. First, two statistical hypotheses that represent these differences are defined. Then by testing these hypotheses using runs test and by comparing the outputs of the hypotheses, a criterion to identify the internal fault is obtained. A total of 200 experimental cases are used to test the performance of the technique. In all of the tests, the proposed method accurately distinguished between fault and inrush currents without any errors. Also the suitable performance of the method is demonstrated by simulation of different faults and switching conditions on a power transformer. For this purpose, a small part of Iran power system involving a power transformer and the transmission lines on both sides of the transformer has been considered. To include effective factors on differential current components, the elements of this power system have been precisely modeled in PSCAD/EMTDC. Copyright © 2010 John Wiley & Sons, Ltd.","PeriodicalId":50474,"journal":{"name":"European Transactions on Electrical Power","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"2011-04-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://sci-hub-pdf.com/10.1002/ETEP.506","citationCount":"5","resultStr":"{\"title\":\"A runs test‐based method for discrimination between internal faults and inrush currents in power transformers\",\"authors\":\"B. Fani, M. Golshan, H. Abyaneh, M. Saghaian-nejad\",\"doi\":\"10.1002/ETEP.506\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"A new method based on runs test is proposed to distinguish the inrush currents from the internal faults in power transformers, which is derived from the inherent differences between these waveforms. First, two statistical hypotheses that represent these differences are defined. Then by testing these hypotheses using runs test and by comparing the outputs of the hypotheses, a criterion to identify the internal fault is obtained. A total of 200 experimental cases are used to test the performance of the technique. In all of the tests, the proposed method accurately distinguished between fault and inrush currents without any errors. Also the suitable performance of the method is demonstrated by simulation of different faults and switching conditions on a power transformer. For this purpose, a small part of Iran power system involving a power transformer and the transmission lines on both sides of the transformer has been considered. To include effective factors on differential current components, the elements of this power system have been precisely modeled in PSCAD/EMTDC. Copyright © 2010 John Wiley & Sons, Ltd.\",\"PeriodicalId\":50474,\"journal\":{\"name\":\"European Transactions on Electrical Power\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2011-04-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"https://sci-hub-pdf.com/10.1002/ETEP.506\",\"citationCount\":\"5\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"European Transactions on Electrical Power\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1002/ETEP.506\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"European Transactions on Electrical Power","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1002/ETEP.506","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 5

摘要

根据励磁涌流波形与励磁涌流波形之间的内在差异,提出了一种基于运行试验的励磁涌流与励磁涌流波形鉴别方法。首先,定义了代表这些差异的两个统计假设。然后通过运行测试对这些假设进行检验,并通过比较假设的输出,得到一个识别内部故障的准则。通过200个实验实例验证了该技术的性能。在所有的测试中,该方法准确地区分了故障电流和涌流,没有任何误差。通过对电力变压器不同故障和开关状态的仿真,验证了该方法的有效性。为此,考虑了伊朗电力系统中涉及电力变压器和变压器两侧输电线路的一小部分。为了包括差分电流分量的有效因素,该电力系统的元件已在PSCAD/EMTDC中精确建模。版权所有©2010 John Wiley & Sons, Ltd
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
A runs test‐based method for discrimination between internal faults and inrush currents in power transformers
A new method based on runs test is proposed to distinguish the inrush currents from the internal faults in power transformers, which is derived from the inherent differences between these waveforms. First, two statistical hypotheses that represent these differences are defined. Then by testing these hypotheses using runs test and by comparing the outputs of the hypotheses, a criterion to identify the internal fault is obtained. A total of 200 experimental cases are used to test the performance of the technique. In all of the tests, the proposed method accurately distinguished between fault and inrush currents without any errors. Also the suitable performance of the method is demonstrated by simulation of different faults and switching conditions on a power transformer. For this purpose, a small part of Iran power system involving a power transformer and the transmission lines on both sides of the transformer has been considered. To include effective factors on differential current components, the elements of this power system have been precisely modeled in PSCAD/EMTDC. Copyright © 2010 John Wiley & Sons, Ltd.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
European Transactions on Electrical Power
European Transactions on Electrical Power 工程技术-工程:电子与电气
自引率
0.00%
发文量
0
审稿时长
5.4 months
期刊最新文献
A fault location method based on genetic algorithm for high‐voltage direct current transmission line Generation companies' adaptive bidding strategies using finite-state automata in a single-sided electricity market Modelling and evaluation of the lightning arc between a power line and a nearby tree Inductance profile calculation of step winding structure in tubular linear reluctance motor using three-dimensional finite element method Study on microstructure and electrical properties of oil‐impregnated paper insulation after exposure to partial discharge
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1