JIS B 8628和JIS B 8639规定的试验设置差异对能量回收通风机性能值影响的实验研究

IF 1.2 4区 工程技术 Q3 THERMODYNAMICS Journal of Thermal Science and Technology Pub Date : 2020-01-01 DOI:10.1299/jtst.2020jtst0027
Tetsutoshi Kan, T. Sawachi, Yuki Nagumo
{"title":"JIS B 8628和JIS B 8639规定的试验设置差异对能量回收通风机性能值影响的实验研究","authors":"Tetsutoshi Kan, T. Sawachi, Yuki Nagumo","doi":"10.1299/jtst.2020jtst0027","DOIUrl":null,"url":null,"abstract":"JIS B 8628, “Air-to-air heat and energy exchanger and ventilators” provides standards for evaluating the performance of the energy recovery ventilators. JIS B 8628 was established in 2000, and revised in 2003. In 2017, JIS B 8628 was revised furthermore to ensure consistency with ISO 16494, which was established in 2014. For that purpose, the two room setup and the ducted setup, which are prescribed in ISO 16494 with specified pressure conditions at inlet and outlet of energy recovery ventilators for the airflow test, the tracer gas test and the thermal performance test, were added in JIS B 8628 (2017). In Japan, either the two room setup or the ducted setup is being used by manufacturers to determine the performance values, which are referred to when the compliance of total building energy performance to the Building Energy Efficiency Act is claimed. However, no studies have yet focused on the difference of the test results between the two room setup and the ducted setup. In this study, authors applied those setups and the test setup prescribed in JIS B 8628 (2003) to four energy recovery ventilators and compared their results. As for the airflow-static pressure characteristics, the curves obtained by the three test setups generally correspond to each other, except for the curves for the air exhaust line obtained by JIS B 8628 (2003). The unit exhaust air transfer ratio values obtained by the ducted setup and JIS B 8628 (2003) tend to be greater than those by the two room setup. As for the thermal performance represented by the total effectiveness, differences among the three test setups can be observed when there is a difference of the unit exhaust air transfer ratio and/or the ratio of the supply airflow rate to the return airflow rate.","PeriodicalId":17405,"journal":{"name":"Journal of Thermal Science and Technology","volume":null,"pages":null},"PeriodicalIF":1.2000,"publicationDate":"2020-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"An experimental study on how the difference between the test setups specified in JIS B 8628 and JIS B 8639 affects the performance values of energy recovery ventilators\",\"authors\":\"Tetsutoshi Kan, T. Sawachi, Yuki Nagumo\",\"doi\":\"10.1299/jtst.2020jtst0027\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"JIS B 8628, “Air-to-air heat and energy exchanger and ventilators” provides standards for evaluating the performance of the energy recovery ventilators. JIS B 8628 was established in 2000, and revised in 2003. In 2017, JIS B 8628 was revised furthermore to ensure consistency with ISO 16494, which was established in 2014. For that purpose, the two room setup and the ducted setup, which are prescribed in ISO 16494 with specified pressure conditions at inlet and outlet of energy recovery ventilators for the airflow test, the tracer gas test and the thermal performance test, were added in JIS B 8628 (2017). In Japan, either the two room setup or the ducted setup is being used by manufacturers to determine the performance values, which are referred to when the compliance of total building energy performance to the Building Energy Efficiency Act is claimed. However, no studies have yet focused on the difference of the test results between the two room setup and the ducted setup. In this study, authors applied those setups and the test setup prescribed in JIS B 8628 (2003) to four energy recovery ventilators and compared their results. As for the airflow-static pressure characteristics, the curves obtained by the three test setups generally correspond to each other, except for the curves for the air exhaust line obtained by JIS B 8628 (2003). The unit exhaust air transfer ratio values obtained by the ducted setup and JIS B 8628 (2003) tend to be greater than those by the two room setup. As for the thermal performance represented by the total effectiveness, differences among the three test setups can be observed when there is a difference of the unit exhaust air transfer ratio and/or the ratio of the supply airflow rate to the return airflow rate.\",\"PeriodicalId\":17405,\"journal\":{\"name\":\"Journal of Thermal Science and Technology\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":1.2000,\"publicationDate\":\"2020-01-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Journal of Thermal Science and Technology\",\"FirstCategoryId\":\"5\",\"ListUrlMain\":\"https://doi.org/10.1299/jtst.2020jtst0027\",\"RegionNum\":4,\"RegionCategory\":\"工程技术\",\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q3\",\"JCRName\":\"THERMODYNAMICS\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of Thermal Science and Technology","FirstCategoryId":"5","ListUrlMain":"https://doi.org/10.1299/jtst.2020jtst0027","RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"THERMODYNAMICS","Score":null,"Total":0}
引用次数: 0

摘要

JIS B 8628“空气对空气热交换器和通风器”提供了评估能量回收通风器性能的标准。JIS B 8628于2000年制定,2003年修订。2017年,JIS B 8628进一步修订,以确保与2014年建立的ISO 16494保持一致。为此,在JIS B 8628(2017)中增加了ISO 16494中规定的两个房间设置和管道设置,在能量回收通风机的进出口处规定了用于气流试验、示踪气体试验和热性能试验的压力条件。在日本,制造商要么采用双房间设置,要么采用管道设置,以确定性能值,这是在声称符合《建筑能源效率法》的建筑总能源性能时所参考的。然而,目前还没有研究集中在两个房间设置和管道设置之间的测试结果的差异。在本研究中,作者将上述装置与JIS B 8628(2003)规定的测试装置应用于4台能量回收风机,并对其结果进行了比较。对于气流-静压特性,除了日本标准JIS B 8628(2003)的排风管线曲线外,三种试验装置得到的曲线基本一致。由导管装置和JIS B 8628(2003)获得的单位排风传动比值往往大于由两个房间装置获得的值。以总效能为代表的热工性能,当机组排风量换气量和/或送风风量与回风风量之比存在差异时,可以观察到三种试验装置之间的差异。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
An experimental study on how the difference between the test setups specified in JIS B 8628 and JIS B 8639 affects the performance values of energy recovery ventilators
JIS B 8628, “Air-to-air heat and energy exchanger and ventilators” provides standards for evaluating the performance of the energy recovery ventilators. JIS B 8628 was established in 2000, and revised in 2003. In 2017, JIS B 8628 was revised furthermore to ensure consistency with ISO 16494, which was established in 2014. For that purpose, the two room setup and the ducted setup, which are prescribed in ISO 16494 with specified pressure conditions at inlet and outlet of energy recovery ventilators for the airflow test, the tracer gas test and the thermal performance test, were added in JIS B 8628 (2017). In Japan, either the two room setup or the ducted setup is being used by manufacturers to determine the performance values, which are referred to when the compliance of total building energy performance to the Building Energy Efficiency Act is claimed. However, no studies have yet focused on the difference of the test results between the two room setup and the ducted setup. In this study, authors applied those setups and the test setup prescribed in JIS B 8628 (2003) to four energy recovery ventilators and compared their results. As for the airflow-static pressure characteristics, the curves obtained by the three test setups generally correspond to each other, except for the curves for the air exhaust line obtained by JIS B 8628 (2003). The unit exhaust air transfer ratio values obtained by the ducted setup and JIS B 8628 (2003) tend to be greater than those by the two room setup. As for the thermal performance represented by the total effectiveness, differences among the three test setups can be observed when there is a difference of the unit exhaust air transfer ratio and/or the ratio of the supply airflow rate to the return airflow rate.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
CiteScore
2.30
自引率
8.30%
发文量
0
审稿时长
5 months
期刊介绍: JTST covers a variety of fields in thermal engineering including heat and mass transfer, thermodynamics, combustion, bio-heat transfer, micro- and macro-scale transport phenomena and practical thermal problems in industrial applications.
期刊最新文献
Development of a process for thin metal plates with electromagnetic pressure and surface tension Validation of Soave–Redlich–Kwong equation of state coupled with a classical mixing rule for sound speed of non-ideal gas mixture of oxygen-hydrogen as liquid rocket propellants Molecular dynamics simulation of energy transfer in reaction process near supported nanoparticle catalyst Improvement of isothermal characteristic of isothermal chamber by filling with graded copper foam Combined effects of diesel energy ratio and diesel injection nozzle diameter on natural gas high pressure direct injection engine with EGR
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1