{"title":"The Location of Partial Discharge Source in the Power Transformer with UHF Sensors","authors":"Naifan Xue, Junjie Yang","doi":"10.1109/ICSAI.2018.8599407","DOIUrl":null,"url":null,"abstract":"This paper discusses the theory of the location of the partial discharge and carries out a PD experiment with a real power transformer. Five Ultra high frequency (UHF) sensors are used to detect the PD source. The location of the PD source can be analyzed and calculated by establishing a power transformer model and collecting the electromagnetic signals generated from the PD source. A comparison between the actual PD source and the estimated location is also made. Time difference of arrival (TDOA) of distinct signals collected by different sensors can be used to search for the PD location. Distance equations are formulated based on the geometrical relationship and the 2-norm theory. To determine the time difference, first peak method is used in the power transformer model.","PeriodicalId":375852,"journal":{"name":"2018 5th International Conference on Systems and Informatics (ICSAI)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2018-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2018 5th International Conference on Systems and Informatics (ICSAI)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICSAI.2018.8599407","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1
Abstract
This paper discusses the theory of the location of the partial discharge and carries out a PD experiment with a real power transformer. Five Ultra high frequency (UHF) sensors are used to detect the PD source. The location of the PD source can be analyzed and calculated by establishing a power transformer model and collecting the electromagnetic signals generated from the PD source. A comparison between the actual PD source and the estimated location is also made. Time difference of arrival (TDOA) of distinct signals collected by different sensors can be used to search for the PD location. Distance equations are formulated based on the geometrical relationship and the 2-norm theory. To determine the time difference, first peak method is used in the power transformer model.
本文讨论了局部放电的定位原理,并在实际电力变压器上进行了局部放电实验。使用5个UHF (Ultra high frequency)传感器检测PD源。通过建立电力变压器模型,采集PD源产生的电磁信号,可以对PD源的位置进行分析计算。对实际PD源和估计位置进行了比较。利用不同传感器采集到的不同信号的到达时间差(TDOA)来搜索PD位置。根据几何关系和二范数理论建立了距离方程。在电力变压器模型中,采用首峰法确定时间差。