{"title":"Analysis of the insulated power-grid transient behavior after faulted phase tripping","authors":"N. Berbic, A. Nuhanovic, V. Madžarević","doi":"10.1109/MELCON.2004.1348219","DOIUrl":null,"url":null,"abstract":"The common cases of a nonselective operation of the phase to ground fault protection in the insulated power grids, which utilize inductive sensors for a voltage unbalance indication, are explained by ferroresonant processes in voltage transformers of healthy drains. This paper deals with phase to ground faults simulations in a known grid, that provide information about possible nonselective phase to ground faults protection operation.","PeriodicalId":164818,"journal":{"name":"Proceedings of the 12th IEEE Mediterranean Electrotechnical Conference (IEEE Cat. No.04CH37521)","volume":"12 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2004-05-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Proceedings of the 12th IEEE Mediterranean Electrotechnical Conference (IEEE Cat. No.04CH37521)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/MELCON.2004.1348219","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2
Abstract
The common cases of a nonselective operation of the phase to ground fault protection in the insulated power grids, which utilize inductive sensors for a voltage unbalance indication, are explained by ferroresonant processes in voltage transformers of healthy drains. This paper deals with phase to ground faults simulations in a known grid, that provide information about possible nonselective phase to ground faults protection operation.