Grid-Connected Low-Voltage Power Supply to Equipment on Transmission Line Structures

H. Ahmadi, M. Armstrong
{"title":"Grid-Connected Low-Voltage Power Supply to Equipment on Transmission Line Structures","authors":"H. Ahmadi, M. Armstrong","doi":"10.1109/CCECE47787.2020.9255707","DOIUrl":null,"url":null,"abstract":"Electrical equipment installed on high-voltage (HV) transmission structures may require low-voltage (LV) electrical supply from the distribution network. For example, cell sites for communication antennas and warning lights are the most common applications in BC Hydro's system. Bringing the LV supply to the HV structures introduces a number of electrical concerns. The first concern is the transfer of ground potential rise (GPR) from the HV system to the LV system during a ground fault on the transmission structure. The second concern is the induction in the LV system due to the proximity to the HV transmission line. In addition, there could be system impacts that require special attention, such as reduction in circuit-to-circuit separation in multiple-circuit corridors, pole fire on the LV wood poles, etc. This paper discusses technical solutions to mitigate the identified concerns and system impacts. Amongst the possible recommendations, addition of appropriately rated isolation transformers to the LV feeder and improving the electrical grounding on the HV transmission structure are shown to be the most effective methods for preventing the transfer of hazardous potentials to the customers connected to the same LV feeder. The proposed isolation circuit has been tested in a HV laboratory to confirm its effectiveness.","PeriodicalId":296506,"journal":{"name":"2020 IEEE Canadian Conference on Electrical and Computer Engineering (CCECE)","volume":"31 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2020-08-30","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2020 IEEE Canadian Conference on Electrical and Computer Engineering (CCECE)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CCECE47787.2020.9255707","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2

Abstract

Electrical equipment installed on high-voltage (HV) transmission structures may require low-voltage (LV) electrical supply from the distribution network. For example, cell sites for communication antennas and warning lights are the most common applications in BC Hydro's system. Bringing the LV supply to the HV structures introduces a number of electrical concerns. The first concern is the transfer of ground potential rise (GPR) from the HV system to the LV system during a ground fault on the transmission structure. The second concern is the induction in the LV system due to the proximity to the HV transmission line. In addition, there could be system impacts that require special attention, such as reduction in circuit-to-circuit separation in multiple-circuit corridors, pole fire on the LV wood poles, etc. This paper discusses technical solutions to mitigate the identified concerns and system impacts. Amongst the possible recommendations, addition of appropriately rated isolation transformers to the LV feeder and improving the electrical grounding on the HV transmission structure are shown to be the most effective methods for preventing the transfer of hazardous potentials to the customers connected to the same LV feeder. The proposed isolation circuit has been tested in a HV laboratory to confirm its effectiveness.
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
输电线结构设备并网低压供电
安装在高压(HV)输电结构上的电气设备可能需要配电网提供低压(LV)电力。例如,用于通信天线和警示灯的蜂窝站点是BC Hydro系统中最常见的应用。将低压电源引入高压结构引入了许多电气问题。第一个问题是在输电结构发生接地故障时,地电位上升(GPR)从高压系统转移到低压系统。第二个问题是低压系统的感应,由于接近高压输电线。此外,还可能存在需要特别注意的系统影响,例如多回路走廊中电路到电路分离的减少,低压木杆的极火等。本文讨论了减轻已确定的关注点和系统影响的技术解决方案。在可能的建议中,在低压馈线上增加适当额定的隔离变压器和改善高压输电结构的电气接地被证明是防止危险电位转移到连接到同一低压馈线的客户的最有效方法。所提出的隔离电路已在高压实验室进行了测试,以证实其有效性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Tracking Control of Force, Position, and Contour for an Excavator with Co-simulation Dual-Modality Cardiac Data Real-Time Rendering and Synchronization in Web Browsers FPGA-Based Evaluation and Implementation of an Automotive RADAR Signal Processing System using High-Level Synthesis A New Capacitive MEMS Flow Sensor for Industrial Gas Transport Monitoring Applications Voltage Stability Constrained Low-Carbon Generation & Transmission Expansion Planning
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1