О.A. Serhieiev, I.V. Kutniashenko, A. Toporov, V.M. Borovlоv, P. Tretiakov, O. Kostina
{"title":"STABILIZATION OF TEMPERATURE REGIME OF LABORATORY ROOM OF HIGH-PERFORMANCE COMPUTERS OF DONNTU","authors":"О.A. Serhieiev, I.V. Kutniashenko, A. Toporov, V.M. Borovlоv, P. Tretiakov, O. Kostina","doi":"10.31474/2308-5312-2020-1-14-12-20","DOIUrl":null,"url":null,"abstract":"Purpose: to analyze the thermal load of the server cluster of the high-performance computing laboratory, stabilize the temperature regime of the room throughout the year, taking into account seasonal changes in the ambient temperature. Methodology: performing experimental studies using modern devices and analyzing experimental data to assess the heat load of server clusters at various degrees of their workload with calculations. Results: a thermal analysis of the work of the server cluster of a high-performance computing laboratory was carried out at various degrees of server load with calculations. Temperature measurements were carried out for various zones and elements of server racks, temperature changes were established when the servers were loaded with calculations. In the modern CFD system, the air flows of the server cooling system and the temperature regime of the server cluster and the server room are simulated, taking into account the location of the equipment and information about the measurements of temperatures and air flow rates. As a result, temperature distributions were obtained for different server loads. A comparison of the supply and exhaust ventilation options was carried out; equipment was selected to ensure the effectiveness of temperature stabilization in the server room at the required level. ISSN 2308-5312 Наукові праці ДонНТУ. Серія: «Машинобудування і машинознавство». No1(14)’2020 20 Scientific novelty: the assessment of heat dissipation during the operation of the server cluster was carried out, the temperature regime of the operation of the server room objects was simulated and the temperature distributions were obtained for different server loads. Practical significance: the design of the room with the location of equipment for supply and exhaust ventilation is proposed; the main parameters of equipment for effective ventilation to reduce the heat load of server racks are determined, recommendations for the use of heat laboratories of high-performance computing for partial heating of the educational building of the state higher educational institution","PeriodicalId":408788,"journal":{"name":"Scientific Papers оf DonNTU: Mechanical Engineering and Machine Science","volume":"65 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1900-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Scientific Papers оf DonNTU: Mechanical Engineering and Machine Science","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.31474/2308-5312-2020-1-14-12-20","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
Purpose: to analyze the thermal load of the server cluster of the high-performance computing laboratory, stabilize the temperature regime of the room throughout the year, taking into account seasonal changes in the ambient temperature. Methodology: performing experimental studies using modern devices and analyzing experimental data to assess the heat load of server clusters at various degrees of their workload with calculations. Results: a thermal analysis of the work of the server cluster of a high-performance computing laboratory was carried out at various degrees of server load with calculations. Temperature measurements were carried out for various zones and elements of server racks, temperature changes were established when the servers were loaded with calculations. In the modern CFD system, the air flows of the server cooling system and the temperature regime of the server cluster and the server room are simulated, taking into account the location of the equipment and information about the measurements of temperatures and air flow rates. As a result, temperature distributions were obtained for different server loads. A comparison of the supply and exhaust ventilation options was carried out; equipment was selected to ensure the effectiveness of temperature stabilization in the server room at the required level. ISSN 2308-5312 Наукові праці ДонНТУ. Серія: «Машинобудування і машинознавство». No1(14)’2020 20 Scientific novelty: the assessment of heat dissipation during the operation of the server cluster was carried out, the temperature regime of the operation of the server room objects was simulated and the temperature distributions were obtained for different server loads. Practical significance: the design of the room with the location of equipment for supply and exhaust ventilation is proposed; the main parameters of equipment for effective ventilation to reduce the heat load of server racks are determined, recommendations for the use of heat laboratories of high-performance computing for partial heating of the educational building of the state higher educational institution
目的:分析某高性能计算实验室服务器集群的热负荷,在考虑环境温度季节性变化的情况下,稳定机房全年的温度状态。方法:使用现代设备进行实验研究,分析实验数据,通过计算来评估服务器集群在不同工作负载程度下的热负荷。结果:对某高性能计算实验室服务器集群在不同程度的服务器负载下的工作进行了热分析,并进行了计算。对服务器机架的各个区域和元素进行温度测量,在服务器加载计算时确定温度变化。在现代CFD系统中,考虑到设备的位置以及温度和空气流速的测量信息,模拟了服务器冷却系统的气流以及服务器集群和服务器室的温度状况。因此,获得了不同服务器负载下的温度分布。对供气和排气通风方案进行了比较;设备的选择是为了确保服务器室温度稳定在所需水平的有效性。Issn 2308-5312 Наукові праці ДонНТУ。Серія:«Машинобудування * машинознавство»。科学新颖:对服务器集群运行过程中的散热进行了评估,模拟了服务器室对象运行时的温度状态,得到了不同服务器负载下的温度分布。实际意义:提出了室内送风、排风设备的布置位置;确定了有效通风设备的主要参数,降低了服务器机架的热负荷,为国家高等学校教学建筑部分供暖采用高性能计算热实验室提出了建议