{"title":"The effect of the chilled water temperature on the performance of an experimental air-cooled chiller","authors":"P. T. Huong, Hoang Mai Hong, Lai Ngoc Anh","doi":"10.15625/0866-7136/15054","DOIUrl":null,"url":null,"abstract":"This paper presents the study results on the effect of the chilled water temperature on the coefficient of performance (COP) of an experimental air-cooled chiller. The measuring sensors and instrument were calibrated, and the uncertainty of the measuring temperature and pressure were evaluated. The uncertainty of measured temperature and pressure at 95% confidence level is 0.12 °C and 1.4 kPa, respectively. The isentropic compression efficiency and the COP of the air-cooled chiller operating at a condensation temperature of 48.05 °C and evaporation temperature of 3.17 °C are 63% and 2.69, respectively. The chilled water temperature has a significant influence on evaporation pressure and the COP of the chiller. If the temperature of the air entering the condenser of the chiller is maintained at 35 °C, the COP of the chiller increases from 2.55 to 2.89 when the temperature of the chiller water increases only 4 K, from 8 °C to 12 °C.","PeriodicalId":239329,"journal":{"name":"Vietnam Journal of Mechanics","volume":"26 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-01-21","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Vietnam Journal of Mechanics","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.15625/0866-7136/15054","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1
Abstract
This paper presents the study results on the effect of the chilled water temperature on the coefficient of performance (COP) of an experimental air-cooled chiller. The measuring sensors and instrument were calibrated, and the uncertainty of the measuring temperature and pressure were evaluated. The uncertainty of measured temperature and pressure at 95% confidence level is 0.12 °C and 1.4 kPa, respectively. The isentropic compression efficiency and the COP of the air-cooled chiller operating at a condensation temperature of 48.05 °C and evaporation temperature of 3.17 °C are 63% and 2.69, respectively. The chilled water temperature has a significant influence on evaporation pressure and the COP of the chiller. If the temperature of the air entering the condenser of the chiller is maintained at 35 °C, the COP of the chiller increases from 2.55 to 2.89 when the temperature of the chiller water increases only 4 K, from 8 °C to 12 °C.