T. Kumai, H. Nakabayashi, Y. Hirata, M. Takahashi, K. Terai, T. Kaminishi, K. Uehara
{"title":"Field trial of optical current transformer using optical fiber as Faraday sensor","authors":"T. Kumai, H. Nakabayashi, Y. Hirata, M. Takahashi, K. Terai, T. Kaminishi, K. Uehara","doi":"10.1109/PESS.2002.1043498","DOIUrl":null,"url":null,"abstract":"The optical current transformers (OCTs) using silica optical fiber as Faraday sensor were manufactured and tested in the field (275 kV substation) for 2 years to confirm their long-term reliability. Regarding the initial performance the current characteristic or the ratio error of the OCT for measurement satisfied the Japanese Electrotechnical Committee (JEC)-1201 class 1PS and that of the OCT for protection satisfied class 1T in the range from -20/spl deg/C to 55/spl deg/C. Regarding the field performance the ratio error of the OCT for measurement was stable within /spl plusmn/1% for 2 years. The current characteristic of the ratio error of the OCT for measurement satisfied class 1PS and a good result was also obtained for the OCT for protection. Also the OCTs measured accurately transient current that arose from a fault in the system. Therefor we confirm the long-term reliability of the OCT in the field through the field trial.","PeriodicalId":117177,"journal":{"name":"IEEE Power Engineering Society Summer Meeting,","volume":"35 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2002-07-25","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"13","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"IEEE Power Engineering Society Summer Meeting,","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PESS.2002.1043498","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 13
Abstract
The optical current transformers (OCTs) using silica optical fiber as Faraday sensor were manufactured and tested in the field (275 kV substation) for 2 years to confirm their long-term reliability. Regarding the initial performance the current characteristic or the ratio error of the OCT for measurement satisfied the Japanese Electrotechnical Committee (JEC)-1201 class 1PS and that of the OCT for protection satisfied class 1T in the range from -20/spl deg/C to 55/spl deg/C. Regarding the field performance the ratio error of the OCT for measurement was stable within /spl plusmn/1% for 2 years. The current characteristic of the ratio error of the OCT for measurement satisfied class 1PS and a good result was also obtained for the OCT for protection. Also the OCTs measured accurately transient current that arose from a fault in the system. Therefor we confirm the long-term reliability of the OCT in the field through the field trial.