Victor Timmers;Agustí Egea-Àlvarez;Aris Gkountaras;Lie Xu
{"title":"Control and Power Balancing of an Off-Grid Wind Turbine With Co-Located Electrolyzer","authors":"Victor Timmers;Agustí Egea-Àlvarez;Aris Gkountaras;Lie Xu","doi":"10.1109/TSTE.2024.3418043","DOIUrl":null,"url":null,"abstract":"Co-locating electrolyzers and offshore wind can significantly reduce the cost of green hydrogen. However, without a grid connection, a new control paradigm is required for the electrolyzer to follow the variable power supplied by the wind turbine. Commercial electrolyzers have power ramp rate limitations, which can result in a mismatch between the wind turbine and electrolyzer power, leading to frequent shutdown and potentially unstable operation. This paper is the first to develop a control system for this off-grid operation with three mechanisms to dynamically balance the power, including energy storage, rotor inertia, and enhanced pitch control. The results show that a $6.8 million supercapacitor is required with a power rating and capacity of approximately 6.7 MW and 8.5 kWh to enable the system to operate through 99% of the annual wind variation. If the electrolyzer ramp rates can be doubled, the same operating hours can be achieved using only control-based power balancing methods at the cost of a marginal reduction in energy production. If commercial electrolyzer ramp rates can be tripled, the system is able to operate without the need for any power balancing.","PeriodicalId":452,"journal":{"name":"IEEE Transactions on Sustainable Energy","volume":"15 4","pages":"2349-2360"},"PeriodicalIF":8.6000,"publicationDate":"2024-06-24","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"IEEE Transactions on Sustainable Energy","FirstCategoryId":"5","ListUrlMain":"https://ieeexplore.ieee.org/document/10569094/","RegionNum":1,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"ENERGY & FUELS","Score":null,"Total":0}
引用次数: 0
Abstract
Co-locating electrolyzers and offshore wind can significantly reduce the cost of green hydrogen. However, without a grid connection, a new control paradigm is required for the electrolyzer to follow the variable power supplied by the wind turbine. Commercial electrolyzers have power ramp rate limitations, which can result in a mismatch between the wind turbine and electrolyzer power, leading to frequent shutdown and potentially unstable operation. This paper is the first to develop a control system for this off-grid operation with three mechanisms to dynamically balance the power, including energy storage, rotor inertia, and enhanced pitch control. The results show that a $6.8 million supercapacitor is required with a power rating and capacity of approximately 6.7 MW and 8.5 kWh to enable the system to operate through 99% of the annual wind variation. If the electrolyzer ramp rates can be doubled, the same operating hours can be achieved using only control-based power balancing methods at the cost of a marginal reduction in energy production. If commercial electrolyzer ramp rates can be tripled, the system is able to operate without the need for any power balancing.
期刊介绍:
The IEEE Transactions on Sustainable Energy serves as a pivotal platform for sharing groundbreaking research findings on sustainable energy systems, with a focus on their seamless integration into power transmission and/or distribution grids. The journal showcases original research spanning the design, implementation, grid-integration, and control of sustainable energy technologies and systems. Additionally, the Transactions warmly welcomes manuscripts addressing the design, implementation, and evaluation of power systems influenced by sustainable energy systems and devices.