Possible interconnections for the Katsina wind farm using synchronous compensators (STATCOM)

Jonathan O. Okoronkwo, O. Ojo
{"title":"Possible interconnections for the Katsina wind farm using synchronous compensators (STATCOM)","authors":"Jonathan O. Okoronkwo, O. Ojo","doi":"10.1109/POWERAFRICA.2017.7991218","DOIUrl":null,"url":null,"abstract":"Squirrel-cage induction generator wind power plant requires the provision of reactive power for self-excitation and to sustain the generated voltage. The Katsina wind power plant comprising of several squirrel cage generators, each has a fixed capacitor bank connected in shunt to the wind turbine generator provide the needed reactive power. These capacitors are selected to enable the excitation of the generators under various wind speeds which are greater than the cut in speed. All of these generators, through underground cables are connected to the main substation. This solution has limitations of under or over-exciting the generators depending on the wind speeds and the local load demand. Furthermore, because of the voltage drops in the underground cables and potential faults in the lines connecting the substation to the wider power systems, the voltages at the turbine terminals and the substation can vary leading to potential under-voltage and over voltage problems. Especially in weak power systems — such as the Nigeria power systems — Static Var Compensators (SVC) and Static Synchronous Compensators (STATCOM) which provide variable reactive power (both leading and lagging) as when needed to maintain the substation voltage at the rated and desired values.","PeriodicalId":6601,"journal":{"name":"2017 IEEE PES PowerAfrica","volume":"24 1","pages":"169-173"},"PeriodicalIF":0.0000,"publicationDate":"2017-06-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2017 IEEE PES PowerAfrica","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/POWERAFRICA.2017.7991218","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Squirrel-cage induction generator wind power plant requires the provision of reactive power for self-excitation and to sustain the generated voltage. The Katsina wind power plant comprising of several squirrel cage generators, each has a fixed capacitor bank connected in shunt to the wind turbine generator provide the needed reactive power. These capacitors are selected to enable the excitation of the generators under various wind speeds which are greater than the cut in speed. All of these generators, through underground cables are connected to the main substation. This solution has limitations of under or over-exciting the generators depending on the wind speeds and the local load demand. Furthermore, because of the voltage drops in the underground cables and potential faults in the lines connecting the substation to the wider power systems, the voltages at the turbine terminals and the substation can vary leading to potential under-voltage and over voltage problems. Especially in weak power systems — such as the Nigeria power systems — Static Var Compensators (SVC) and Static Synchronous Compensators (STATCOM) which provide variable reactive power (both leading and lagging) as when needed to maintain the substation voltage at the rated and desired values.
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
使用同步补偿器的卡齐纳风电场可能的互连(STATCOM)
鼠笼式感应发电机风力发电厂需要提供自激无功功率并维持产生的电压。卡齐纳风力发电厂由几个鼠笼式发电机组成,每个发电机都有一个固定的电容器组,并联到风力发电机上,提供所需的无功功率。选择这些电容器是为了在大于切割速度的各种风速下对发电机进行激励。所有这些发电机,通过地下电缆连接到主变电站。根据风速和当地负荷需求,这种解决方案有不足或过度激励发电机的限制。此外,由于地下电缆的电压下降和连接变电站到更广泛的电力系统的线路中的潜在故障,涡轮机终端和变电站的电压可能会发生变化,导致潜在的欠压和过压问题。特别是在弱电系统中,如尼日利亚电力系统,静态无功补偿器(SVC)和静态同步补偿器(STATCOM)在需要时提供可变无功功率(领先和滞后),以保持变电站电压在额定和期望值。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Optimized network planning of mini-grids for the rural electrification of developing countries Application of statistical tools in power transformer FRA results interpretation: Transformer winding diagnosis based on frequency response analysis An algorithm for micro-load shedding in generation constrained electricity distribution network Asynchronous interconnection of the proposed East Africa Power Pool (EAPP) Impact of large scale grid-connected wind generators on the power system network
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1