并联无源电力滤波器和失谐电抗器对混合电厂电能质量的改善

L. Gumilar, A. Kusumawardana, W. Nugroho, Mokhammad Sholeh
{"title":"并联无源电力滤波器和失谐电抗器对混合电厂电能质量的改善","authors":"L. Gumilar, A. Kusumawardana, W. Nugroho, Mokhammad Sholeh","doi":"10.1109/ICoSTA48221.2020.1570599090","DOIUrl":null,"url":null,"abstract":"Renewable energy can cause problems in the quality of electric power, such as harmonics. The reason is that solar power plants and wind power plants use power electronic instruments such as inverters, rectifiers, buck, boosts, and so on. These devices are used to charge batteries and are also used for load supplies. Electronic power devices can cause hormones in the electric power system if connected to the grid. For this reason, power quality assessment is needed on the power system, whether THD (Total Harmonic Distortion) more than the tolerance limit of 5 percent. If THD more than 5 percent, mitigation is needed to reduce THD. This research was carried out in the laboratory Department of Electrical Engineering. The results of the THD-V measurement at this location are 19,19%. The method uses a shunt passive filter and detuned reactor to reduce THD. This research will be made into 2 scenarios. The first scenario uses only a shunt passive filter and the second scenario uses a hybrid shunt passive filter with the detuned reactor. The purpose of being made into 2 scenarios is to prove that the detuned reactor can optimize the shunt passive filter. The results of these scenarios are the first scenario, harmonic mitigation using only the passive shunt filter can reduce THD-V to 3,39 percent. The second scenario is that harmonic mitigation using a combination of passive shunt filter and the detuned reactor can reduce the THD-V to 3,07 percent. It can be concluded that the role of the detuned reactor can improve the performance of shunt passive filters. Detuned reactor functions to limit the current entering the filter and can reduce the harmonic effects arising from the harmonic filter itself.","PeriodicalId":375166,"journal":{"name":"2020 International Conference on Smart Technology and Applications (ICoSTA)","volume":"7 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2020-02-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"4","resultStr":"{\"title\":\"Power Quality Enhancement on Hybrid Power Plants Using Shunt Passive Power Filter and Detuned Reactor\",\"authors\":\"L. Gumilar, A. Kusumawardana, W. Nugroho, Mokhammad Sholeh\",\"doi\":\"10.1109/ICoSTA48221.2020.1570599090\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Renewable energy can cause problems in the quality of electric power, such as harmonics. The reason is that solar power plants and wind power plants use power electronic instruments such as inverters, rectifiers, buck, boosts, and so on. These devices are used to charge batteries and are also used for load supplies. Electronic power devices can cause hormones in the electric power system if connected to the grid. For this reason, power quality assessment is needed on the power system, whether THD (Total Harmonic Distortion) more than the tolerance limit of 5 percent. If THD more than 5 percent, mitigation is needed to reduce THD. This research was carried out in the laboratory Department of Electrical Engineering. The results of the THD-V measurement at this location are 19,19%. The method uses a shunt passive filter and detuned reactor to reduce THD. This research will be made into 2 scenarios. The first scenario uses only a shunt passive filter and the second scenario uses a hybrid shunt passive filter with the detuned reactor. The purpose of being made into 2 scenarios is to prove that the detuned reactor can optimize the shunt passive filter. The results of these scenarios are the first scenario, harmonic mitigation using only the passive shunt filter can reduce THD-V to 3,39 percent. The second scenario is that harmonic mitigation using a combination of passive shunt filter and the detuned reactor can reduce the THD-V to 3,07 percent. It can be concluded that the role of the detuned reactor can improve the performance of shunt passive filters. Detuned reactor functions to limit the current entering the filter and can reduce the harmonic effects arising from the harmonic filter itself.\",\"PeriodicalId\":375166,\"journal\":{\"name\":\"2020 International Conference on Smart Technology and Applications (ICoSTA)\",\"volume\":\"7 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2020-02-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"4\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2020 International Conference on Smart Technology and Applications (ICoSTA)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICoSTA48221.2020.1570599090\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2020 International Conference on Smart Technology and Applications (ICoSTA)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICoSTA48221.2020.1570599090","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 4

摘要

可再生能源会引起电力质量问题,比如谐波。原因是太阳能发电厂和风力发电厂使用的是逆变器、整流器、降压、升压等电力电子仪表。这些设备用于给电池充电,也用于负载供应。电子电力设备如果接入电网,会在电力系统中产生激素。为此,需要对电力系统进行电能质量评估,看THD(总谐波失真)是否超过5%的容差限值。如果THD超过5%,则需要缓解以减少THD。这项研究是在电气工程系的实验室进行的。该位置的THD-V测量结果为19.19%。该方法使用并联无源滤波器和失谐电抗器来降低THD。本研究将分为2个场景。第一种方案仅使用并联无源滤波器,第二种方案使用混合并联无源滤波器和失谐电抗器。分为两种情况的目的是为了证明失谐电抗器可以优化并联无源滤波器。这些方案的结果是第一种方案,仅使用无源分流滤波器的谐波缓解可以将THD-V降低到3.39%。第二种情况是,使用无源分流滤波器和失谐电抗器组合的谐波缓解可以将THD-V降低到3.07%。由此可见,失谐电抗器的作用可以改善并联无源滤波器的性能。失谐电抗器的作用是限制进入滤波器的电流,并可以减少谐波滤波器本身产生的谐波效应。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Power Quality Enhancement on Hybrid Power Plants Using Shunt Passive Power Filter and Detuned Reactor
Renewable energy can cause problems in the quality of electric power, such as harmonics. The reason is that solar power plants and wind power plants use power electronic instruments such as inverters, rectifiers, buck, boosts, and so on. These devices are used to charge batteries and are also used for load supplies. Electronic power devices can cause hormones in the electric power system if connected to the grid. For this reason, power quality assessment is needed on the power system, whether THD (Total Harmonic Distortion) more than the tolerance limit of 5 percent. If THD more than 5 percent, mitigation is needed to reduce THD. This research was carried out in the laboratory Department of Electrical Engineering. The results of the THD-V measurement at this location are 19,19%. The method uses a shunt passive filter and detuned reactor to reduce THD. This research will be made into 2 scenarios. The first scenario uses only a shunt passive filter and the second scenario uses a hybrid shunt passive filter with the detuned reactor. The purpose of being made into 2 scenarios is to prove that the detuned reactor can optimize the shunt passive filter. The results of these scenarios are the first scenario, harmonic mitigation using only the passive shunt filter can reduce THD-V to 3,39 percent. The second scenario is that harmonic mitigation using a combination of passive shunt filter and the detuned reactor can reduce the THD-V to 3,07 percent. It can be concluded that the role of the detuned reactor can improve the performance of shunt passive filters. Detuned reactor functions to limit the current entering the filter and can reduce the harmonic effects arising from the harmonic filter itself.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Decentralized Tourism Destinations Rating System Using 6AsTD Framework and Blockchain ICoSTA 2020 Table of Contents IoT Based: Improving Control System For High-Quality Beef in Supermarkets Analysis of Power Transactions on the Integrated Solar Home System A Fuzzy Servqual Method for Evaluated Umrah Service Quality
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1