工业制冰厂热力不可逆性分析

R. Mishra, S. S. Kachhwaha
{"title":"工业制冰厂热力不可逆性分析","authors":"R. Mishra, S. S. Kachhwaha","doi":"10.51976/ijari.241413","DOIUrl":null,"url":null,"abstract":"The behavior of single-stage vapour compression-refrigeration cycle, using NH3, has been investigated by the exergy method. The condenser and the evaporator’s saturation temperatures were varied from 295 K to 305 K and from 249 K to 239 K respectively. The effects of temperature changes in the condenser and evaporator on the plant’s irreversibility rate were determined. The greater the temperature difference between either (i) the condenser and the environment, or (ii) the evaporator and the cold room, the higher the irreversibility rate. Reduction in the irreversibility rate of the condenser gives approximately 2.58 times greater reduction in the irreversibility rate for the whole plant, whereas reduction in the evaporator’s irreversibility rate gives a 2.32 times greater mean reduction in the irreversibility rate of the whole plant. Because the changes in the temperatures in the condenser and the evaporator contribute significantly to the plant’s overall irreversibility, there is considerable scope for optimizing the condition imposed upon the condenser and evaporator.","PeriodicalId":330303,"journal":{"name":"International Journal of Advance Research and Innovation","volume":"12 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1900-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Thermodynamic Irreversibilities Analysis of Industrial Ice Plant\",\"authors\":\"R. Mishra, S. S. Kachhwaha\",\"doi\":\"10.51976/ijari.241413\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The behavior of single-stage vapour compression-refrigeration cycle, using NH3, has been investigated by the exergy method. The condenser and the evaporator’s saturation temperatures were varied from 295 K to 305 K and from 249 K to 239 K respectively. The effects of temperature changes in the condenser and evaporator on the plant’s irreversibility rate were determined. The greater the temperature difference between either (i) the condenser and the environment, or (ii) the evaporator and the cold room, the higher the irreversibility rate. Reduction in the irreversibility rate of the condenser gives approximately 2.58 times greater reduction in the irreversibility rate for the whole plant, whereas reduction in the evaporator’s irreversibility rate gives a 2.32 times greater mean reduction in the irreversibility rate of the whole plant. Because the changes in the temperatures in the condenser and the evaporator contribute significantly to the plant’s overall irreversibility, there is considerable scope for optimizing the condition imposed upon the condenser and evaporator.\",\"PeriodicalId\":330303,\"journal\":{\"name\":\"International Journal of Advance Research and Innovation\",\"volume\":\"12 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"1900-01-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"International Journal of Advance Research and Innovation\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.51976/ijari.241413\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"International Journal of Advance Research and Innovation","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.51976/ijari.241413","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

用火用法研究了以NH3为原料的单级蒸汽压缩-制冷循环的行为。冷凝器和蒸发器的饱和温度分别在295 ~ 305 K和249 ~ 239 K之间变化。确定了冷凝器和蒸发器温度变化对装置不可逆性的影响。(1)冷凝器与环境之间的温差或(2)蒸发器与冷室之间的温差越大,不可逆性速率就越高。冷凝器不可逆性速率的降低使整个装置的不可逆性速率降低约2.58倍,而蒸发器不可逆性速率的降低使整个装置的不可逆性速率平均降低2.32倍。由于冷凝器和蒸发器温度的变化对电厂的整体不可逆性有很大的影响,因此对冷凝器和蒸发器施加的条件进行优化有相当大的余地。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Thermodynamic Irreversibilities Analysis of Industrial Ice Plant
The behavior of single-stage vapour compression-refrigeration cycle, using NH3, has been investigated by the exergy method. The condenser and the evaporator’s saturation temperatures were varied from 295 K to 305 K and from 249 K to 239 K respectively. The effects of temperature changes in the condenser and evaporator on the plant’s irreversibility rate were determined. The greater the temperature difference between either (i) the condenser and the environment, or (ii) the evaporator and the cold room, the higher the irreversibility rate. Reduction in the irreversibility rate of the condenser gives approximately 2.58 times greater reduction in the irreversibility rate for the whole plant, whereas reduction in the evaporator’s irreversibility rate gives a 2.32 times greater mean reduction in the irreversibility rate of the whole plant. Because the changes in the temperatures in the condenser and the evaporator contribute significantly to the plant’s overall irreversibility, there is considerable scope for optimizing the condition imposed upon the condenser and evaporator.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Strategic Management Practice for Small and Medium-sized Enterprises in Tamil Nadu: Empirical Evidence Roles of Top Management and Customer Orientation in Enhancing The Performance of Customer Relationship Management (CRM) in Hotel Industry Acoustic Properties of Light Concrete of Natural Pozzolans of Ambohinaorina Design, Modification and Analysis of Industrial Air Compressor (Type: Vt4): A Review Use of Renewable Energy in Dairy Industry
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1