{"title":"一种新的次同步扭转相互作用及其抑制对策","authors":"Xiangning Xiao, Jian Zhang, Chunlin Guo, Lin Yang","doi":"10.1109/ENERGYTECH.2013.6645284","DOIUrl":null,"url":null,"abstract":"In Inner Mongolia of China, the generators in several power plants are experiencing a new subsynchronous interaction problem. It belongs to subsynchronous torsional interaction (SSTI) between the generators and HVDC, but has many different characteristics from conventional SSTI. This paper describes the different characteristics according to the actual recording. Preliminary analysis is made for the root cause as well as the probable disturbance source. PSCAD/EMTDC is used to build up equivalent model of the power system and complex torque coefficient approach is utilized to scan the electrical damping characteristics of the system. A stimulation method is presented to simulate the similar disturbance as actual condition. The feasibilities of several mitigation countermeasures are analysed in detail and finally the countermeasure that STATCOM at the generator terminal is recommended.","PeriodicalId":154402,"journal":{"name":"2013 IEEE Energytech","volume":"59 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2013-05-21","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"7","resultStr":"{\"title\":\"A new subsynchronous torsional interaction and its mitigation countermeasures\",\"authors\":\"Xiangning Xiao, Jian Zhang, Chunlin Guo, Lin Yang\",\"doi\":\"10.1109/ENERGYTECH.2013.6645284\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"In Inner Mongolia of China, the generators in several power plants are experiencing a new subsynchronous interaction problem. It belongs to subsynchronous torsional interaction (SSTI) between the generators and HVDC, but has many different characteristics from conventional SSTI. This paper describes the different characteristics according to the actual recording. Preliminary analysis is made for the root cause as well as the probable disturbance source. PSCAD/EMTDC is used to build up equivalent model of the power system and complex torque coefficient approach is utilized to scan the electrical damping characteristics of the system. A stimulation method is presented to simulate the similar disturbance as actual condition. The feasibilities of several mitigation countermeasures are analysed in detail and finally the countermeasure that STATCOM at the generator terminal is recommended.\",\"PeriodicalId\":154402,\"journal\":{\"name\":\"2013 IEEE Energytech\",\"volume\":\"59 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2013-05-21\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"7\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2013 IEEE Energytech\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ENERGYTECH.2013.6645284\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2013 IEEE Energytech","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ENERGYTECH.2013.6645284","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
A new subsynchronous torsional interaction and its mitigation countermeasures
In Inner Mongolia of China, the generators in several power plants are experiencing a new subsynchronous interaction problem. It belongs to subsynchronous torsional interaction (SSTI) between the generators and HVDC, but has many different characteristics from conventional SSTI. This paper describes the different characteristics according to the actual recording. Preliminary analysis is made for the root cause as well as the probable disturbance source. PSCAD/EMTDC is used to build up equivalent model of the power system and complex torque coefficient approach is utilized to scan the electrical damping characteristics of the system. A stimulation method is presented to simulate the similar disturbance as actual condition. The feasibilities of several mitigation countermeasures are analysed in detail and finally the countermeasure that STATCOM at the generator terminal is recommended.