非有效接地系统中基于零序导纳测量的故障定位方法

Zhang Linli, Gao Houlei, X. Bingyin, Xue Yongduan
{"title":"非有效接地系统中基于零序导纳测量的故障定位方法","authors":"Zhang Linli, Gao Houlei, X. Bingyin, Xue Yongduan","doi":"10.1109/ISGT-ASIA.2012.6303095","DOIUrl":null,"url":null,"abstract":"A new fault location method based on zero sequence admittance measurement is presented in order to solve the fault location problem of single phase-to-earth fault in non-solidly earthed distribution network. The zero sequence admittance is calculated using measured zero sequence current and zero sequence voltage at sectionalized switch. The fault direction is determined by master station according to the angle of measured admittance, and then the faulty section is located by analyzing the fault direction results of different sectionalized switches. This method can be implemented in distribution automation (DA) system using the feeder terminal unit (FTU) as field measurement equipment, without requiring of additional equipment. The feasibility and accuracy of this proposed method is proved by the ATP simulation results.","PeriodicalId":330758,"journal":{"name":"IEEE PES Innovative Smart Grid Technologies","volume":"149 3 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2012-05-21","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"10","resultStr":"{\"title\":\"Fault location method based on zero sequence admittance measurement in non-effectively earthed system\",\"authors\":\"Zhang Linli, Gao Houlei, X. Bingyin, Xue Yongduan\",\"doi\":\"10.1109/ISGT-ASIA.2012.6303095\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"A new fault location method based on zero sequence admittance measurement is presented in order to solve the fault location problem of single phase-to-earth fault in non-solidly earthed distribution network. The zero sequence admittance is calculated using measured zero sequence current and zero sequence voltage at sectionalized switch. The fault direction is determined by master station according to the angle of measured admittance, and then the faulty section is located by analyzing the fault direction results of different sectionalized switches. This method can be implemented in distribution automation (DA) system using the feeder terminal unit (FTU) as field measurement equipment, without requiring of additional equipment. The feasibility and accuracy of this proposed method is proved by the ATP simulation results.\",\"PeriodicalId\":330758,\"journal\":{\"name\":\"IEEE PES Innovative Smart Grid Technologies\",\"volume\":\"149 3 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2012-05-21\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"10\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"IEEE PES Innovative Smart Grid Technologies\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ISGT-ASIA.2012.6303095\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"IEEE PES Innovative Smart Grid Technologies","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ISGT-ASIA.2012.6303095","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 10

摘要

针对非接地配电网单相接地故障的定位问题,提出了一种基于零序导纳测量的故障定位新方法。零序导纳是利用实测的零序电流和分节开关处的零序电压来计算的。主站根据测得导纳的角度确定故障方向,然后通过分析不同分段开关的故障方向结果定位故障路段。该方法可以在配电自动化(DA)系统中使用馈线终端(FTU)作为现场测量设备,而不需要额外的设备。ATP仿真结果验证了该方法的可行性和准确性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Fault location method based on zero sequence admittance measurement in non-effectively earthed system
A new fault location method based on zero sequence admittance measurement is presented in order to solve the fault location problem of single phase-to-earth fault in non-solidly earthed distribution network. The zero sequence admittance is calculated using measured zero sequence current and zero sequence voltage at sectionalized switch. The fault direction is determined by master station according to the angle of measured admittance, and then the faulty section is located by analyzing the fault direction results of different sectionalized switches. This method can be implemented in distribution automation (DA) system using the feeder terminal unit (FTU) as field measurement equipment, without requiring of additional equipment. The feasibility and accuracy of this proposed method is proved by the ATP simulation results.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Wind-photovoltaic-storage system optimal control scheme based on generation scheduling Smart grid oriented smart substation characteristics analysis Studies on practical Small Signal Stability Region of electrical power systems A survey of communication technology in distribution network An interior point method based on continuous Newton's method for optimal power flow
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1