爪哇-巴厘电网150kV输电线路故障电流残留保护系统失效

A. A. Kusuma, P. Pramana, B. S. Munir
{"title":"爪哇-巴厘电网150kV输电线路故障电流残留保护系统失效","authors":"A. A. Kusuma, P. Pramana, B. S. Munir","doi":"10.1109/APCoRISE46197.2019.9318875","DOIUrl":null,"url":null,"abstract":"Reliability of measurement apparatus is an important thing in order to secure the continuous supply of power in the system. Measurement error potentially affects the protection system performance. In the study, an example of protection system failure due to measurement error on current transformer (CT) on one of the 150kV transmission line in Java-Bali grid will be discussed. The failure occurs due to residual fault current that remain flow at the faulted phase even though fault clearing has been done by the primary protection of the transmission line. Therefore, the study will determine the cause of fault residual current measured by CT after fault clearing by performing simulation in application of transient analysis. In this study, the data during single phase to ground fault on the transmission line are presented. Along with the explanation of literature study related to measurement error on CT. After that, simulations using variation of CT measurement condition are performed.","PeriodicalId":250648,"journal":{"name":"2019 Asia Pacific Conference on Research in Industrial and Systems Engineering (APCoRISE)","volume":"3 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2019-04-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Protection System Failure on 150kV Transmission Line in Java-Bali Grid due to Fault Current Residual\",\"authors\":\"A. A. Kusuma, P. Pramana, B. S. Munir\",\"doi\":\"10.1109/APCoRISE46197.2019.9318875\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Reliability of measurement apparatus is an important thing in order to secure the continuous supply of power in the system. Measurement error potentially affects the protection system performance. In the study, an example of protection system failure due to measurement error on current transformer (CT) on one of the 150kV transmission line in Java-Bali grid will be discussed. The failure occurs due to residual fault current that remain flow at the faulted phase even though fault clearing has been done by the primary protection of the transmission line. Therefore, the study will determine the cause of fault residual current measured by CT after fault clearing by performing simulation in application of transient analysis. In this study, the data during single phase to ground fault on the transmission line are presented. Along with the explanation of literature study related to measurement error on CT. After that, simulations using variation of CT measurement condition are performed.\",\"PeriodicalId\":250648,\"journal\":{\"name\":\"2019 Asia Pacific Conference on Research in Industrial and Systems Engineering (APCoRISE)\",\"volume\":\"3 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2019-04-18\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2019 Asia Pacific Conference on Research in Industrial and Systems Engineering (APCoRISE)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/APCoRISE46197.2019.9318875\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2019 Asia Pacific Conference on Research in Industrial and Systems Engineering (APCoRISE)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/APCoRISE46197.2019.9318875","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

为了保证电力系统的持续供电,测量仪器的可靠性是非常重要的。测量误差可能会影响保护系统的性能。本文以爪哇-巴厘电网某150kV输电线路电流互感器测量误差导致保护系统失效为例进行了分析。故障发生的原因是,即使输电线路的主保护已完成故障清除,故障电流仍在故障相中流动。因此,本研究将在暂态分析的应用中进行仿真,确定故障清除后CT测量的故障剩余电流产生的原因。本文给出了输电线路单相接地故障时的数据。随着文献研究对CT测量误差的解释。然后,利用CT测量条件的变化进行了仿真。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Protection System Failure on 150kV Transmission Line in Java-Bali Grid due to Fault Current Residual
Reliability of measurement apparatus is an important thing in order to secure the continuous supply of power in the system. Measurement error potentially affects the protection system performance. In the study, an example of protection system failure due to measurement error on current transformer (CT) on one of the 150kV transmission line in Java-Bali grid will be discussed. The failure occurs due to residual fault current that remain flow at the faulted phase even though fault clearing has been done by the primary protection of the transmission line. Therefore, the study will determine the cause of fault residual current measured by CT after fault clearing by performing simulation in application of transient analysis. In this study, the data during single phase to ground fault on the transmission line are presented. Along with the explanation of literature study related to measurement error on CT. After that, simulations using variation of CT measurement condition are performed.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
An Image Processing and Artificial Intelligence based Traffic Signal Control System of Dhaka Model Conceptualization for Optimal Strategies in Transboundary Movement of Waste Electrical and Electronic Equipment: A Game Theory Approach The Design of Model and Inventory Routing Problem (IRP) Algorithm for Swapped Battery at Battery Exchange Station (BES): Case Study of Electric Motor Classifying Twitter Spammer based on User's Behavior using Decision Tree An Improved Pupil Detection Method under Eyeglass Occlusions
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1