{"title":"接地故障电流谐波对漏电装置脱扣的影响","authors":"S. Czapp","doi":"10.1109/ISNCC.2008.4627489","DOIUrl":null,"url":null,"abstract":"The most popular means of protection against indirect contact in low voltage systems is automatic disconnection of supply, since it is a simple and economically attractive way to achieve safety in an electrical installation. As a protective device, residual current devices (RCDs) are commonly used. In certain conditions using the RCDs is obligatory. The widespread application of static converters, especially frequency converters, results in installing RCDs in circuits where nonsinusoidal earth fault current flows. The earth fault current in the output circuit of frequency converters comprises harmonics and interharmonics, whose order mainly depends on the PWM frequency. The level of higher frequency components in the earth fault current may exceed the fundamental one. The nonsinusoidal earth fault current influences tripping of the residual current devices. In the paper, results of the theoretical analysis and the laboratory tests of residual current devices operation are presented and discussed. They prove that in some cases higher frequency components cause improper tripping of the residual current devices and a real hazard of electrocution exists.","PeriodicalId":143815,"journal":{"name":"2008 International School on Nonsinusoidal Currents and Compensation","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"2008-06-10","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"35","resultStr":"{\"title\":\"The effect of earth fault current harmonics on tripping of residual current devices\",\"authors\":\"S. Czapp\",\"doi\":\"10.1109/ISNCC.2008.4627489\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The most popular means of protection against indirect contact in low voltage systems is automatic disconnection of supply, since it is a simple and economically attractive way to achieve safety in an electrical installation. As a protective device, residual current devices (RCDs) are commonly used. In certain conditions using the RCDs is obligatory. The widespread application of static converters, especially frequency converters, results in installing RCDs in circuits where nonsinusoidal earth fault current flows. The earth fault current in the output circuit of frequency converters comprises harmonics and interharmonics, whose order mainly depends on the PWM frequency. The level of higher frequency components in the earth fault current may exceed the fundamental one. The nonsinusoidal earth fault current influences tripping of the residual current devices. In the paper, results of the theoretical analysis and the laboratory tests of residual current devices operation are presented and discussed. They prove that in some cases higher frequency components cause improper tripping of the residual current devices and a real hazard of electrocution exists.\",\"PeriodicalId\":143815,\"journal\":{\"name\":\"2008 International School on Nonsinusoidal Currents and Compensation\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2008-06-10\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"35\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2008 International School on Nonsinusoidal Currents and Compensation\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ISNCC.2008.4627489\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2008 International School on Nonsinusoidal Currents and Compensation","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ISNCC.2008.4627489","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 35

摘要

在低压系统中,防止间接接触最常用的保护手段是自动断开电源,因为它是一种简单且经济的方式,可以实现电气装置的安全。漏电保护装置是常用的一种保护装置。在某些情况下,必须使用rcd。静态变流器,特别是变频器的广泛应用,导致在非正弦接地故障电流流过的电路中安装rcd。变频器输出电路中的接地故障电流包括谐波和间谐波,其顺序主要取决于PWM频率。接地故障电流中高频分量的电平可能超过基频分量。非正弦接地故障电流影响剩余电流装置的脱扣。本文对残流器件运行的理论分析和实验室试验结果进行了介绍和讨论。他们证明,在某些情况下,较高的频率分量会导致漏电装置的不正确跳闸,并存在触电的真正危险。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
The effect of earth fault current harmonics on tripping of residual current devices
The most popular means of protection against indirect contact in low voltage systems is automatic disconnection of supply, since it is a simple and economically attractive way to achieve safety in an electrical installation. As a protective device, residual current devices (RCDs) are commonly used. In certain conditions using the RCDs is obligatory. The widespread application of static converters, especially frequency converters, results in installing RCDs in circuits where nonsinusoidal earth fault current flows. The earth fault current in the output circuit of frequency converters comprises harmonics and interharmonics, whose order mainly depends on the PWM frequency. The level of higher frequency components in the earth fault current may exceed the fundamental one. The nonsinusoidal earth fault current influences tripping of the residual current devices. In the paper, results of the theoretical analysis and the laboratory tests of residual current devices operation are presented and discussed. They prove that in some cases higher frequency components cause improper tripping of the residual current devices and a real hazard of electrocution exists.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Instantaneous single-phase system power demonstration using virtual two phase theory Power quality conditioners with minimum number of current sensor requirement Power electronics active filter with controlled dynamics Conditions of CM voltage cancellation in multilevel voltage inverters with conventional and improved carrier-based SVPWM Natural doubling of the apparent switching frequency using three-level ANPC converter
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1