{"title":"1000kv气体绝缘变电站快速瞬态过电压的计算","authors":"M. Haseeb, M. J. Thomas","doi":"10.1109/APPEEC.2017.8308964","DOIUrl":null,"url":null,"abstract":"Very fast transient overvoltages (VFTO) generated in a gas insulated substation (GIS) during disconnector switching operations is one of the major concerns in insulation design of the GIS. Such over voltages can cause malfunctioning of the protection and control circuits in addition to initiating faults inside the gas insulated bus ducts of the substation especially in the presence of metallic particles. In this paper, VFTO have been estimated at various points in a 1000 kV rated substation for all possible valid disconnector switching operations. For the substation studied, the maximum computed overvoltage is 1.58 pu without considering the trapped charge on the busbar. Major frequency components in the simulated VFTO lies in the range of 840 KHz to 30 MHz. Simulations have been carried out using the Electromagnetic Transient Program (EMTP).","PeriodicalId":247669,"journal":{"name":"2017 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC)","volume":"30 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2017-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":"{\"title\":\"Computation of very fast transient overvoltages (VFTO) in a 1000 kV gas insulated substation\",\"authors\":\"M. Haseeb, M. J. Thomas\",\"doi\":\"10.1109/APPEEC.2017.8308964\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Very fast transient overvoltages (VFTO) generated in a gas insulated substation (GIS) during disconnector switching operations is one of the major concerns in insulation design of the GIS. Such over voltages can cause malfunctioning of the protection and control circuits in addition to initiating faults inside the gas insulated bus ducts of the substation especially in the presence of metallic particles. In this paper, VFTO have been estimated at various points in a 1000 kV rated substation for all possible valid disconnector switching operations. For the substation studied, the maximum computed overvoltage is 1.58 pu without considering the trapped charge on the busbar. Major frequency components in the simulated VFTO lies in the range of 840 KHz to 30 MHz. Simulations have been carried out using the Electromagnetic Transient Program (EMTP).\",\"PeriodicalId\":247669,\"journal\":{\"name\":\"2017 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC)\",\"volume\":\"30 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2017-11-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"2\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2017 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/APPEEC.2017.8308964\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2017 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/APPEEC.2017.8308964","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2

摘要

气体绝缘变电站(GIS)在隔离开关操作过程中产生的快速瞬态过电压(VFTO)是GIS绝缘设计中的主要问题之一。这种过电压除了引起变电站气体绝缘母线管道内的故障外,还会引起保护和控制电路的故障,特别是在存在金属颗粒的情况下。在本文中,在1000千伏额定变电站的各个点上,对所有可能的有效隔离开关操作进行了VFTO估计。对于所研究的变电站,在不考虑母线上捕获电荷的情况下,计算出的最大过电压为1.58 pu。在模拟的VFTO中,主要的频率分量位于840 KHz到30 MHz的范围内。利用电磁瞬变程序(EMTP)进行了仿真。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Computation of very fast transient overvoltages (VFTO) in a 1000 kV gas insulated substation
Very fast transient overvoltages (VFTO) generated in a gas insulated substation (GIS) during disconnector switching operations is one of the major concerns in insulation design of the GIS. Such over voltages can cause malfunctioning of the protection and control circuits in addition to initiating faults inside the gas insulated bus ducts of the substation especially in the presence of metallic particles. In this paper, VFTO have been estimated at various points in a 1000 kV rated substation for all possible valid disconnector switching operations. For the substation studied, the maximum computed overvoltage is 1.58 pu without considering the trapped charge on the busbar. Major frequency components in the simulated VFTO lies in the range of 840 KHz to 30 MHz. Simulations have been carried out using the Electromagnetic Transient Program (EMTP).
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
A novel modulation strategy for active rectification of a snubber less soft-switched single stage 30 high frequency link DC-AC converter Implementation of social spider optimization for optimized hydel-thermic operational delineation Frequency Response Analysis (FRA) in power transformers: An approach to locate inter-disk SC fault Fault estimation with analytical cable model for MMC-HVDC in offshore applications Modified current control technique for grid synchronization in voltage source converters
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1