{"title":"间接对称移相变压器保护的相角偏移和基于斜率的约束","authors":"S. Bhasker, Manoj Tripathy","doi":"10.31272/jeasd.28.3.2","DOIUrl":null,"url":null,"abstract":"This study presents a method to limit the functioning of the differential relay during the different operating conditions of an Indirect Symmetrical Phase Shift Transformer (ISPST). The proposed method depends on two thresholds; phase angle shift (PAS) between two ends of an ISPST to discriminate internal faults and inrush conditions from normal, over-excitation, and external fault conditions and slope of differential current helps to discriminate the situation of internal fault from inrush. In the first step of the algorithm, the PAS-based threshold discriminates normal, over-excitation, and external fault conditions from magnetizing inrush and internal fault conditions. In the second step, the slope-based threshold discriminates magnetizing inrush from internal fault conditions. The reliability of the proposed method has also been examined under the condition of current transformer saturation due to heavy external faults. Additionally, the comparison of the suggested and conventional methods is discussed to check the superiority of the proposed method. The proposed method eliminates the need for phase angle shift correction in the suggested method. A variety of faults in the series and excitation unit are simulated using the PSCAD/EMTDC platform to verify the approach method.","PeriodicalId":33282,"journal":{"name":"Journal of Engineering and Sustainable Development","volume":"32 22","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2024-05-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"PHASE ANGLE SHIFT AND SLOPE BASED RESTRAINT FOR INDIRECT SYMMETRICAL PHASE SHIFT TRANSFORMER PROTECTION\",\"authors\":\"S. Bhasker, Manoj Tripathy\",\"doi\":\"10.31272/jeasd.28.3.2\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"This study presents a method to limit the functioning of the differential relay during the different operating conditions of an Indirect Symmetrical Phase Shift Transformer (ISPST). The proposed method depends on two thresholds; phase angle shift (PAS) between two ends of an ISPST to discriminate internal faults and inrush conditions from normal, over-excitation, and external fault conditions and slope of differential current helps to discriminate the situation of internal fault from inrush. In the first step of the algorithm, the PAS-based threshold discriminates normal, over-excitation, and external fault conditions from magnetizing inrush and internal fault conditions. In the second step, the slope-based threshold discriminates magnetizing inrush from internal fault conditions. The reliability of the proposed method has also been examined under the condition of current transformer saturation due to heavy external faults. Additionally, the comparison of the suggested and conventional methods is discussed to check the superiority of the proposed method. The proposed method eliminates the need for phase angle shift correction in the suggested method. A variety of faults in the series and excitation unit are simulated using the PSCAD/EMTDC platform to verify the approach method.\",\"PeriodicalId\":33282,\"journal\":{\"name\":\"Journal of Engineering and Sustainable Development\",\"volume\":\"32 22\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2024-05-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Journal of Engineering and Sustainable Development\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.31272/jeasd.28.3.2\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of Engineering and Sustainable Development","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.31272/jeasd.28.3.2","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
摘要
本研究提出了一种在间接对称移相变压器(ISPST)的不同运行条件下限制差动继电器功能的方法。所提出的方法依赖于两个阈值:ISPST 两端之间的相位角偏移 (PAS),用于从正常、过励磁和外部故障条件中区分内部故障和浪涌条件;差动电流斜率有助于从浪涌中区分内部故障情况。在算法的第一步中,基于 PAS 的阈值将正常、过励磁和外部故障情况与磁化浪涌和内部故障情况区分开来。在第二步中,基于斜率的阈值将磁化浪涌与内部故障情况区分开来。在严重外部故障导致电流互感器饱和的情况下,也对所提方法的可靠性进行了检验。此外,还讨论了建议方法与传统方法的比较,以检验建议方法的优越性。建议的方法无需进行相位角偏移校正。使用 PSCAD/EMTDC 平台模拟了串联单元和励磁单元中的各种故障,以验证该方法。
PHASE ANGLE SHIFT AND SLOPE BASED RESTRAINT FOR INDIRECT SYMMETRICAL PHASE SHIFT TRANSFORMER PROTECTION
This study presents a method to limit the functioning of the differential relay during the different operating conditions of an Indirect Symmetrical Phase Shift Transformer (ISPST). The proposed method depends on two thresholds; phase angle shift (PAS) between two ends of an ISPST to discriminate internal faults and inrush conditions from normal, over-excitation, and external fault conditions and slope of differential current helps to discriminate the situation of internal fault from inrush. In the first step of the algorithm, the PAS-based threshold discriminates normal, over-excitation, and external fault conditions from magnetizing inrush and internal fault conditions. In the second step, the slope-based threshold discriminates magnetizing inrush from internal fault conditions. The reliability of the proposed method has also been examined under the condition of current transformer saturation due to heavy external faults. Additionally, the comparison of the suggested and conventional methods is discussed to check the superiority of the proposed method. The proposed method eliminates the need for phase angle shift correction in the suggested method. A variety of faults in the series and excitation unit are simulated using the PSCAD/EMTDC platform to verify the approach method.