两级和三级低温循环的火用分析

IF 5.8 4区 工程技术 Q1 MECHANICS Applied Rheology Pub Date : 2022-01-01 DOI:10.1515/arh-2022-0134
Musa Atasbak, Arzu Keven, Rabi Karaali̇
{"title":"两级和三级低温循环的火用分析","authors":"Musa Atasbak, Arzu Keven, Rabi Karaali̇","doi":"10.1515/arh-2022-0134","DOIUrl":null,"url":null,"abstract":"Abstract Cryogenics has an important influence on industry and science. In this study, optimum working conditions are obtained by applying exergy analysis and local optimization methods to two- and three-stage vapor compression cascade cryogenic cycle. The first and second laws of thermodynamics, exergy analysis, and local optimization methods are applied to the two- and three-stage cascade cryogenic cycle. By considering the needs and demands, it is possible to create new cycles by adding new devices and/or new stages to these cycles. The results of the optimum operating conditions are obtained for the two- and three-stage vapor compression cascade cryogenic cycle. It is seen that to achieve high COP values and high efficiency; it is necessary to reduce the compression ratio of the compressor as much as the fluid allows. For the two-stage cycle, the minimum total work required for cryogenic cooling is around P 7 = 2,400 kPa. The COP value is 0.30 between P 7 = 2,400 and 2,800 kPa, and the maximum exergy efficiency is obtained around 0.235. It is seen operating the first-stage compressor at high pressures increases the total losses of the entire cycle from 7,500 to 18,550 kW. The increase in total exergy losses is around 247%, and operating the first-stage compressor at high pressures increases the exergy efficiency of the entire cycle. The increase in total exergy efficiency is around 160%. When the second-stage compressor is operated at low pressure, the COP value increases by 2%, the exergy efficiency increases by 20%, and the exergy losses decrease by around 40%.","PeriodicalId":50738,"journal":{"name":"Applied Rheology","volume":"32 1","pages":"190 - 204"},"PeriodicalIF":5.8000,"publicationDate":"2022-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":"{\"title\":\"Exergy analyses of two and three stage cryogenic cycles\",\"authors\":\"Musa Atasbak, Arzu Keven, Rabi Karaali̇\",\"doi\":\"10.1515/arh-2022-0134\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Abstract Cryogenics has an important influence on industry and science. In this study, optimum working conditions are obtained by applying exergy analysis and local optimization methods to two- and three-stage vapor compression cascade cryogenic cycle. The first and second laws of thermodynamics, exergy analysis, and local optimization methods are applied to the two- and three-stage cascade cryogenic cycle. By considering the needs and demands, it is possible to create new cycles by adding new devices and/or new stages to these cycles. The results of the optimum operating conditions are obtained for the two- and three-stage vapor compression cascade cryogenic cycle. It is seen that to achieve high COP values and high efficiency; it is necessary to reduce the compression ratio of the compressor as much as the fluid allows. For the two-stage cycle, the minimum total work required for cryogenic cooling is around P 7 = 2,400 kPa. The COP value is 0.30 between P 7 = 2,400 and 2,800 kPa, and the maximum exergy efficiency is obtained around 0.235. It is seen operating the first-stage compressor at high pressures increases the total losses of the entire cycle from 7,500 to 18,550 kW. The increase in total exergy losses is around 247%, and operating the first-stage compressor at high pressures increases the exergy efficiency of the entire cycle. The increase in total exergy efficiency is around 160%. When the second-stage compressor is operated at low pressure, the COP value increases by 2%, the exergy efficiency increases by 20%, and the exergy losses decrease by around 40%.\",\"PeriodicalId\":50738,\"journal\":{\"name\":\"Applied Rheology\",\"volume\":\"32 1\",\"pages\":\"190 - 204\"},\"PeriodicalIF\":5.8000,\"publicationDate\":\"2022-01-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"1\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Applied Rheology\",\"FirstCategoryId\":\"5\",\"ListUrlMain\":\"https://doi.org/10.1515/arh-2022-0134\",\"RegionNum\":4,\"RegionCategory\":\"工程技术\",\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q1\",\"JCRName\":\"MECHANICS\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Applied Rheology","FirstCategoryId":"5","ListUrlMain":"https://doi.org/10.1515/arh-2022-0134","RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q1","JCRName":"MECHANICS","Score":null,"Total":0}
引用次数: 1

摘要

低温学对工业和科学有着重要的影响。在本研究中,采用火用分析和局部优化方法对二级和三级蒸汽压缩叶栅低温循环进行了优化。将热力学第一定律和第二定律、火用分析和局部优化方法应用于二级和三级串级低温循环。通过考虑需求和要求,可以通过在这些循环中添加新设备和/或新阶段来创建新的循环。得到了二级和三级蒸汽压缩叶栅低温循环的最佳操作条件。可以看出,要实现高COP值和高效率;有必要在流体允许的范围内尽量降低压缩机的压缩比。对于两级循环,低温冷却所需的最小总功约为p7 = 2,400 kPa。在p7 = 2400 ~ 2800 kPa范围内,COP值为0.30,火用效率在0.235左右达到最大值。在高压下运行第一级压缩机,整个循环的总损失从7500千瓦增加到18550千瓦。总的火用损失增加了247%左右,在高压下运行第一级压缩机提高了整个循环的火用效率。总能源效率提高约160%。当二级压缩机低压运行时,COP值提高2%,火用效率提高20%,火用损失降低40%左右。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Exergy analyses of two and three stage cryogenic cycles
Abstract Cryogenics has an important influence on industry and science. In this study, optimum working conditions are obtained by applying exergy analysis and local optimization methods to two- and three-stage vapor compression cascade cryogenic cycle. The first and second laws of thermodynamics, exergy analysis, and local optimization methods are applied to the two- and three-stage cascade cryogenic cycle. By considering the needs and demands, it is possible to create new cycles by adding new devices and/or new stages to these cycles. The results of the optimum operating conditions are obtained for the two- and three-stage vapor compression cascade cryogenic cycle. It is seen that to achieve high COP values and high efficiency; it is necessary to reduce the compression ratio of the compressor as much as the fluid allows. For the two-stage cycle, the minimum total work required for cryogenic cooling is around P 7 = 2,400 kPa. The COP value is 0.30 between P 7 = 2,400 and 2,800 kPa, and the maximum exergy efficiency is obtained around 0.235. It is seen operating the first-stage compressor at high pressures increases the total losses of the entire cycle from 7,500 to 18,550 kW. The increase in total exergy losses is around 247%, and operating the first-stage compressor at high pressures increases the exergy efficiency of the entire cycle. The increase in total exergy efficiency is around 160%. When the second-stage compressor is operated at low pressure, the COP value increases by 2%, the exergy efficiency increases by 20%, and the exergy losses decrease by around 40%.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
Applied Rheology
Applied Rheology 物理-力学
CiteScore
3.00
自引率
5.60%
发文量
7
审稿时长
>12 weeks
期刊介绍: Applied Rheology is a peer-reviewed, open access, electronic journal devoted to the publication in the field of applied rheology. The journal provides the readers with free, instant, and permanent access to all content worldwide; and the authors with extensive promotion of published articles, long-time preservation, language-correction services, no space constraints and immediate publication.
期刊最新文献
Prediction of sensory textures of cosmetics using large amplitude oscillatory shear and extensional rheology Viscoplastic fluid flow in pipes: A rheological study using in-situ laser Doppler velocimetry Structural damage characteristics and mechanism of granite residual soil Rheological characteristics and seepage laws of sandstone specimens containing an inclined single fracture under three-dimensional stress Computational analysis of nanoparticles and waste discharge concentration past a rotating sphere with Lorentz forces
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1