{"title":"光伏发电并网微电网过流保护分析与设计","authors":"Jaymala D. Pradhan , Somnath S. Hadpe , Rakesh G. Shriwastava","doi":"10.1016/j.gltp.2022.03.023","DOIUrl":null,"url":null,"abstract":"<div><p>This paper aimed to demonstrate the reliability of the Over Current protection (OCP) scheme in protecting microgrids with inverter interfaced RES for low voltage distribution networks. To prove this reliability, the PSCAD/EMTDC simulation software was used to conduct simulations for the OCP scheme, while comparing throughout grid-connected mode with and without PV generation, as well as in island mode. The computations are carried out using a model of a CIGRE low voltage distribution system. The OCP average relay tripping time for SLG faults through grid mode without PV has been 0.131 s, & 0.121 s for LLL faults. With regards to PV generators, the average relay tripping time increased to 0.199 s & 0.135 s, including both. This is due to the fault current contributed by PV generation inclusion, which restricts the current seen by the predefined OC relays. The findings revealed that some OC relays failed to trip in island mode causing a loss of coordination and a decrease in fault currents. The system was further tested for different generation levels (15%, 57%, and 81%) in island mode and gave a negligible difference in average tripping time for different generation levels.</p></div>","PeriodicalId":100588,"journal":{"name":"Global Transitions Proceedings","volume":"3 1","pages":"Pages 349-358"},"PeriodicalIF":0.0000,"publicationDate":"2022-06-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://www.sciencedirect.com/science/article/pii/S2666285X22000292/pdfft?md5=62cd1d590c4e97d34fafbd62240ee9b1&pid=1-s2.0-S2666285X22000292-main.pdf","citationCount":"3","resultStr":"{\"title\":\"Analysis and design of overcurrent protection for grid-connected microgrid with PV generation\",\"authors\":\"Jaymala D. Pradhan , Somnath S. Hadpe , Rakesh G. Shriwastava\",\"doi\":\"10.1016/j.gltp.2022.03.023\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"<div><p>This paper aimed to demonstrate the reliability of the Over Current protection (OCP) scheme in protecting microgrids with inverter interfaced RES for low voltage distribution networks. To prove this reliability, the PSCAD/EMTDC simulation software was used to conduct simulations for the OCP scheme, while comparing throughout grid-connected mode with and without PV generation, as well as in island mode. The computations are carried out using a model of a CIGRE low voltage distribution system. The OCP average relay tripping time for SLG faults through grid mode without PV has been 0.131 s, & 0.121 s for LLL faults. With regards to PV generators, the average relay tripping time increased to 0.199 s & 0.135 s, including both. This is due to the fault current contributed by PV generation inclusion, which restricts the current seen by the predefined OC relays. The findings revealed that some OC relays failed to trip in island mode causing a loss of coordination and a decrease in fault currents. The system was further tested for different generation levels (15%, 57%, and 81%) in island mode and gave a negligible difference in average tripping time for different generation levels.</p></div>\",\"PeriodicalId\":100588,\"journal\":{\"name\":\"Global Transitions Proceedings\",\"volume\":\"3 1\",\"pages\":\"Pages 349-358\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2022-06-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"https://www.sciencedirect.com/science/article/pii/S2666285X22000292/pdfft?md5=62cd1d590c4e97d34fafbd62240ee9b1&pid=1-s2.0-S2666285X22000292-main.pdf\",\"citationCount\":\"3\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Global Transitions Proceedings\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://www.sciencedirect.com/science/article/pii/S2666285X22000292\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Global Transitions Proceedings","FirstCategoryId":"1085","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S2666285X22000292","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3
摘要
本文旨在证明过流保护(OCP)方案在保护低压配电网中具有逆变器接口的微电网中的可靠性。为了证明这种可靠性,使用PSCAD/EMTDC仿真软件对OCP方案进行了仿真,同时比较了整个并网模式下有和没有光伏发电以及孤岛模式下的情况。利用CIGRE低压配电系统模型进行了计算。无PV电网模式下SLG故障的OCP平均继电器脱扣时间为0.131 s;LLL故障为0.121 s。光伏发电机组的平均继电器脱扣时间增加到0.199 s &0.135秒,包括两者。这是由于光伏发电产生的故障电流,它限制了预定义的OC继电器看到的电流。研究结果表明,一些OC继电器在孤岛模式下未能跳闸,导致协调损失和故障电流减少。在孤岛模式下,对系统进行了不同发电水平(15%、57%和81%)的进一步测试,不同发电水平的平均跳闸时间差异可以忽略不计。
Analysis and design of overcurrent protection for grid-connected microgrid with PV generation
This paper aimed to demonstrate the reliability of the Over Current protection (OCP) scheme in protecting microgrids with inverter interfaced RES for low voltage distribution networks. To prove this reliability, the PSCAD/EMTDC simulation software was used to conduct simulations for the OCP scheme, while comparing throughout grid-connected mode with and without PV generation, as well as in island mode. The computations are carried out using a model of a CIGRE low voltage distribution system. The OCP average relay tripping time for SLG faults through grid mode without PV has been 0.131 s, & 0.121 s for LLL faults. With regards to PV generators, the average relay tripping time increased to 0.199 s & 0.135 s, including both. This is due to the fault current contributed by PV generation inclusion, which restricts the current seen by the predefined OC relays. The findings revealed that some OC relays failed to trip in island mode causing a loss of coordination and a decrease in fault currents. The system was further tested for different generation levels (15%, 57%, and 81%) in island mode and gave a negligible difference in average tripping time for different generation levels.