{"title":"Corrosion and Current Burst Testing of Copper and Aluminum Electrical Power Connectors","authors":"V. Buccholz, R. Frank, C. Morton","doi":"10.1109/TDC.2006.1668638","DOIUrl":null,"url":null,"abstract":"Crimped and mechanically bolted aluminum and copper connectors are commonly used for terminating industrial electrical power cables of ratings up to 600 V. Aluminum connectors are available for use with aluminum or copper conductor, and copper connectors are available for use with copper conductor only. The performance of copper and aluminum connectors was compared by accelerated aging under corrosive environmental conditions. The testing consisted of 2000 hours of cyclic salt fog environmental exposure, in conjunction with periodic electrical current burst testing. The connectors were evaluated by comparing the change in resistance of the test samples as the test progressed","PeriodicalId":123024,"journal":{"name":"2005/2006 IEEE/PES Transmission and Distribution Conference and Exhibition","volume":"30 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-05-21","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2005/2006 IEEE/PES Transmission and Distribution Conference and Exhibition","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/TDC.2006.1668638","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1
Abstract
Crimped and mechanically bolted aluminum and copper connectors are commonly used for terminating industrial electrical power cables of ratings up to 600 V. Aluminum connectors are available for use with aluminum or copper conductor, and copper connectors are available for use with copper conductor only. The performance of copper and aluminum connectors was compared by accelerated aging under corrosive environmental conditions. The testing consisted of 2000 hours of cyclic salt fog environmental exposure, in conjunction with periodic electrical current burst testing. The connectors were evaluated by comparing the change in resistance of the test samples as the test progressed