AEP experience with protection of three delta/hex phase angle regulating transformers

M. Thompson, H. Miller, J. Burger
{"title":"AEP experience with protection of three delta/hex phase angle regulating transformers","authors":"M. Thompson, H. Miller, J. Burger","doi":"10.1109/CPRE.2007.359896","DOIUrl":null,"url":null,"abstract":"American Electric Power installed three 138 kV, 150 MVA delta/hex phase angle regulating (PAR) transformers on the south Texas transmission grid during 2006. These transformers help optimize power flow on the transmission grid until planned 345 kV line construction projects can be completed to improve the strength of the grid in this portion of the power system. The delta/hex PAR transformer is a new single-tank design that promises to be much more economical to build and install than previous designs - improving the economic viability of deployment of these devices on the transmission grid. This paper addresses the challenges of providing fully redundant, sensitive, and secure protection for all types of faults, including turn-to-turn faults in this type of transformer and its surrounding bus work. The protection system includes a mix of conventional protection concepts and a completely new differential protection system that can compensate for the variable phase angle shift introduced by operation of the PAR transformer. The complete protection system was tested using digital model power system transient testing prior to installation in the field.","PeriodicalId":114949,"journal":{"name":"2007 Power Systems Conference: Advanced Metering, Protection, Control, Communication, and Distributed Resources","volume":"40 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2007-03-27","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"15","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2007 Power Systems Conference: Advanced Metering, Protection, Control, Communication, and Distributed Resources","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CPRE.2007.359896","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 15

Abstract

American Electric Power installed three 138 kV, 150 MVA delta/hex phase angle regulating (PAR) transformers on the south Texas transmission grid during 2006. These transformers help optimize power flow on the transmission grid until planned 345 kV line construction projects can be completed to improve the strength of the grid in this portion of the power system. The delta/hex PAR transformer is a new single-tank design that promises to be much more economical to build and install than previous designs - improving the economic viability of deployment of these devices on the transmission grid. This paper addresses the challenges of providing fully redundant, sensitive, and secure protection for all types of faults, including turn-to-turn faults in this type of transformer and its surrounding bus work. The protection system includes a mix of conventional protection concepts and a completely new differential protection system that can compensate for the variable phase angle shift introduced by operation of the PAR transformer. The complete protection system was tested using digital model power system transient testing prior to installation in the field.
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
具有3台三角/六角角调节变压器的AEP保护经验
2006年,美国电力公司在南德克萨斯州输电网安装了3台138千伏、150 MVA的三角/六角相角调节(PAR)变压器。这些变压器有助于优化输电网的潮流,直到计划的345千伏线路建设项目完成,以提高电力系统这部分电网的强度。delta/hex PAR变压器是一种新的单罐设计,与以前的设计相比,它的建造和安装更加经济,提高了这些设备在输电网上部署的经济可行性。本文解决了为所有类型的故障提供完全冗余,敏感和安全保护的挑战,包括这种类型的变压器及其周围母线工作中的匝间故障。该保护系统包括传统保护概念和一个全新的差动保护系统的混合,可以补偿由PAR变压器的操作引入的可变相角偏移。在现场安装前,采用数字模型电力系统暂态测试对整个保护系统进行了测试。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
AEP experience with protection of three delta/hex phase angle regulating transformers High-speed control scheme to prevent instability of a large multi-unit power plan Tutorial: From the Steinmetz model to the protection of high inertia drives Mitigation of subsynchronous oscillations in a series compensated wind farm with Thyristor Controlled Series Capacitor (TCSC) Precise distance to fault locator with two end phasor measurement transmitted via serial protection data interface
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1