配线柜接线的接触电阻和温升

E. Fjeld, W. Rondeel, Gunn Kristin Sønsteby, Finn Werner Bekken, Thomas Ranvik Eriksen
{"title":"配线柜接线的接触电阻和温升","authors":"E. Fjeld, W. Rondeel, Gunn Kristin Sønsteby, Finn Werner Bekken, Thomas Ranvik Eriksen","doi":"10.1109/HLM49214.2020.9307905","DOIUrl":null,"url":null,"abstract":"Initiated by a number of fire accidents in the low voltage switchgear in cable distribution cabinets, investigations have been performed to identify the cause of these fires. The results indicate that the cable connection was likely to be the cause of the problems, rather than overheating of the fuse links accommodated in the fuse switch disconnector modules. In the relevant equipment, the cable is connected with a cable clamp tightened with a specified torque. However, it was found that by mechanically stressing the cable (moving the cable in order to connect another phase), the individual strands of the cable conductor might be displaced and the contact pressure reduced. Based on these findings, laboratory testing have been done, investigating how contact resistance and temperature rise of the cable connection might vary with the practical execution. The results seems to indicate that applying a cable lug connection could be a more reliable solution. Finally, measurement of temperature rise of properly installed cable connections in the field are made by applying miniature wireless sensor elements. The findings show that during a relatively mild Norwegian winter (ambient temperatures between -5–5°C) the temperature rise of the cable connection is far below the relevant temperature limits of such contacts set by the IEC 60439-1.","PeriodicalId":268345,"journal":{"name":"2020 IEEE 66th Holm Conference on Electrical Contacts and Intensive Course (HLM)","volume":"13 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2020-09-30","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Contact Resistance and Temperature Rise of Cable Connections in Cable Distribution Cabinets\",\"authors\":\"E. Fjeld, W. Rondeel, Gunn Kristin Sønsteby, Finn Werner Bekken, Thomas Ranvik Eriksen\",\"doi\":\"10.1109/HLM49214.2020.9307905\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Initiated by a number of fire accidents in the low voltage switchgear in cable distribution cabinets, investigations have been performed to identify the cause of these fires. The results indicate that the cable connection was likely to be the cause of the problems, rather than overheating of the fuse links accommodated in the fuse switch disconnector modules. In the relevant equipment, the cable is connected with a cable clamp tightened with a specified torque. However, it was found that by mechanically stressing the cable (moving the cable in order to connect another phase), the individual strands of the cable conductor might be displaced and the contact pressure reduced. Based on these findings, laboratory testing have been done, investigating how contact resistance and temperature rise of the cable connection might vary with the practical execution. The results seems to indicate that applying a cable lug connection could be a more reliable solution. Finally, measurement of temperature rise of properly installed cable connections in the field are made by applying miniature wireless sensor elements. The findings show that during a relatively mild Norwegian winter (ambient temperatures between -5–5°C) the temperature rise of the cable connection is far below the relevant temperature limits of such contacts set by the IEC 60439-1.\",\"PeriodicalId\":268345,\"journal\":{\"name\":\"2020 IEEE 66th Holm Conference on Electrical Contacts and Intensive Course (HLM)\",\"volume\":\"13 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2020-09-30\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2020 IEEE 66th Holm Conference on Electrical Contacts and Intensive Course (HLM)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/HLM49214.2020.9307905\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2020 IEEE 66th Holm Conference on Electrical Contacts and Intensive Course (HLM)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/HLM49214.2020.9307905","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

由一系列电缆配电柜低压开关设备的火灾事故引发,调查已进行,以确定这些火灾的原因。结果表明,电缆连接很可能是问题的原因,而不是过热的熔断器连接容纳在熔断器开关隔离模块。在相关设备中,电缆是用规定扭矩拧紧的电缆夹连接的。然而,人们发现,通过机械地给电缆施加压力(移动电缆以连接另一相),电缆导体的个别股可能会移位,接触压力会降低。基于这些发现,已经进行了实验室测试,研究电缆连接的接触电阻和温升如何随实际执行而变化。结果似乎表明,应用电缆耳连接可能是一个更可靠的解决方案。最后,利用微型无线传感器元件对现场正确安装的电缆接头进行温升测量。研究结果表明,在挪威相对温和的冬季(环境温度在-5-5°C之间),电缆连接的温升远低于IEC 60439-1规定的此类触点的相关温度限制。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Contact Resistance and Temperature Rise of Cable Connections in Cable Distribution Cabinets
Initiated by a number of fire accidents in the low voltage switchgear in cable distribution cabinets, investigations have been performed to identify the cause of these fires. The results indicate that the cable connection was likely to be the cause of the problems, rather than overheating of the fuse links accommodated in the fuse switch disconnector modules. In the relevant equipment, the cable is connected with a cable clamp tightened with a specified torque. However, it was found that by mechanically stressing the cable (moving the cable in order to connect another phase), the individual strands of the cable conductor might be displaced and the contact pressure reduced. Based on these findings, laboratory testing have been done, investigating how contact resistance and temperature rise of the cable connection might vary with the practical execution. The results seems to indicate that applying a cable lug connection could be a more reliable solution. Finally, measurement of temperature rise of properly installed cable connections in the field are made by applying miniature wireless sensor elements. The findings show that during a relatively mild Norwegian winter (ambient temperatures between -5–5°C) the temperature rise of the cable connection is far below the relevant temperature limits of such contacts set by the IEC 60439-1.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
The Relationship between Contact Resistance and Roughness (Sq) of a Bi-layered Surface using a Finite Element Model Experimental Investigation of Alternating Current Arc Behavior and Associated Contact Welding Failure for General-purpose Relay Impact of the Ball Grid Array Connection Failures on Signal Integrity HLM 2020 Commmittees 3D Simulation of Electric Arcing and Pressure increase in an Automotive HVDC Relay During a Short Circuit Situation
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1