三电平v接整流-逆变系统传导噪声的实验验证

J. Itoh, H. D. Minh, D. Sato
{"title":"三电平v接整流-逆变系统传导噪声的实验验证","authors":"J. Itoh, H. D. Minh, D. Sato","doi":"10.1109/EPEPEMC.2014.6980552","DOIUrl":null,"url":null,"abstract":"This paper discusses the conduction noise reduction possibility of a transformer-less three-level V-connection rectifier-inverter system. This circuit is used for the main circuit in an Uninterruptible Power Supply (UPS) system. The efficiency of this circuit is higher than that of the conventional three-phase rectifier-inverter circuit due to no isolated transformer in output side. In this paper, to verify the conduction noise of the V-connection system, a theoretical analysis about the common-mode currents which based on the common-mode equivalent circuit, is discussed. Based on this, the comparison of the conduction noise between the three-level V-connection Back To Back (BTB) system and the conventional three-level three-phase connection BTB system is assumed. In addition, the conduction noise of two systems are measured and compared in order to confirm the assumption. As a result, it is confirmed that the conduction noise which is generated from the three-level V-connection rectifier-inverter circuit is higher than that of the conventional three-phase rectifier-inverter circuit.","PeriodicalId":325670,"journal":{"name":"2014 16th International Power Electronics and Motion Control Conference and Exposition","volume":"10 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2014-12-11","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"3","resultStr":"{\"title\":\"Experimental verification of conduction noise of three-level V-connection rectifier-inverter system\",\"authors\":\"J. Itoh, H. D. Minh, D. Sato\",\"doi\":\"10.1109/EPEPEMC.2014.6980552\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"This paper discusses the conduction noise reduction possibility of a transformer-less three-level V-connection rectifier-inverter system. This circuit is used for the main circuit in an Uninterruptible Power Supply (UPS) system. The efficiency of this circuit is higher than that of the conventional three-phase rectifier-inverter circuit due to no isolated transformer in output side. In this paper, to verify the conduction noise of the V-connection system, a theoretical analysis about the common-mode currents which based on the common-mode equivalent circuit, is discussed. Based on this, the comparison of the conduction noise between the three-level V-connection Back To Back (BTB) system and the conventional three-level three-phase connection BTB system is assumed. In addition, the conduction noise of two systems are measured and compared in order to confirm the assumption. As a result, it is confirmed that the conduction noise which is generated from the three-level V-connection rectifier-inverter circuit is higher than that of the conventional three-phase rectifier-inverter circuit.\",\"PeriodicalId\":325670,\"journal\":{\"name\":\"2014 16th International Power Electronics and Motion Control Conference and Exposition\",\"volume\":\"10 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2014-12-11\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"3\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2014 16th International Power Electronics and Motion Control Conference and Exposition\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/EPEPEMC.2014.6980552\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2014 16th International Power Electronics and Motion Control Conference and Exposition","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/EPEPEMC.2014.6980552","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3

摘要

本文讨论了一种无变压器的三电平v接整逆变系统降低传导噪声的可能性。该电路用于UPS (uninterrupted Power Supply)系统的主电路。由于输出侧无隔离变压器,该电路的效率高于传统的三相整逆变电路。为了验证v型连接系统的传导噪声,本文基于共模等效电路对共模电流进行了理论分析。在此基础上,对三电平v接背对背(BTB)系统与传统三电平三相接BTB系统的传导噪声进行了比较假设。此外,还对两种系统的传导噪声进行了测量和比较,以验证上述假设。结果证实,三电平v接整流-逆变电路产生的传导噪声高于常规三相整流-逆变电路。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Experimental verification of conduction noise of three-level V-connection rectifier-inverter system
This paper discusses the conduction noise reduction possibility of a transformer-less three-level V-connection rectifier-inverter system. This circuit is used for the main circuit in an Uninterruptible Power Supply (UPS) system. The efficiency of this circuit is higher than that of the conventional three-phase rectifier-inverter circuit due to no isolated transformer in output side. In this paper, to verify the conduction noise of the V-connection system, a theoretical analysis about the common-mode currents which based on the common-mode equivalent circuit, is discussed. Based on this, the comparison of the conduction noise between the three-level V-connection Back To Back (BTB) system and the conventional three-level three-phase connection BTB system is assumed. In addition, the conduction noise of two systems are measured and compared in order to confirm the assumption. As a result, it is confirmed that the conduction noise which is generated from the three-level V-connection rectifier-inverter circuit is higher than that of the conventional three-phase rectifier-inverter circuit.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
Keynote 1: Is GaN a Game Changing Device ? Reactive power control of wind turbines A wireless energy transceiver based on induction heating equipment Real time symmetrical coordinate transformation applied for detection of imbalanced fault in utility power system Neural speed controller based on two state variables applied for a drive with elastic connection
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1